CHA-M/Y 1202÷2003
Aircooled liquid Chillers and Heat Pumps with axial fans, Screw compressors and shell and tube exchanger









The liquid Chillers and Heat Pumps of CHA-M/Y 1202÷2002 ENERGYMAX series, with R134a refrigerant, are designed for large service sector or industrial-type ambients. They are used, in combination with terminal units, for the air conditioning of the rooms or to remove the heat developed during industrial processes.
They are equipped with axial fans, Screw compressors and shell and tube exchanger. The use of large size condensing coils, together with fans with high unit efficiency, as well as the optimization of the hydraulic and cooling circuit and the use of latest generation Screw compressors, combined with a suitable sizing of the user system, allows to obtain high efficiency during operation with remarkably reduced energy consumption.
A wide range of accessories, factory fitted or supplied separately, complete the outstanding versatility and functionality of the series.
Versionen
- CHA-M/Y - Cooling only
- CHA-M/Y/WP - Reversible Heat Pump
Power range
- 240-484 kW
- 68,0-138 Ton
Merkmale
- Structure with supporting frame, made of galvanised sheet metal with additional protection provided by polyester powder coating.
- Screw compressors with built-in oil separator, suction filter, crankcase heater, oil sight glass, thermal protection, hot gas shut off valves and capacity steps.
- Axial fans directly coupled to an electric motor with external rotor.
- Condenser made of copper tubes and aluminium finned coils.
- Shell and tube type evaporator, with two independent circuits on the refrigerant side and one on the water side.
- Electronic expansion valve.
- R134a refrigerant.
- Electrical board includes: main switch with door safety interlock, protection modules, overload protection for compressors and thermocontacts for fans.
- Condensing control included, allows to reach up to 0 °C external air temperature.
- Microprocessor control and regulation system.
Zubehör
Im Werk montiertes Zubehör
- RZ Stufenlose Drosselung der Verdichter
- BT Ausführung für Betrieb mit niedriger Wassertemperatur
- HR Enthitzer
- HRT/S Vollständige Wärmerückgewinnung, seriell angeordnet
- TX Register mit vorbeschichteten Lamellen
- FE Frostschutzheizung für Verdampfer
- II Inverter auf einem Verdichter und Soft Start auf anderen Verdichter
- ID Inverter auf allen Verdichtern
- SS Soft Starter
- WM Web Monitoring - Drahtlose Fernüberwachung (GPRS/EDGE/3G/TCP-IP)
- AD Trennwand Geräteteil Luft
- IS Modbus RTU-Protokoll, serielle Schnittstelle RS485
- CP Potentialfreie Kontakte
Lose mitgeliefertes Zubehör
- MN Hoch- und Niederdruckmanometer
- CR Fernbedienung
- AM Federschwingungsdämpfer
- RP Schutzgitter Verflüssigerregister
- AG Gummi-Schwingungsdämpfer
- FL Strömungswächter
Technical data
1202 | 1302 | 1502 | 1702 | 1902 | 2002 | |||
Kühlung | Kühlleistung (1) | kW | 240 | 276 | 313 | 368 | 423 | 484 |
Leistungsaufnahme (1) | kW | 85,1 | 100 | 111 | 131 | 152 | 183 | |
EER (1) | 2,82 | 2,76 | 2,82 | 2,81 | 2,78 | 2,64 | ||
Kühlung (EN14511) | Kühlleistung (1) | kW | 239 | 275 | 312 | 366 | 421 | 482 |
Leistungsaufnahme (1) | kW | 86,1 | 101 | 112 | 133 | 154 | 185 | |
EER (1) | 2,78 | 2,74 | 2,79 | 2,75 | 2,73 | 2,61 | ||
Heizung | Heizleistung (2) | kW | 271 | 302 | 348 | 403 | 466 | 541 |
Leistungsaufnahme (2) | kW | 88,6 | 99,7 | 112 | 130 | 149 | 178 | |
COP (2) | 3,04 | 3,03 | 3,11 | 3,10 | 3,13 | 3,04 | ||
Heizung (EN14511) | Heizleistung (2) | kW | 272 | 303 | 350 | 405 | 468 | 544 |
Leistungsaufnahme (2) | kW | 91,1 | 102 | 116 | 135 | 154 | 184 | |
COP (2) | 2,99 | 2,97 | 3,02 | 3,00 | 3,04 | 2,96 | ||
Verdichter | Anzahl | n° | 2 | 2 | 2 | 2 | 2 | 2 |
Kältekreisläufe | n° | 2 | 2 | 2 | 2 | 2 | 2 | |
Leistungsstufen | n° | 6 | 6 | 6 | 6 | 6 | 6 | |
Verdampfer | Wassermenge | l/s | 11,47 | 13,19 | 14,95 | 17,58 | 20,21 | 23,12 |
Druckverluste | kPa | 46 | 47 | 53 | 67 | 53 | 60 | |
Wasseranschlüsse | DN | 100 | 100 | 100 | 100 | 100 | 100 | |
Elektrische Merkmale | Versorgungsspannung | V/Ph/Hz | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 |
Max. Betriebsstrom | A | 212 | 250 | 278 | 334 | 363 | 434 | |
Max. Anlaufstrom | A | 277 | 371 | 385 | 444 | 518 | 611 | |
Schalldruck | Version STD (3) | dB(A) | 76 | 76 | 75 | 77 | 77 | 77 |
Gewichte | Transportgewicht | kg | 2475 | 2842 | 3083 | 3262 | 3500 | 3927 |
Betriebsgewicht | kg | 2640 | 3000 | 3280 | 3450 | 3690 | 4250 |
Dimensions
1202 | 1302 | 1502 | 1702 | 1902 | 2002 | |||
L | STD | mm | 2800 | 2800 | 3900 | 3900 | 3900 | 3900 |
W | STD | mm | 2200 | 2200 | 2200 | 2200 | 2200 | 2200 |
H | STD | mm | 2100 | 2100 | 2100 | 2100 | 2100 | 2100 |
Aufzeichnungen
- 1 Kaltwasser von 12 bis7 °C, Außenlufttemperatur 35 °C.
- 2 Warmwasser von 40 bis 45 °C, Außenlufttemperatur 7 °C T.K./6 °C F.K.
- 3 Durchschnittlicher Schalldruckpegel im Freifeld im Abstand von 1 m zur Einheit, gemäß ISO 3744.
- N.B. (1) Die Gewichte der Version WP sind in den technischen Unterlagen aufgeführt.
Dokumente
- Produktübersicht 00_clint_international_product_over_09.2019_w.pdf
- Produkthandbücher _clint_international_product_guide_09.2019_w.pdf
- Kommerzielle Broschüre 04_clint_international_leaflet_energymax_09.2019_w.pdf
- Technischen Unterlagen 07_CHA-M_Y_1202-2002_clbm_56.7.pdf
- Installations-, Bedienungs- und Wartungshandbücher CHA-MY_1202_2002_CLMM_56.7_J1mW6UD.pdf