logo_ECO-V-THERM_2024.png

clint tec_microchannel_2025.png

clint tec_R290_refrigeranti_2025.png

CHV/P/MC 152-P÷756-P

Air cooled liquid Chillers with axial fans, Scroll compressors and plate exchanger.

_icona_clint_solo_raffreddamento_2024.png _icona_clint_compressore_scroll_2024.png _icona_clint_fan_assiale_2024.png _icona_clint_exchanger_plate_2024.png _icona_clint_exchanger_microchannel_coil_2024.png _icona_clint_solution_A_class_cooling_2024.png _icona_clint_refrigerant_R290_2024.png

ECO V-THERM is the new range of air cooled liquid Chillers designed for high performance while respecting the environment.
The liquid Chillers of the CHV/P/HE/MC 152-P÷756-P series, with R290 refrigerant, are designed to satisfy the needs of medium-sized service sector or industrial ambients.
They are used, combined with Fan Coil units, for the air conditioning of the rooms.
Using the natural refrigerant R290, with an extremely low GWP, they meet current and future European environmental regulations, combining efficiency and sustainability.
Microchannel condensing coils minimise the amount of refrigerant required in the units.
The units are compliant to the ErP Regulation.

Versions

  • CHV/P/MC - Cooling only with MICROCHANNEL coils

Power range

  • 48.0-220 kW
  • 14.0-63.0 Ton

Features

  • Structure with supporting frame, made of galvanised sheet metal with additional protection provided by polyester powder coating.
  • Compressor box housed on the side of the unit opposite the electrical board ad equipped with an ATEX-certified extraction fan installed at the bottom of the compartment.
  • Scroll compressors with oil sight glass, internal overheat protection and crankcase heater.
  • Axial fans directly coupled to an electric motor with external rotor.
  • Condenser made up of aluminium Microchannel coils positioned in a V-shaped geometry.
  • Evaporator AISI 316 stainless steel braze welded plates type with one (mod. 152-P÷383-P) or two (mod. 404-P÷756-P) independent circuits on the refrigerant side and one on the water side.
  • Cooling circuit shut-off valve on liquid line.
  • Electronic expansion valve.
  • Electronic high and low pressure gauges.
  • R290 refrigerant.
  • The condensing control is included: electronic proportional device that ensures efficient and continuous functioning of the unit. It also allows to reduce the sound level especially at night. It consists of a fans speed controller with continuous speed regulation, an high/low pressure transducer on cooling circuit and an electrical heater on electrical board.
  • Electrical board includes: main switch with door safety interlock, automatic cirtcuit brakers, thermal protection relays for compressors and thermocontacts for fans.
  • Microprocessor control and regulation system.

Factory fitted accessories

  • RE Adjustable minimum/maximum voltage and phase control relay
  • SL Unit silencement
  • BT Low water temperature kit
  • BTA Low ambient air temperature kit
  • EC EC Inverter fans
  • DS Desuperheater
  • TXB Coil with epoxy treatment
  • SI Inertial tank
  • PS Single circulating pump
  • PSI Inverter single circulating pump
  • PD Double circulating pump
  • PDI Inverter double circulating pump
  • GS Single circulating pump gasket for glycol >30%
  • GD Double circulating pump gaskets for glycol >30%
  • FE Antifreeze heater for evaporator
  • FX Antifreeze heater for evaporator and pipes
  • FQ Antifreeze heater on evaporator, tank and pipes
  • FZ Antifreeze heater for evaporator, single pump and pipes
  • FH Antifreeze heater for evaporator, double pump and pipes
  • FU Antifreeze heater for evaporator, tank, single pump and pipes
  • FD Antifreeze heater for evaporator, tank, double pump and pipes
  • SS Soft start
  • WM Web Monitoring - Wireless remote monitoring (4G)
  • IS Modbus RTU protocol, RS485 serial interface
  • IST Modbus TCP/IP protocol, Ethernet port
  • ISB1 BACnet MSTP protocol, RS485 serial interface, BTL certified
  • ISBT1 BACnet IP protocol, Ethernet port, BTL certified
  • ISS SNMP protocol, Ethernet port
  • MTS Master/Slave Network Management
  • IAV Remote set-point, 0-10V signal
  • IAA Remote set-point, 4-20mA signal
  • IAS Remote signal for second set-point activation
  • IDL Demand limit from digital input
  • LDS Leak detection sensor R290
  • RP Coils protection metallic guards

Loose accessories

  • CR Remote control panel
  • FL Flow switch
  • AG Rubber shock absorbers
  • AM Spring shock absorbers
152-P182-P202-P252-P303-P383-P404-P504-P606-P756-P
CoolingCooling capacity (1)kW48,454,367,376,592,2110141152189220
Absorbed power (1)kW16,218,021,323,229,335,942,546,058,971,3
EER (1)2,993,023,163,303,153,063,323,303,213,09
Cooling (EN14511)Cooling capacity (1)kW48,354,267,276,492,0110141152189220
EER (1)2,952,983,133,263,113,043,283,263,183,05
SEER (2)4,104,124,134,124,134,114,194,164,214,18
Energy Efficiency (2)%161162162162162161165163165164
CompressorQuantity2222334466
Refrigerant circuits1111112222
Capacity steps2222334466
EvaporatorWater flowl/s2,312,593,213,654,395,246,727,249,0110,50
Pressure dropskPa26,726,020,321,226,215,027,230,622,825,3
Water connectionsDN2"2"2"2"2"2"2"1/22"1/23"3"
Electrical characteristicsPower supplyV/Ph/Hz400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50
Max. running currentA5256637491108126149182215
Max. starting currentA175175183238210271246313301379
Unit with pumpPump available static pressurekPa158154149139118109168159147126
Water connectionsDN2"2"2"2"2"2"2"1/22"1/23"3"
Sound powerSTD version (3)dB(A)83838585868688888989
With SL accessory (3)dB(A)82828484858586868787
WeightsTransport weightkg80781610651074114311621896190620712096
Operating weightkg81082010701080115011701910192020902120

Dimensions

152-P182-P202-P252-P303-P383-P404-P504-P606-P756-P
LSTDmm1600160026002600260026005000500050005000
WSTDmm1350135013501350135013501350135013501350
HSTDmm2160216021602160216021602160216021602160

Notes

  • 1 Chilled water from 12 to 7 °C, ambient air temperature 35 °C.
  • 2 Seasonal energy efficiency of cooling at low temperature. According to EU Regulation n. 2016/2281.