Aircooled liquid Chillers Free-Cooling with axial fans, Scroll compressor and plate exchanger

SOLO_FREDDO.png COMPRESSORE_SCROLL111.png ASSIALE11.png SCAMBIATORE_PIASTRE11.png ICONA_FC.png R410A1.png

The liquid Chillers of the CHA/K/FC 91÷151 series, with R410A refrigerant, offer innovative technology to meet the needs of systems for both domestic as well as industrial applications requiring the production of cooled water continuously year-round.
During the cold months, in the FREE-COOLING operation mode, the return liquid of the system is cooled directly by forced convection of outdoor air through the condensing coil, thus saving energy by not operating the unit's Scroll compressors. A 3-way valve system is controlled by the electronic microprocessor controller, allowing functioning in CHILLER, FREE-COOLING or MIXED (simultaneously CHILLER and FREE-COOLING) modes.
The units are compliant to the 2021 ErP Regulation for process cooling application.

Versions

  • CHA/K/FC - Cooling only
  • CHA/K/FC/SP - Cooling only with tank and pump

Power range

  • 28.0-43.0 kW
  • 7.9-12.0 Ton

Features

  • Structure with supporting frame, made of galvanised sheet metal with additional protection provided by polyester powder coating.
  • Scroll compressors with oil sight glass, internal overheat protection and crankcase heater.
  • Axial fans with low ventilation and special wing profile, directly coupled to external rotor motors.
  • Condenser made of copper tubes and aluminium finned coil combined with FREE-COOLING coil.
  • Evaporator AISI 316 stainless steel braze welded plates type, complete with water differential pressure switch.
  • R410A refrigerant.
  • Electrical board includes: main switch with door lock device, fuses, compressor and pump remote control switch.
  • Condensing Control is included: electronic proportional device that ensures efficient and continuous functioning of the unit with outside air temperature down to –20 °C. It also allows to reduce the sound level especially at night. It consists of a fans speed controller with continuous speed regulation, high and low pressure transducers on cooling circuit and an electrical heater on electrical board.
  • Water circuit for SP version includes: insulated tank, circulating pump, safety valve, gauge and expansion vessel.
  • Microprocessor control and regulation system.

Factory fitted accessories

  • BT Low water temperature kit
  • TX Coil with pre-coated fins
  • PS Single circulating pump

Loose accessories

  • CR Remote control panel
  • IS Modbus RTU protocol, RS485 serial interface
  • RP Coils protection metallic guards
  • AG Rubber shock absorbers
91101131151
CoolingCooling capacity (1)kW27,931,437,342,8
Absorbed power (1)kW9,511,013,915,6
EER (1)2,942,852,682,74
Cooling (EN14511)Cooling capacity (1)kW27,530,936,742,1
Absorbed power (1)kW9,911,514,516,3
EER (1)2,782,692,532,58
SEPR (2)5,615,625,215,22
Free-Cooling cycleAir temperature (3)°C-1,7-2,70,5-1,2
Absorbed power (3)kW0,980,981,961,96
CompressorQuantity1111
Water circuit.Water flowl/s1,551,742,072,37
Pressure dropskPa117142132141
Water connections"G1"1"1"1"
Electrical characteristicsPower supplyV/Ph/Hz400/3+N/50400/3+N/50400/3+N/50400/3+N/50
Max. running currentA20222932
Max. starting currentA144144162201
Unit SP versionWater flowl/s1,551,742,072,37
Pump available static pressurekPa109152150129
Tank water volumel100100100100
Water connections"G1"1"1"1"
Sound pressureSTD/SP version (4)dB(A)60616161
Weight STD versionsTransport weightkg415430470485
Operating weightkg437452499515

Dimensions

91101131151
LSTD/SPmm1850185018501850
WSTD/SPmm900900900900
HSTD/SPmm1840184018401840

Notes

  • 1 Chilled water (with ethylene glycol at 30%) from 15 to 10 °C, ambient air temperature 35 °C.
  • 2 Seasonal energy efficiency of high temperature process cooling according to EU Regulation No. 2016/2281.
  • 3 Ambient air temperature at wich the cooling capacity indicated in point (1) is reached.
  • 4 Sound pressure level measured in free field conditions at 1 m from the unit. According to ISO 3744.