clint THERMICA.png

clint tec_inverter_rotary.png

_clint_tec_ec_inverter_fans.png

CHA/IK/TR/A 18÷35 + DMN220

A CLASS ENERGY EFFICIENCY AIRCOOLED REVERSIBLE HEAT PUMPS WITH EC INVERTER AXIAL FANS, INVERTER ROTARY COMPRESSOR, PLATE EXCHANGER, HYDRONIC KIT AND DISTRIBUTION MODULE FOR DOMESTIC HOT WATER PRODUCTION.

caldo_e_freddo1.png _icon_inverter_Rotary_compressor_14.png icon_EC_Inverter_14_sin.png SCAMBIATORE_PIASTRE11.png DOCCIA_CATALOGONE.png icon_green_sun_2020.png _icon_A_CLASS_2018_heating.png R410A1.png

Thermica System is a fully hydronic system for room heating/cooling and domestic hot water production up to 55°C.
The system consists of a monoblock air/water heat pump with built-in hydronic module and an indoor unit with 220 l tank, hydraulically connected to each other. It is ideal for floor heating, medium and low temperature radiators, fan coil units and domestic hot water production, in new housing or in buildings with low energy demand.
The interior distribution module contains all hydraulic and electric components to facilitate installation and maintenance procedures, which thus become very simple.
Through the easy-to-use Touch Screen user interface, it is possible to control the operating parameters of the Heat Pump, as well as of the entire system.
The units are compliant to the ErP Regulation.

Versions

  • DMN220 - All in one version Distribution Module
  • CHA/IK/TR/A - Reversible Heat Pump

Power range

  • 5.2-8.2 kW
  • 1.5-2.3 Ton

Features

  • Structure with supporting frame, made of galvanised sheet metal with additional protection provided by polyester powder coating.
  • DC INVERTER Rotary compressor, with DC BRUSHLESS motor, complete with overload protection.
  • EC INVERTER axial fans with low ventilation and special wing profile, directly coupled to external rotor motors.
  • Condenser with copper tube and aluminium finned coil, complete with condensate drain pan and protection guards.
  • Evaporator plate-type AISI 316 stainless steel, equipped with antifreeze heater.
  • Electronic expansion valve.
  • R410A refrigerant.
  • Electrical board includes: main switch with door lock device, fuses, compressor and pump remote control switch.
  • Electronic proportional device to decrease the sound level, with a continuous regulation of the fan speed. This device also allows the cooling functioning of the unit by external temperature till -20 °C.
  • Functioning in heating mode with outside air temperature down to -20 °C.
  • Water circuit includes: circulator with high efficiency DC BRUSHLESS motor, flow switch, safety valve, gauge and expansion vessel.
  • Distribution module for domestic hot water production complete with 220 l DHW tank, 3 kW supplementary electric heater predisposition, 3-way DHW/system diverter valve, non-return valve, hydraulic separator, medium temperature zone flow rate calibration valve, pressure gauge, expansion vessel, pump and mixing valve for low temperature zone, automatic air vent valve, safety valve and water drain, domestic hot water flow switch, thermostatic domestic hot water mixer.
  • Microprocessor control and regulation system.

Loose accessories

  • EHM Supplementary electrical heater for distribution module
  • AG Rubber shock absorbers
182535
Riscaldamento ambienteHeating capacity (1)kW5,186,058,16
Absorbed power (1)kW1,561,942,56
COP (1)3,323,123,19
Outdoor unitPower supplyV/Ph/Hz230/1/50230/1/50230/1/50
Max. running currentA141920
Max. starting currentA71010
Water flowl/s0,290,350,46
Pump nominal powerkW0,0750,0750,075
Pump available static pressurekPa676053
Water connections"G1"1"1"
Transport weightkg7879103
Operating weightkg707194
Sound pressure (9)dB(A)505555
Riscaldamento ambiente (EN14511)SCOP (2)4,504,343,96
Energy Efficiency (2)%177171155
Energy Class (3)A+++A++A++
SCOP (4)3,233,132,93
Energy Efficiency (4)%126122114
Energy Class (5)A++A+A+
Heating capacity (1)kW5,145,988,03
Absorbed power (1)kW1,481,862,45
COP (1)3,483,213,28
Heating capacity (10)kW6,057,239,71
Absorbed power (10)kW1,391,852,42
COP (10)4,353,904,02
Riscaldamento acqua calda (EN14511)Profilo di carico dichiarato (5)LLL
Energy Efficiency (5)%545252
Energy Class (5)AAA
Raffreddamento ambienteCooling capacity (6)kW4,725,468,34
EER (6)2,732,582,73
Absorbed power (6)kW1,732,123,05
Raffreddamento ambiente (EN14511)Cooling capacity (6)kW4,765,588,42
Absorbed power (6)kW1,662,042,92
EER (6)2,862,742,88
Cooling capacity (7)kW5,006,039,10
Absorbed power (7)kW1,261,582,27
EER (7)3,963,814,01
SEER (8)5,594,825,61
Energy Efficiency (8)%221190221
Indoor unit (DMN220)Volume serbatoio ACSl220220220
Absorbed powerkW0,140,140,14
Pump nominal powerkW0,0750,0750,075
Power supplyV/Ph/Hz230/1/50230/1/50230/1/50
Supplementary electrical heaterkW333
Attacchi idraulici Serbatoio ACS"G3/4"3/4"3/4"
Attacchi idraulici Pompa di Calore"G1"1"1"
Attacchi idraulici Impianto Bassa temperatura"G1"1"1"
Attacchi idraulici Impianto Media temperatura"G3/4"3/4"3/4"
Attacchi idraulici Serbatoio Inerziale"G1"1"1"
Attacchi idraulici Solare eTermico"G3/4"3/4"3/4"
Transport weightkg999999
Operating weightkg321321321

Dimensions

182535
LSTDmm105010501160
DMN220mm620620620
WSTDmm290290330
DMN220mm640640640
HSTDmm685685890
DMN220mm199519951995

Notes

  • 1 Heated water from 40 to 45 °C, ambient air temperature 7 °C d.b./6 °C w.b.
  • 2 Seasonal energy efficiency of heating at low temperature with average climatic conditions. According to EU Regulation n. 813/2013.
  • 3 Seasonal energy efficiency class of heating at low temperature with average climatic conditions. According to EU Regulation n. 811/2013.
  • 4 Seasonal energy efficiency of heating at medium temperature with average climatic conditions. According to EU Regulation n. 813/2013.
  • 5 Seasonal energy efficiency class of heating at medium temperature with average climatic conditions. According to EU Regulation n. 811/2013.
  • 6 Chilled water from 12 to 7 °C, ambient air temperature 35 °C.
  • 7 Chilled water from 23 to 18 °C, ambient air temperature 35 °C.
  • 8 Seasonal energy efficiency of cooling at low temperature. According to EU Regulation n. 2016/2281.
  • 9 Sound pressure level measured in free field conditions at 1 m from the unit. According to ISO 3744.
  • 10 Heated water from 30 to 35 °C, ambient air temperature 7 °C d.b./6 °C w.b.