_clint_hydroplus.png

CHA-M/K 181÷522

Aircooled liquid Chillers and Heat Pumps with axial fans, Scroll compressors and shell and tube exchanger

SOLO_FREDDO.png caldo_e_freddo1.png COMPRESSORE_SCROLL111.png ASSIALE11.png SCAMBIATORE_FASCIO1.png _icon_aqualogik_technology.png R410A1.png

The liquid Chillers and Heat Pumps of CHA-M/K 181÷522 HYDROPLUS series, with R410A refrigerant, are designed for medium-sized service sector or industrial ambients.
They are used, combined with Fan Coil units, for the air conditioning of the rooms or to remove the heat developed during industrial processes. They can be supplied with Modbus RTU protocol through RS485 serial interface.
Equipped with axial fans, Scroll compressors and shell and tube exchanger, these units can be completed by a hydraulic circuit with AQUALOGIK technology.
The AQUALOGIK smart control system optimises the water set point and modulates the power supply voltage of the pump and the fans, thus making the use of the inertial tank superfluous. This obtains high energy efficiency, quiet operation and optimised dimensions and costs.
A wide range of accessories, factory fitted or supplied separately, complete the outstanding versatility and functionality of the series.

Versions

  • CHA-M/K - Cooling only
  • CHA-M/K/WP - Reversible Heat Pump
  • CHA-M/K/ST - Cooling only with AQUALOGIK technology
  • CHA-M/SZ/K/WP/ST - Reversible Heat Pump with AQUALOGIK technology

Power range

  • 53.0-155 kW
  • 15.0-44.0 Ton

Features

  • Structure with supporting frame, made of galvanised sheet metal with additional protection provided by polyester powder coating.
  • Scroll compressors with oil sight glass, internal overheat protection and crankcase heater.
  • Axial fans directly coupled to an electric motor with external rotor.
  • Condenser made of copper tubes and aluminium finned coil.
  • Shell and tube type evaporator, with one circuit on the refrigerant side and one on the water side.
  • R410A refrigerant.
  • Electrical board includes: main switch with door safety interlock, protection modules, overload protection for compressors and thermocontacts for fans.
  • On ST versions water circuit includes INVERTER circulating pump, safety valve and expansion vessel.
  • On ST versions Condensing Control is included: electronic proportional device that ensures efficient and continuous functioning of the unit with outside air temperature down to –20 °C in cooling mode. It also allows to reduce the sound level especially at night. It consists of a fans speed controller with continuous speed regulation, an high/low pressure transducer on cooling circuit and an electrical heater on electrical board.
  • Microprocessor control and regulation system (with AQUALOGIK technology on ST versions).

Factory fitted accessories

  • SL Unit silencement
  • CT Condensing control down to 0 °C
  • BT Low water temperature kit
  • HT High water temperature operation 13/18°C
  • HRT/S Total heat recovery in series
  • TX Coil with pre-coated fins
  • SI Inertial tank
  • IS Modbus RTU protocol, RS485 serial interface

Loose accessories

  • MN High and low pressure gauges
  • CR Remote control panel
  • RP Coils protection metallic guards
  • AG Rubber shock absorbers
  • FL Flow switch
181241301392522
CoolingCooling capacity (1)kW53,165,186,4125155
Absorbed power (1)kW17,922,429,244,859,3
EER (1)2,972,912,962,792,61
Cooling (EN14511)Cooling capacity (1)kW52,864,685,9124154
Absorbed power (1)kW18,222,929,745,560,2
EER (1)2,902,822,892,732,56
HeatingHeating capacity (2)kW59,373,993,8138168
Absorbed power (2)kW19,224,130,445,357,2
COP (2)3,093,073,093,052,94
Heating (EN14511)Heating capacity (2)kW59,774,594,4139169
Absorbed power (2)kW19,624,931,246,859,1
COP (2)3,052,993,032,972,86
CompressorQuantity11122
Refrigerant circuits11111
Capacity steps11122
EvaporatorWater flowl/s2,543,114,135,977,41
Pressure dropskPa3555455562
Water connections"G1 ½"2"2 ½"3"3"
Electrical characteristicsPower supplyV/Ph/Hz400/3/50400/3/50400/3/50400/3/50400/3/50
Max. running currentA435267103127
Max. starting currentA219264328316387
Electrical characteristics (ST versions)Power supplyV/Ph/Hz400/3/50400/3/50400/3/50400/3/50400/3/50
Max. running currentA455470108132
Max. starting currentA221266331321392
Unit ST versionsWater flowl/s2,543,114,135,977,41
Pump nominal powerkW0,750,751,101,851,85
Pump available static pressurekPa12510013011590
Expansion vessell1212121212
Water connections"G2 ½"2 ½"2 ½"2 ½"2 ½"
Sound pressureSTD and ST versions (3)dB(A)5959616363
With SL accessory (3)dB(A)5757596161
WeightsTransport weightkg6116497649261026
Operating weightkg6306707909601060
Weights (ST versions)Transport weightkg6266647799461046
Operating weightkg6456858059801080

Dimensions

181241301392522
LSTDmm23502350235023502350
WSTDmm11001100110011001100
HSTDmm19201920192022202220

Notes

  • 1 Chilled water from 12 to 7 °C, ambient air temperature 35 °C.
  • 2 Heated water from 40 to 45 °C, ambient air temperature 7 °C d.b./6 °C w.b.
  • 3 Sound pressure level measured in free field conditions at 1 m from the unit. According to ISO 3744.
  • N.B. (1) Weights of WP versions are specified on technical brochure.