CHA-M/K 181÷522
Aircooled liquid Chillers and Heat Pumps with axial fans, Scroll compressors and shell and tube exchanger







The liquid Chillers and Heat Pumps of CHA-M/K 181÷522 HYDROPLUS series, with R410A refrigerant, are designed for medium-sized service sector or industrial ambients.
They are used, combined with Fan Coil units, for the air conditioning of the rooms or to remove the heat developed during industrial processes. They can be supplied with Modbus RTU protocol through RS485 serial interface.
Equipped with axial fans, Scroll compressors and shell and tube exchanger, these units can be completed by a hydraulic circuit with AQUALOGIK technology.
The AQUALOGIK smart control system optimises the water set point and modulates the power supply voltage of the pump and the fans, thus making the use of the inertial tank superfluous. This obtains high energy efficiency, quiet operation and optimised dimensions and costs.
A wide range of accessories, factory fitted or supplied separately, complete the outstanding versatility and functionality of the series.
Versions
- CHA-M/K - Cooling only
- CHA-M/K/WP - Reversible Heat Pump
- CHA-M/K/ST - Cooling only with AQUALOGIK technology
- CHA-M/SZ/K/WP/ST - Reversible Heat Pump with AQUALOGIK technology
Power range
- 53.0-155 kW
- 15.0-44.0 Ton
Features
- Structure with supporting frame, made of galvanised sheet metal with additional protection provided by polyester powder coating.
- Scroll compressors with oil sight glass, internal overheat protection and crankcase heater.
- Axial fans directly coupled to an electric motor with external rotor.
- Condenser made of copper tubes and aluminium finned coil.
- Shell and tube type evaporator, with one circuit on the refrigerant side and one on the water side.
- R410A refrigerant.
- Electrical board includes: main switch with door safety interlock, protection modules, overload protection for compressors and thermocontacts for fans.
- On ST versions water circuit includes INVERTER circulating pump, safety valve and expansion vessel.
- On ST versions Condensing Control is included: electronic proportional device that ensures efficient and continuous functioning of the unit with outside air temperature down to –20 °C in cooling mode. It also allows to reduce the sound level especially at night. It consists of a fans speed controller with continuous speed regulation, an high/low pressure transducer on cooling circuit and an electrical heater on electrical board.
- Microprocessor control and regulation system (with AQUALOGIK technology on ST versions).
Accessories
Factory fitted accessories
- SL Unit silencement
- CT Condensing control down to 0 °C
- BT Low water temperature kit
- HT High water temperature operation 13/18°C
- HRT/S Total heat recovery in series
- TX Coil with pre-coated fins
- SI Inertial tank
- IS Modbus RTU protocol, RS485 serial interface
Loose accessories
- MN High and low pressure gauges
- CR Remote control panel
- RP Coils protection metallic guards
- AG Rubber shock absorbers
- FL Flow switch
Technical data
181 | 241 | 301 | 392 | 522 | |||
Cooling | Cooling capacity (1) | kW | 53,1 | 65,1 | 86,4 | 125 | 155 |
Absorbed power (1) | kW | 17,9 | 22,4 | 29,2 | 44,8 | 59,3 | |
EER (1) | 2,97 | 2,91 | 2,96 | 2,79 | 2,61 | ||
Cooling (EN14511) | Cooling capacity (1) | kW | 52,8 | 64,6 | 85,9 | 124 | 154 |
Absorbed power (1) | kW | 18,2 | 22,9 | 29,7 | 45,5 | 60,2 | |
EER (1) | 2,90 | 2,82 | 2,89 | 2,73 | 2,56 | ||
Heating | Heating capacity (2) | kW | 59,3 | 73,9 | 93,8 | 138 | 168 |
Absorbed power (2) | kW | 19,2 | 24,1 | 30,4 | 45,3 | 57,2 | |
COP (2) | 3,09 | 3,07 | 3,09 | 3,05 | 2,94 | ||
Heating (EN14511) | Heating capacity (2) | kW | 59,7 | 74,5 | 94,4 | 139 | 169 |
Absorbed power (2) | kW | 19,6 | 24,9 | 31,2 | 46,8 | 59,1 | |
COP (2) | 3,05 | 2,99 | 3,03 | 2,97 | 2,86 | ||
Compressor | Quantity | n° | 1 | 1 | 1 | 2 | 2 |
Refrigerant circuits | n° | 1 | 1 | 1 | 1 | 1 | |
Capacity steps | n° | 1 | 1 | 1 | 2 | 2 | |
Evaporator | Water flow | l/s | 2,54 | 3,11 | 4,13 | 5,97 | 7,41 |
Pressure drops | kPa | 35 | 55 | 45 | 55 | 62 | |
Water connections | "G | 1 ½" | 2" | 2 ½" | 3" | 3" | |
Electrical characteristics | Power supply | V/Ph/Hz | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 |
Max. running current | A | 43 | 52 | 67 | 103 | 127 | |
Max. starting current | A | 219 | 264 | 328 | 316 | 387 | |
Electrical characteristics (ST versions) | Power supply | V/Ph/Hz | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 |
Max. running current | A | 45 | 54 | 70 | 108 | 132 | |
Max. starting current | A | 221 | 266 | 331 | 321 | 392 | |
Unit ST versions | Water flow | l/s | 2,54 | 3,11 | 4,13 | 5,97 | 7,41 |
Pump nominal power | kW | 0,75 | 0,75 | 1,10 | 1,85 | 1,85 | |
Pump available static pressure | kPa | 125 | 100 | 130 | 115 | 90 | |
Expansion vessel | l | 12 | 12 | 12 | 12 | 12 | |
Water connections | "G | 2 ½" | 2 ½" | 2 ½" | 2 ½" | 2 ½" | |
Sound pressure | STD and ST versions (3) | dB(A) | 59 | 59 | 61 | 63 | 63 |
With SL accessory (3) | dB(A) | 57 | 57 | 59 | 61 | 61 | |
Weights | Transport weight | kg | 611 | 649 | 764 | 926 | 1026 |
Operating weight | kg | 630 | 670 | 790 | 960 | 1060 | |
Weights (ST versions) | Transport weight | kg | 626 | 664 | 779 | 946 | 1046 |
Operating weight | kg | 645 | 685 | 805 | 980 | 1080 |
Dimensions
181 | 241 | 301 | 392 | 522 | |||
L | STD | mm | 2350 | 2350 | 2350 | 2350 | 2350 |
W | STD | mm | 1100 | 1100 | 1100 | 1100 | 1100 |
H | STD | mm | 1920 | 1920 | 1920 | 2220 | 2220 |
Notes
- 1 Chilled water from 12 to 7 °C, ambient air temperature 35 °C.
- 2 Heated water from 40 to 45 °C, ambient air temperature 7 °C d.b./6 °C w.b.
- 3 Sound pressure level measured in free field conditions at 1 m from the unit. According to ISO 3744.
- N.B. (1) Weights of WP versions are specified on technical brochure.