_logo_nextpower.png

CHA-M/K 724-P÷1306-P

Aircooled liquid Chillers and Heat Pumps with axial fans, Scroll compressors and plate exchanger

SOLO_FREDDO.png caldo_e_freddo1.png COMPRESSORE_SCROLL111.png ASSIALE11.png SCAMBIATORE_PIASTRE11.png _clint_asia_icon_side_connections_2015.png R410A1.png

The models of NEXTPOWER range are dedicated to conditioning of medium and wide areas. The intelligent control module optimizes functioning times and supplied power from compressors based on heat load demands in the system.
The range is equipped with R410A refrigerant and features Scroll compressors and plate exchanger.
High reliability is the key plus of NEXTPOWER, thanks to the use of components built in large series and the management of several compressors allowing an increased compressor life span and the reduction of machine stopping risks: a faulty compressor will not compromise the functioning of the unit, that will continue to work with decreased power levels. The optional Air Section Divider allows to service one circuit without stopping the whole unit.
NEXTPOWER obtains high energy yield with high ESEER/IPLV values and excellent silent
functioning, since the fans adjust their speed to the actual system load, providing benefits
in terms of silent operation, important especially at night.
NEXTPOWER, thanks to the high partialization and the intelligent control module, doesn't require inertial storage tank.

Versions

  • CHA-M/K - Cooling only
  • CHA-M/K/WP - Reversible Heat Pump

Power range

  • 221-519 kW
  • 63.0-148 Ton

Features

  • Structure with supporting frame, made of galvanised sheet metal with additional protection provided by polyester powder coating.
  • Scroll compressors with oil sight glass, internal overheat protection and crankcase heater.
  • Axial fans directly coupled to an electric motor with external rotor.
  • Condenser made of copper tubes and aluminium finned coils.
  • Evaporator AISI 316 stainless steel braze welded plates type with two independent circuits on the refrigerant side and one on the water side, complete with water differential pressure switch. On the heat pump units is always installed an antifreeze heater.
  • Electronic expansion valve.
  • R410A refrigerant.
  • Electrical board includes: main switch with door safety interlock, protection modules, overload protection for compressors and thermocontacts for fans.
  • Microprocessor control and regulation system.

Factory fitted accessories

  • SL Unit silencement
  • CT Condensing control down to 0 °C
  • BT Low water temperature kit
  • DS Desuperheater
  • RT Total heat recovery
  • TX Coil with pre-coated fins
  • AD Air section divider
  • IS Modbus RTU protocol, RS485 serial interface

Loose accessories

  • MN High and low pressure gauges
  • CR Remote control panel
  • RP Coils protection metallic guards
  • AG Rubber shock absorbers
724-P824-P1044-P1206-P1306-P
CoolingCooling capacity (1)kW221296371448519
Absorbed power (1)kW77101122158196
EER (1)2,872,933,042,842,65
Cooling (EN14511)Cooling capacity (1)kW220294369446517
Absorbed power (1)kW78,1103124160198
EER (1)2,822,852,982,792,61
HeatingHeating capacity (2)kW256341411507601
Absorbed power (2)kW83,1110131168193
COP (2)3,083,103,143,023,11
Heating (EN14511)Heating capacity (2)kW257343414510604
Absorbed power (2)kW86,1115136174200
COP (2)2,982,983,042,933,02
CompressorQuantity44466
Refrigerant circuits22222
Capacity steps44466
EvaporatorWater flowl/s10,5614,1417,7321,4024,80
Pressure dropskPa5565635449
Water connectionsDN100100100100100
Electrical characteristicsPower supplyV/Ph/Hz400/3/50400/3/50400/3/50400/3/50400/3/50
Max. running currentA161195249293361
Max. starting currentA340410512515625
Sound pressureSTD version (3)dB(A)6768686970
With SL accessory (3)dB(A)6465656667
WeightsTransport weightkg16501748234424792685
Operating weightkg16901790239025302740

Dimensions

724-P824-P1044-P1206-P1306-P
LSTDmm28002800390039003900
WSTDmm22002200220022002200
HSTDmm21002100210021002100

Notes

  • 1 Chilled water from 12 to 7 °C, ambient air temperature 35 °C.
  • 2 Heated water from 40 to 45 °C, ambient air temperature 7 °C d.b./6 °C w.b.
  • 3 Sound pressure level measured in free field conditions at 1 m from the unit. According to ISO 3744.
  • N.B. (1) Weights of WP version are specified on technical brochure.