CHA-M/Y 1202÷2003
Aircooled liquid Chillers and Heat Pumps with axial fans, Screw compressors and shell and tube exchanger









The liquid Chillers and Heat Pumps of CHA-M/Y 1202÷2002 ENERGYMAX series, with R134a refrigerant, are designed for large service sector or industrial-type ambients. They are used, in combination with terminal units, for the air conditioning of the rooms or to remove the heat developed during industrial processes.
They are equipped with axial fans, Screw compressors and shell and tube exchanger. The use of large size condensing coils, together with fans with high unit efficiency, as well as the optimization of the hydraulic and cooling circuit and the use of latest generation Screw compressors, combined with a suitable sizing of the user system, allows to obtain high efficiency during operation with remarkably reduced energy consumption.
A wide range of accessories, factory fitted or supplied separately, complete the outstanding versatility and functionality of the series.
Versions
- CHA-M/Y - Cooling only
- CHA-M/Y/WP - Reversible Heat Pump
Power range
- 240-484 kW
- 68.0-138 Ton
Features
- Structure with supporting frame, made of galvanised sheet metal with additional protection provided by polyester powder coating.
- Screw compressors with built-in oil separator, suction filter, crankcase heater, oil sight glass, thermal protection, hot gas shut off valves and capacity steps.
- Axial fans directly coupled to an electric motor with external rotor.
- Condenser made of copper tubes and aluminium finned coils.
- Shell and tube type evaporator, with two independent circuits on the refrigerant side and one on the water side.
- Electronic expansion valve.
- R134a refrigerant.
- Electrical board includes: main switch with door safety interlock, protection modules, overload protection for compressors and thermocontacts for fans.
- Condensing control included, allows to reach up to 0 °C external air temperature.
- Microprocessor control and regulation system.
Accessories
Factory fitted accessories
- RZ Compressors stepless control
- BT Low water temperature kit
- HR Desuperheater
- HRT/S Total heat recovery in series
- TX Coil with pre-coated fins
- FE Antifreeze heater for evaporator
- II Inverter on one compressor and soft start for other compressors
- ID Inverter on all compressors
- SS Soft start
- WM Web Monitoring - Wireless remote monitoring (GPRS/EDGE/3G/TCP-IP)
- AD Air section divider
- IS Modbus RTU protocol, RS485 serial interface
- CP Potential free contacts
Loose accessories
- MN High and low pressure gauges
- CR Remote control panel
- AM Spring shock absorbers
- RP Coils protection metallic guards
- AG Rubber shock absorbers
- FL Flow switch
Technical data
1202 | 1302 | 1502 | 1702 | 1902 | 2002 | |||
Cooling | Cooling capacity (1) | kW | 240 | 276 | 313 | 368 | 423 | 484 |
Absorbed power (1) | kW | 85,1 | 100 | 111 | 131 | 152 | 183 | |
EER (1) | 2,82 | 2,76 | 2,82 | 2,81 | 2,78 | 2,64 | ||
Cooling (EN14511) | Cooling capacity (1) | kW | 239 | 275 | 312 | 366 | 421 | 482 |
Absorbed power (1) | kW | 86,1 | 101 | 112 | 133 | 154 | 185 | |
EER (1) | 2,78 | 2,74 | 2,79 | 2,75 | 2,73 | 2,61 | ||
Heating | Heating capacity (2) | kW | 271 | 302 | 348 | 403 | 466 | 541 |
Absorbed power (2) | kW | 88,6 | 99,7 | 112 | 130 | 149 | 178 | |
COP (2) | 3,04 | 3,03 | 3,11 | 3,10 | 3,13 | 3,04 | ||
Heating (EN14511) | Heating capacity (2) | kW | 272 | 303 | 350 | 405 | 468 | 544 |
Absorbed power (2) | kW | 91,1 | 102 | 116 | 135 | 154 | 184 | |
COP (2) | 2,99 | 2,97 | 3,02 | 3,00 | 3,04 | 2,96 | ||
Compressor | Quantity | n° | 2 | 2 | 2 | 2 | 2 | 2 |
Refrigerant circuits | n° | 2 | 2 | 2 | 2 | 2 | 2 | |
Capacity steps | n° | 6 | 6 | 6 | 6 | 6 | 6 | |
Evaporator | Water flow | l/s | 11,47 | 13,19 | 14,95 | 17,58 | 20,21 | 23,12 |
Pressure drops | kPa | 46 | 47 | 53 | 67 | 53 | 60 | |
Water connections | DN | 100 | 100 | 100 | 100 | 100 | 100 | |
Electrical characteristics | Power supply | V/Ph/Hz | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 |
Max. running current | A | 212 | 250 | 278 | 334 | 363 | 434 | |
Max. starting current | A | 277 | 371 | 385 | 444 | 518 | 611 | |
Sound pressure | STD version (3) | dB(A) | 76 | 76 | 75 | 77 | 77 | 77 |
Weights | Transport weight | kg | 2475 | 2842 | 3083 | 3262 | 3500 | 3927 |
Operating weight | kg | 2640 | 3000 | 3280 | 3450 | 3690 | 4250 |
Dimensions
1202 | 1302 | 1502 | 1702 | 1902 | 2002 | |||
L | STD | mm | 2800 | 2800 | 3900 | 3900 | 3900 | 3900 |
W | STD | mm | 2200 | 2200 | 2200 | 2200 | 2200 | 2200 |
H | STD | mm | 2100 | 2100 | 2100 | 2100 | 2100 | 2100 |
Notes
- 1 Chilled water from 12 to 7 °C, ambient air temperature 35 °C.
- 2 Heated water from 40 to 45 °C, ambient air temperature 7 °C d.b./6 °C w.b.
- 3 Sound pressure level measured in free field conditions at 1 m from the unit. According to ISO 3744.
- N.B. (1) Weights of WP version are specified on technical brochure.
Documents
- Product overview 00_clint_international_product_over_09.2019_w.pdf
- Product guides _clint_international_product_guide_09.2019_w.pdf
- Commercial leaflets 04_clint_international_leaflet_energymax_09.2019_w.pdf
- Technical brochures 07_CHA-M_Y_1202-2002_clbm_56.7.pdf
- Installation, use and maintenance manuals CHA-MY_1202_2002_CLMM_56.7_J1mW6UD.pdf