MHA/K 31÷151

Air cooled condensing units with axial fans and Scroll compressor

_icona_clint_solo_raffreddamento_2024.png _icona_clint_compressore_scroll_2024.png _icona_clint_fan_assiale_2024.png _icona_clint_refrigerant_R410A_2024.png

The condensing units of the MHA/K 31÷151 series, set up for R410A refrigerant, are designed for small and medium-sized domestic or industrial systems.
These outdoor units are combined with evaporators in split system air conditioning installations, allowing the rooms to be cooled and dehumidified. They can also be used in combination with hydronic evaporating units, generally in air conditioning applications.
They are equipped with Scroll compressors and axial fans, and they enable immediate and efficient use thanks to particular technical and design adjustments.
A wide range of accessories, factory fitted or supplied separately, complete the outstanding versatility and functionality of the series.

Versions

  • MHA/K - Cooling only

Power range

  • 9.2-45.0 kW
  • 2.6-13.0 Ton

Features

  • Structure with supporting frame, in peraluman and galvanized sheet.
  • Scroll compressor with internal overheat protection and crankcase heater, if needed.
  • Axial fans with low ventilation and special wing profile, directly coupled to external rotor motors.
  • Condenser made of copper tubes and aluminium finned coil.
  • R410A refrigerant.
  • Electrical board includes: main switch with door lock device, fuses and compressor remote control switch.

Factory fitted accessories

  • CC Condensing control down to -20 °C
  • TX Coil with pre-coated fins
  • RL Liquid receiver
  • VS Solenoid valve

Loose accessories

  • RP Coils protection metallic guards
  • AG Rubber shock absorbers
31415161718191101131151
CoolingCooling capacity (1)kW9,210,813,215,819,121,226,430,936,645,3
Absorbed power (1)kW2,93,74,15,16,27,18,69,211,514,2
CompressorQuantity1111111111
TypeScrollScrollScrollScrollScrollScrollScrollScrollScrollScroll
CondenserFan1122221222
Air flowm³/s0,760,761,611,531,531,532,254,614,614,61
ConnectionsSuction lineØ mm16161818222228282828
Liquid lineØ mm10101212121212121216
Electrical characteristicsPower supplyV/Ph/Hz230/1/50230/1/50400/3+N/50400/3+N/50400/3+N/50400/3+N/50400/3+N/50400/3+N/50400/3+N/50400/3+N/50
Max. running currentA1518710101223293039
Max. starting currentA798658615874142147142167
Sound pressureSTD version (2)dB(A)53545455565759616161
WeightsTransport weightkg9092109111113115218232252266
Operating weightkg9193111114116118221235256271

Dimensions

31415161718191101131151
LSTDmm87087011601160116011601850185018501850
WSTDmm3203205005005005001000100010001000
HSTDmm1100110012701270127012701300130013001300

Notes

  • 1 Evaporating temperature 5 °C, ambient air temperature 35 °C.
  • 2 Sound pressure level measured in free field conditions at 1 m from the unit. According to ISO 3744.