Resistenza elettrica ad integrazione

Resistenza elettrica ad integrazione

EH accessory for cassette unit

Electrical heaters manufactured in accordance with international electrical and safety standards, armoured type with Aluminium heat exchange fins.

• Max. operating temperature of electric heaters: 350 °C;
• Equipped with 1 automatic reset safety thermostat, power relay and no general (differential automatic circuit breaker) circuit breaker.
Note: When there are electric heaters, an air velocity on the electric heater of > 1 m/s and the post-ventilation function (min. 300 sec, or ventilation always on) is mandatory, see e.g. controllers DRH1, DRH2.