Resistenza elettrica ad integrazione
EH accessory for cassette unit
Electrical heaters manufactured in accordance with international electrical and safety standards, armoured type with Aluminium heat exchange fins.
• Max. operating temperature of electric heaters: 350 °C;
• Equipped with 1 automatic reset safety thermostat, power relay and no general (differential automatic circuit breaker) circuit breaker.
Note: When there are electric heaters, an air velocity on the electric heater of > 1 m/s and the post-ventilation function (min. 300 sec, or ventilation always on) is mandatory, see e.g. controllers DRH1, DRH2.