The hydronic Fan Coil units with cabinet, SXM 113÷443, feature an exclusive and compact design combined with the highest efficiency and noiseless operation.
Part of an hydronic system equipped with a liquid Chiller, they generate cool air silently and with instantaneous reaction. During the winter, if combined with a thermal system, they provide warm air, making it possible to meet heating needs. A filter, easily removable and washable, absorbs and holds suspended dust, allowing constant cleaning cycles and maintaining an adequate air quality, in accordance with hygiene standards, especially in high occupancy locations.
The units, equipped with EC Inverter motor, modulate the air flow adapting the performances instant to instant to the actual needs of the room to be conditioned, thus assuring a total comfort with greater energy savings.

Versions

  • SXM/VH/EC - Vertical unit with EC Inverter fans, front inlet and vertical delivery

Power range

  • 1.1-4.1 kW
  • 0.3-1.2 Ton

Features

  • Cabinet made of painted aluminum characterized by a depth of only 13 cm (similar to colour RAL 9003 white); load-bearing structure made of galvanized steel-sheet, with internal thermal-acoustic insulation. Air delivery grill by fixed fins, equipped with small sliding side doors for easily access to the internal control panel (similar to colour RAL 7045 grey). Feet made of painted steel-sheet (similar to colour RAL 7045 grey).
  • Condensate drain pan provided with natural condensation drain and thermal insulation.
  • Heat exchanger coil made of copper pipes and aluminium fins, water connections provided with anti-torsion system, manual air vent and water drain valves.
  • Fan section provided with tangential fan in plastic material with aximmetric blades directly coupled to the EC Inverter electronic motor. Modulating regulation with 0-10Vdc signal with control panels provided as accessory or with independent regulation system.
  • Easily removable and washable air filter, with a fine mesh structure made of honeycomb polypropylene net.
  • Standard water connections on the left side in front of the unit.

Loose accessories

  • Z Couple of feet
  • C1 Auxiliary condensate drain pan for vertical versions
  • V23 3-Way on/off valves for 2-Pipe system
  • V23M 3-Way modulating valves for 2-Pipe system
  • V25 3-Way On/Off valves with 2 shut-off (ball) for 2-Pipe system
  • V25M 3-Way modulating valves with 2 shut-off (ball) for 2-Pipe system
  • V22 2-Way On/Off valves for 2-Pipe system
  • V22M 2-Way modulating valves for 2-pipe system
  • V26 2-Way on/off valves with 2 shut-off (ball) for 2-Pipe system
  • V26M 2-Way modulating valves with 2 shut-off (ball) for 2-Pipe system
  • DRH2 Wall mounted configurable electronic control panel for AC/EC versions
  • SRH1 Wall mounted Wi-Fi configurable electronic control panel
  • DBH4 On board configurable electronic control panel for AC/EC versions
  • SBH1 On board Wi-Fi configurable electronic control panel
  • SNW4 Water temperature probe
  • TMB3 Minimun hot water temperature thermostat 32°C
  • TMB4 Minimum hot water temperature thermostat 42°C
113223333443
Max coolingTotal cooling capacity (1)kW1,132,273,254,09
Sensible cooling capacity (1)kW0,851,682,402,96
Water flow (1)l/h194389558702
Pressure drops (1)kPa21,515,215,027,5
Heating MaxHeating capacity (2)kW1,252,373,424,30
Water flow (2)l/h218413595748
Pressure drops (2)kPa21,014,313,724,1
Cooling MedTotal cooling capacity (1)kW0,651,271,782,35
Sensible cooling capacity (1)kW0,480,931,301,69
Water flow (1)l/h111218305404
Pressure drops (1)kPa8,05,55,210,3
Heating MedHeating capacity (2)kW0,681,261,772,36
Water flow (2)l/h119220308412
Pressure drops (2)kPa7,04,64,28,1
Cooling MinTotal cooling capacity (1)kW0,360,720,991,34
Sensible cooling capacity (1)kW0,260,520,710,94
Water flow (1)l/h62124170229
Pressure drops (1)kPa2,92,11,93,9
Heating MinHeating capacity (2)kW0,370,680,941,28
Water flow (2)l/h64119165224
Pressure drops (2)kPa2,31,51,42,7
RowsQuantity3333
Water volumedm³0,601,101,582,07
Water connectionsIn / Out"G1/2" F1/2" F1/2" F1/2" F
Input voltageMaxV10101010
MedV4,64,64,64,6
MinV2222
Air flowMaxm³/h195352514620
Medm³/h100177252326
Minm³/h5294132174
Electrical characteristicsPower supplyV/Ph/Hz230/1/50-60230/1/50-60230/1/50-60230/1/50-60
Max absorbed powerkW0,0140,0200,0230,027
Absorbed power MedkW0,0050,0070,0080,008
Absorbed power MinkW0,0020,0030,0030,003
Sound pressureMax (3)dB(A)42444546
Med (3)dB(A)25272829
Min (3)dB(A)22232425
WeightsTransport weightkg18212629
Operating weightkg16192326

Dimensions

113223333443
LSTDmm65085010501250
WSTDmm129129129129
HSTDmm572572572572
DSTD (4)mm110110110110

Notes

  • 1 Ambient air temperature 27 °C d.b./19 °C w.b., water temperature 7/12 °C.
  • 2 Ambient air temperature 20 °C d.b., water temperature 45/40 °C,
  • 3 Sound pressure level measured at 1 m from the unit with reverberation time 0,5 s.
  • N.B. (1) Inhibited ethylene glycol can be added to the water.
  • N.B. (2) Maximum operating pressure 1500 kPa.
  • N.B. (3) Maximum inlet water temperature 90 °C.