_clint_hydroplus.png

CWW-M/K 181-P÷522-P

Watercooled liquid Chillers and Heat Pumps with Scroll compressors and plate exchangers

SOLO_FREDDO.png caldo_e_freddo1.png COMPRESSORE_SCROLL111.png SCAMBIATORE_PIASTRE11.png R410A1.png

The CWW-M/K 181-P÷522-P HYDROPLUS liquid Chillers and Heat Pumps, with R410A refrigerant, are designed for medium-sized domestic or industrial systems which require medium-high power, space-saving units and quiet operation. This range is ideal for indoor installation and, equipped with a self-contained structure, it reduces the overall dimensions to a minimum while at the same time making installation and maintenance operations easier.
Equipped with prepainted plate structure, Scroll compressors and plate type exchangers, these units have cooling and hydraulic circuits complete with everything necessary for quick installation and high energy efficiency, even in the version with tank and pump.
A wide series of accessories, factory-assembled or supplied separately, such as the desuperheater or the total heat recovery, rounds off the variety of equipment in this product range.

Versions

  • CWW-M/K - Cooling only
  • CWW-M/K/WP - Reversible Heat Pump

Power range

  • 58.0-176 kW
  • 16.0-50.0 Ton

Features

  • Structure with supporting frame, made of galvanised sheet metal with additional protection provided by polyester powder coating.
  • Scroll compressors with oil sight glass, internal overheat protection and crankcase heater.
  • Condenser AISI 316 stainless steel braze welded plates type with one circuit on the refrigerant side and one on the water side.
  • Evaporator AISI 316 stainless steel braze welded plates type with one circuit on the refrigerant side and one on the water side, completed with water differential pressure switch.
  • R410A refrigerant.
  • Electrical board includes: main switch with door safety interlock, protection modules and overload protection for compressors.
  • Microprocessor control and regulation system.

Factory fitted accessories

  • SL Unit silencement
  • BT Low water temperature kit
  • DS Desuperheater
  • RT Total heat recovery
  • IS Modbus RTU protocol, RS485 serial interface

Loose accessories

  • MN High and low pressure gauges
  • CR Remote control panel
  • SPU Inertial tank and single circulating pump
  • SPD Inertial tank and double circulating pump
  • PV2 2-Way electronic pressostatic valve
  • PV3 3-Way electronic pressostatic valve
  • AG Rubber shock absorbers
  • AG1 Rubber shock absorbers for SPU and SPD modules
181-P241-P301-P392-P522-P
CoolingCooling capacity (1)kW57,573,994,5137176
Absorbed power (1)kW13,216,921,931,941,3
Cooling (EN14511)Cooling capacity (1)kW57,173,494,0136175
Absorbed power (1)kW14,017,923,133,543,5
EER (1)4,084,084,074,074,03
HeatingHeating capacity (2)kW71,392,4116168218
Absorbed power (2)kW16,821,327,640,651,9
Heating (EN14511)Heating capacity (2)kW71,993,2117169219
Absorbed power (2)kW17,722,528,842,354,2
COP (2)4,064,144,064,004,05
CompressorQuantity11122
Refrigerant circuits11111
Capacity steps11122
EvaporatorWater flowl/s2,753,534,526,558,41
Pressure dropskPa4352465156
Water connectionsDN3232656565
CondenserWater flowl/s3,384,345,568,0710,38
Pressure dropskPa5259485460
Water connectionsDN3232656565
Electrical characteristicsPower supplyV/Ph/Hz400/3/50400/3/50400/3/50400/3/50400/3/50
Max. running currentA39485995119
Max. starting currentA215260320308379
Unit with tank and pumpPump available static pressurekPa125100120125120
Tank water volumel300300300300300
Water connections"G2 ½"2 ½"2 ½"2 ½"2 ½"
Sound pressureSTD version (3)dB(A)5959606062
With SL accessory (3)dB(A)5656575759
WeightsTransport weight (4)kg372391456609725
Operating weight (4)kg380400470620750

Dimensions

181-P241-P301-P392-P522-P
LUNITmm12001200120016001600
UNIT + SPU/SPDmm23102310231027102710
WUNITmm680680680680680
UNIT + SPU/SPDmm680680680680680
HUNITmm15201520152015201520
UNIT + SPU/SPDmm15201520152015201520

Notes

  • 1 Chilled water from 12 to 7 °C, water temperature at the condenser from 30 to 35 °C.
  • 2 Heated water from 40 to 45 °C, water temperature at the evaporator from 15 to 10 °C.
  • 3 Sound pressure level measured in free field conditions at 1 m from the unit. According to ISO 3744.
  • 4 Unit without tank and pump.
  • N.B. (1) Weights of WP version are specified on technical brochure.