CWW-M/K 181-P÷522-P
Watercooled liquid Chillers and Heat Pumps with Scroll compressors and plate exchangers





The CWW-M/K 181-P÷522-P HYDROPLUS liquid Chillers and Heat Pumps, with R410A refrigerant, are designed for medium-sized domestic or industrial systems which require medium-high power, space-saving units and quiet operation. This range is ideal for indoor installation and, equipped with a self-contained structure, it reduces the overall dimensions to a minimum while at the same time making installation and maintenance operations easier.
Equipped with prepainted plate structure, Scroll compressors and plate type exchangers, these units have cooling and hydraulic circuits complete with everything necessary for quick installation and high energy efficiency, even in the version with tank and pump.
A wide series of accessories, factory-assembled or supplied separately, such as the desuperheater or the total heat recovery, rounds off the variety of equipment in this product range.
Versions
- CWW-M/K - Cooling only
- CWW-M/K/WP - Reversible Heat Pump
Power range
- 58.0-176 kW
- 16.0-50.0 Ton
Features
- Structure with supporting frame, made of galvanised sheet metal with additional protection provided by polyester powder coating.
- Scroll compressors with oil sight glass, internal overheat protection and crankcase heater.
- Condenser AISI 316 stainless steel braze welded plates type with one circuit on the refrigerant side and one on the water side.
- Evaporator AISI 316 stainless steel braze welded plates type with one circuit on the refrigerant side and one on the water side, completed with water differential pressure switch.
- R410A refrigerant.
- Electrical board includes: main switch with door safety interlock, protection modules and overload protection for compressors.
- Microprocessor control and regulation system.
Accessories
Factory fitted accessories
- SL Unit silencement
- BT Low water temperature kit
- DS Desuperheater
- RT Total heat recovery
- IS Modbus RTU protocol, RS485 serial interface
Loose accessories
- MN High and low pressure gauges
- CR Remote control panel
- SPU Inertial tank and single circulating pump
- SPD Inertial tank and double circulating pump
- PV2 2-Way electronic pressostatic valve
- PV3 3-Way electronic pressostatic valve
- AG Rubber shock absorbers
- AG1 Rubber shock absorbers for SPU and SPD modules
Technical data
181-P | 241-P | 301-P | 392-P | 522-P | |||
Cooling | Cooling capacity (1) | kW | 57,5 | 73,9 | 94,5 | 137 | 176 |
Absorbed power (1) | kW | 13,2 | 16,9 | 21,9 | 31,9 | 41,3 | |
Cooling (EN14511) | Cooling capacity (1) | kW | 57,1 | 73,4 | 94,0 | 136 | 175 |
Absorbed power (1) | kW | 14,0 | 17,9 | 23,1 | 33,5 | 43,5 | |
EER (1) | 4,08 | 4,08 | 4,07 | 4,07 | 4,03 | ||
Heating | Heating capacity (2) | kW | 71,3 | 92,4 | 116 | 168 | 218 |
Absorbed power (2) | kW | 16,8 | 21,3 | 27,6 | 40,6 | 51,9 | |
Heating (EN14511) | Heating capacity (2) | kW | 71,9 | 93,2 | 117 | 169 | 219 |
Absorbed power (2) | kW | 17,7 | 22,5 | 28,8 | 42,3 | 54,2 | |
COP (2) | 4,06 | 4,14 | 4,06 | 4,00 | 4,05 | ||
Compressor | Quantity | n° | 1 | 1 | 1 | 2 | 2 |
Refrigerant circuits | n° | 1 | 1 | 1 | 1 | 1 | |
Capacity steps | n° | 1 | 1 | 1 | 2 | 2 | |
Evaporator | Water flow | l/s | 2,75 | 3,53 | 4,52 | 6,55 | 8,41 |
Pressure drops | kPa | 43 | 52 | 46 | 51 | 56 | |
Water connections | DN | 32 | 32 | 65 | 65 | 65 | |
Condenser | Water flow | l/s | 3,38 | 4,34 | 5,56 | 8,07 | 10,38 |
Pressure drops | kPa | 52 | 59 | 48 | 54 | 60 | |
Water connections | DN | 32 | 32 | 65 | 65 | 65 | |
Electrical characteristics | Power supply | V/Ph/Hz | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 |
Max. running current | A | 39 | 48 | 59 | 95 | 119 | |
Max. starting current | A | 215 | 260 | 320 | 308 | 379 | |
Unit with tank and pump | Pump available static pressure | kPa | 125 | 100 | 120 | 125 | 120 |
Tank water volume | l | 300 | 300 | 300 | 300 | 300 | |
Water connections | "G | 2 ½" | 2 ½" | 2 ½" | 2 ½" | 2 ½" | |
Sound pressure | STD version (3) | dB(A) | 59 | 59 | 60 | 60 | 62 |
With SL accessory (3) | dB(A) | 56 | 56 | 57 | 57 | 59 | |
Weights | Transport weight (4) | kg | 372 | 391 | 456 | 609 | 725 |
Operating weight (4) | kg | 380 | 400 | 470 | 620 | 750 |
Dimensions
181-P | 241-P | 301-P | 392-P | 522-P | |||
L | UNIT | mm | 1200 | 1200 | 1200 | 1600 | 1600 |
UNIT + SPU/SPD | mm | 2310 | 2310 | 2310 | 2710 | 2710 | |
W | UNIT | mm | 680 | 680 | 680 | 680 | 680 |
UNIT + SPU/SPD | mm | 680 | 680 | 680 | 680 | 680 | |
H | UNIT | mm | 1520 | 1520 | 1520 | 1520 | 1520 |
UNIT + SPU/SPD | mm | 1520 | 1520 | 1520 | 1520 | 1520 |
Notes
- 1 Chilled water from 12 to 7 °C, water temperature at the condenser from 30 to 35 °C.
- 2 Heated water from 40 to 45 °C, water temperature at the evaporator from 15 to 10 °C.
- 3 Sound pressure level measured in free field conditions at 1 m from the unit. According to ISO 3744.
- 4 Unit without tank and pump.
- N.B. (1) Weights of WP version are specified on technical brochure.
Documents
- Product overview 00_clint_international_product_over_09.2019_w.pdf
- Product guides _clint_international_product_guide_09.2019_w.pdf
- Commercial leaflets 02_clint_international_leaflet_hydroplus_09.2019_w.pdf
- Technical brochures 13_CWW-M_K_181-P-522-P_clbm_137.7.pdf
- Installation, use and maintenance manuals CWW-MK-181P_522P_CLMM_137.7_x5N7nEM.pdf