CWW-M/SZ/Y/A 1301÷2601
A CLASS energy efficiency watercooled liquid Chillers with Screw compressors and flooded shell and tube exchangers








The liquid chillers of the CWW-M/SZ/Y/A 1301÷2601 ENERGYMAX series, with R134a refrigerant, are designed for the service sector or industrial systems requiring high power. These units are characterized by an high efficiency, in A CLASS, with EER higher than 5,05 thanks to the dedicated technical solutions as flooded shell and tube evaporator and Screw compressors.
Units are equipped with latest generation Screw compressors, flooded shell and tube evaporator and connections for condensation with tower water or well water or with a Dry-Cooler. Furthermore, they have a series of accessories which are factory-assembled of supplied separately such as desuperheater, total heat recovery and, if neccessary, a device for operating a heat pump. Designed and produced to optimize the layout of each component so as to make any necessary maintenance operations more convenient, these units have an essential and compact structure intended for indoor installation.
The units feature 460V power supply and 60Hz frequency.
Versions
- CWW-M/SZ/Y/A - Cooling only
Power range
- 239-518 kW
- 68.0-147 Ton
Features
- Structure with supporting frame, made of galvanised sheet metal with additional protection provided by polyester powder coating.
- Screw compressors, with external oil separator, suction filter, oil sight glass, thermal protection, hot gas shut off valves and stepless capacity steps.
- Shell and tube type condenser, with easily removable cast iron heads to enable access for maintenance operations.
- Flooded shell and tube type evaporator, with casing with high efficiency tube nest designed for R134a.
- Electronic expansion valve.
- R134a refrigerant.
- Electrical board includes: main switch with door safety interlock, protection modules and overload protection for compressors.
- Microprocessor control and regulation system.
Accessories
Factory fitted accessories
- BT Low water temperature kit
- HR Desuperheater
- HRT/S Total heat recovery in series
- FE Antifreeze heater for evaporator
- DP Device for heat pump operation
- II Inverter on one compressor and soft start for other compressors
- SS Soft start
- WM Web Monitoring - Wireless remote monitoring (GPRS/EDGE/3G/TCP-IP)
- IS Modbus RTU protocol, RS485 serial interface
- CP Potential free contacts
Loose accessories
- MN High and low pressure gauges
- CR Remote control panel
- AM Spring shock absorbers
- PV3 3-Way electronic pressostatic valve
- AG Rubber shock absorbers
- FL Flow switch
Technical data
1301 | 1501 | 1701 | 1901 | 2001 | 2601 | |||
Cooling | Cooling capacity (1) | kW | 239 | 282 | 337 | 406 | 462 | 518 |
Absorbed power (1) | kW | 46 | 53 | 65 | 78 | 86 | 96 | |
Compressor | Quantity | n° | 1 | 1 | 1 | 1 | 1 | 1 |
Refrigerant circuits | n° | 1 | 1 | 1 | 1 | 1 | 1 | |
Capacity steps | n° | Stepless | Stepless | Stepless | Stepless | Stepless | Stepless | |
Evaporator | Water flow | l/s | 11,42 | 13,47 | 16,10 | 19,40 | 22,07 | 24,75 |
Pressure drops | kPa | 39 | 37 | 40 | 46 | 38 | 34 | |
Water connections | DN | 100 | 100 | 100 | 100 | 100 | 100 | |
Condenser | Water flow | l/s | 13,62 | 16,01 | 19,21 | 23,12 | 26,18 | 29,34 |
Pressure drops | kPa | 48 | 41 | 57 | 56 | 54 | 46 | |
Water connections | DN | 100 | 100 | 100 | 100 | 100 | 125 | |
Electrical characteristics | Power supply | V/Ph/Hz | 460/3/60 | 460/3/60 | 460/3/60 | 460/3/60 | 460/3/60 | 460/3/60 |
Max. running current | A | 105 | 121 | 148 | 177 | 199 | 214 | |
Max. starting current | A | 361 | 416 | 422 | 488 | 529 | 742 | |
Sound pressure | STD version (2) | dB(A) | 70 | 71 | 73 | 75 | 76 | 77 |
Weights | Transport weight | kg | 2910 | 3090 | 3217 | 3410 | 3722 | 3910 |
Operating weight | kg | 3010 | 3220 | 3360 | 3580 | 3900 | 4120 |
Dimensions
1301 | 1501 | 1701 | 1901 | 2001 | 2601 | |||
L | STD | mm | 3400 | 3400 | 3400 | 3400 | 3400 | 3400 |
W | STD | mm | 1150 | 1150 | 1150 | 1150 | 1150 | 1150 |
H | STD | mm | 2100 | 2100 | 2100 | 2100 | 2100 | 2100 |
Notes
- 1 Chilled water from 12 to 7 °C, water temperature at the condenser from 30 to 35 °C.
- 2 Sound pressure level measured in free field conditions at 1 m from the unit. According to ISO 3744.