RTQXT-M/K 51÷362
Single Skin packaged Roof Top units with Scroll compressors and radial fans
The single skin Packaged Roof Top units of the FLEXI AIR series, with R410A refrigerant, can be connected to a duct network for air conditioning of small and medium surface areas for public use such as halls, shopping centres, cafeterias, restaurants and health centres, or for industrial ambients such as food processing or preservation centres.
Equipped with radial fan or EC Inverter Plug-Fan, these units are available in a cooling only and in a reversible heat pump version. The EC Inverter Plug-Fan with high energy efficiency backward blades are managed by an electronic control adjusting fan rotational speed to adapt the air flow to the system capacity.
The cabinet features a perimeter base structure composed of elements with zinc coated galvanized treatment. The frame is realized with extruded aluminium alloy sections. The perimeter panels are realized in pre-painted metal sheet.
The unit can be equipped, as an option, with a Free-Cooling Economizer section in addition to the components installed on the basic version. The ECONOMIZER is automatically controlled both in FREE-COOLING or FREE-HEATING.
Versiones
- RTQXT-M/K - Cooling only
- RTQXT-M/K/WP - Reversible Heat Pump
- RTQXT-M/K/EC - Cooling only with EC Inverter Plug-Fan
- RTQXT-M/K/EC/WP - Reversible Heat Pump with EC Inverter Plug-Fan
Power range
- 13,0-85,0 kW
- 3,6-24,0 Ton
Características
- The perimeter base structure is composed of elements in passivated and press-bent galvanised sheet. The frame is realised with extruded aluminium alloy sections coupled by 3-way joints. The assembly of the base and frame is with double support and guarantees the tradable surface of the base panels, whose installation takes place without the use of projecting screws. The perimeter panels can be easily removed. They are realised in pre-painted metal sheet and allow access inside the unit for maintenance and repair operations. The structure has a 10 mm thick insulation layer.
- Scroll compressors with oil sight glass, internal overheat protection and crankcase heater.
- Condenser and evaporator made of copper tube and aluminium finned coil.
- Delivery radial fan coupled to 3-phase motors by V belt and variable pulley.
- Both the cooling only and reversible heat pump versions are available with high efficiency delivery EC INVERTER PLUG-FAN, with electronic speed control to easily adapt to the system characteristics.
- R410A refrigerant.
- Electrical board includes: main switch with door safety interlock; thermal protection relays for compressors; thermocontacts for fans of the
- condensing unit section; contactors for fans motors of the air treatment section; interface relay and electrical terminals for external connections.
- Microprocessor for the automatic control of the unit, allowing continuous display of the operational status of the unit, control set and real air temperature and, in case of partial or total block of the unit, indication of security device that intervened.
- Operating outdoor ambient air temperature up to 52 °C.
Accesorios
Accesorios montados en fábrica
- ECO Sección economizer Free Cooling con rejillas con persianas de aluminio y motor eléctrico. El control con microprocesador coordina la apertura de las rejillas con persianas para gestionar la expulsión, recirculación y renovación del aire.
- SL Silenciamiento unidad
- CC Control de condensación hasta -20 °C
- ECA Ventiladores EC Inverter en la sección de condensación
- TXKC Batería de condensación con tratamiento epoxi negro
- TXKE Batería de evaporación con tratamiento epoxi negro
- FTM5 Plate filters efficiency M5
- AT Control regulación caudal aire constante
- AT/P Control de regulación presión estática útil constante
- PF Presostato diferencial para el control de los filtros
- IST Protocolo Modbus TCP/IP, puerto Ethernet
- ISB Protocolo BACnet MSTP, interfaz serial RS485
- ISBT protocolo BACnet TCP/IP, puerto Ethernet
- ISS Protocolo SNMP, puerto Ethernet
- MN Manómetros de alta y baja presión
- CS Cubiertas de protección para rejillas
- RP Mallas de protección baterías
Accesorios suministrados por separado
- CR Control remoto
- CDT Panel de control remoto con termostato de ambiente con pantalla táctil
- AG Antivibratorios de caucho
Technical data
51 | 71 | 101 | 121 | 151 | 181 | 242 | 302 | 362 | |||
Refrigeración | Potencia frigorífica (1) | kW | 12,8 | 17,4 | 23,2 | 29,9 | 34,0 | 41,1 | 57,4 | 65,7 | 84,9 |
Potencia absorbida (1) | kW | 4,9 | 6,3 | 8,8 | 11,4 | 12,9 | 16,6 | 23,0 | 26,4 | 34,3 | |
EER (1) | 2,61 | 2,76 | 2,64 | 2,62 | 2,64 | 2,48 | 2,50 | 2,49 | 2,48 | ||
Potencia frigorífica (2) | kW | 13,8 | 18,4 | 25,2 | 32,5 | 37,2 | 44,8 | 62,4 | 71,8 | 93,1 | |
Potencia absorbida (2) | kW | 4,2 | 5,6 | 7,8 | 10,1 | 11,5 | 14,8 | 20,7 | 23,4 | 30,7 | |
EER (2) | 3,29 | 3,29 | 3,23 | 3,22 | 3,23 | 3,03 | 3,01 | 3,07 | 3,03 | ||
Refrigeración (versión EC) | Potencia frigorífica (1) | kW | 12,8 | 17,4 | 23,2 | 29,9 | 34,0 | 41,1 | 57,4 | 65,7 | 84,9 |
Potencia absorbida (1) | kW | 4,6 | 6,1 | 8,7 | 11,3 | 12,8 | 16,5 | 22,9 | 26,3 | 33,3 | |
EER (1) | 2,78 | 2,85 | 2,67 | 2,65 | 2,66 | 2,49 | 2,51 | 2,50 | 2,55 | ||
Potencia frigorífica (2) | kW | 13,8 | 18,4 | 25,2 | 32,5 | 37,2 | 44,8 | 62,4 | 71,8 | 93,1 | |
Potencia absorbida (2) | kW | 3,9 | 5,4 | 7,7 | 10,0 | 11,4 | 14,7 | 20,6 | 23,3 | 29,7 | |
EER (2) | 3,54 | 3,41 | 3,27 | 3,25 | 3,26 | 3,05 | 3,03 | 3,08 | 3,13 | ||
Calefacción | Potencia térmica (3) | kW | 14,1 | 19,0 | 25,9 | 33,4 | 38,3 | 49,1 | 64,8 | 75,1 | 96,6 |
Potencia absorbida (3) | kW | 4,3 | 5,6 | 7,8 | 10,0 | 11,1 | 13,9 | 20,4 | 22,4 | 28,5 | |
COP (3) | 3,28 | 3,39 | 3,32 | 3,34 | 3,45 | 3,53 | 3,18 | 3,35 | 3,39 | ||
Calefacción (versión EC): | Potencia térmica (3) | kW | 14,1 | 19,0 | 25,9 | 33,4 | 38,3 | 49,1 | 64,8 | 75,1 | 96,6 |
Potencia absorbida (3) | kW | 4,0 | 5,4 | 7,7 | 9,9 | 11,0 | 13,8 | 20,3 | 22,3 | 27,5 | |
COP (3) | 3,53 | 3,52 | 3,36 | 3,37 | 3,48 | 3,56 | 3,19 | 3,37 | 3,51 | ||
Sección de tratamiento de aire | Caudal de aire | m³/s | 0,86 | 0,94 | 1,25 | 1,58 | 1,89 | 2,36 | 3,15 | 3,93 | 4,72 |
Presión estática útil | Pa | 60 | 60 | 150 | 150 | 150 | 150 | 210 | 210 | 210 | |
Ventilador | n° | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | |
Filtros | Tipo | G4 | G4 | G4 | G4 | G4 | G4 | G4 | G4 | G4 | |
Sección de condensación | Compresor | n° | 1 | 1 | 1 | 1 | 1 | 1 | 2 | 2 | 2 |
Circuitos frigorifícos | n° | 1 | 1 | 1 | 1 | 1 | 1 | 2 | 2 | 2 | |
Etapas de parcialización | % | 0-100 | 0-100 | 0-100 | 0-100 | 0-100 | 0-100 | 0-50-100 | 0-50-100 | 0-50-100 | |
Caudal de aire | m³/s | 1,87 | 1,81 | 2,85 | 2,78 | 4,44 | 4,44 | 8,89 | 8,89 | 8,89 | |
Características eléctricas | Alimentación | V/Ph/Hz | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 |
Corriente máx. funcionamiento | A | 13 | 16 | 20 | 26 | 29 | 36 | 50 | 60 | 72 | |
Corriente máx. de arranque | A | 63 | 90 | 103 | 148 | 153 | 204 | 172 | 184 | 240 | |
Características eléctricas (versión EC) | Alimentación | V/Ph/Hz | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 |
Corriente máx. funcionamiento | A | 14 | 17 | 20 | 26 | 29 | 36 | 54 | 60 | 71 | |
Corriente máx. de arranque | A | 64 | 91 | 103 | 148 | 153 | 203 | 176 | 184 | 239 | |
Presión sonora | Versión STD (4) | dB(A) | 66 | 66 | 65 | 66 | 67 | 70 | 71 | 72 | 71 |
Pesos | Peso de transporte | kg | 430 | 470 | 525 | 595 | 610 | 695 | 1010 | 1065 | 1165 |
Peso en funcionamiento | kg | 415 | 455 | 510 | 580 | 595 | 680 | 995 | 1050 | 1150 | |
Pesos (versión EC) | Peso de transporte | kg | 455 | 510 | 570 | 645 | 660 | 755 | 1100 | 1160 | 1295 |
Peso en funcionamiento | kg | 440 | 495 | 555 | 630 | 645 | 740 | 1085 | 1145 | 1280 |
Dimensions
51 | 71 | 101 | 121 | 151 | 181 | 242 | 302 | 362 | |||
L | STD | mm | 1200 | 1450 | 1600 | 1800 | 2000 | 2140 | 2100 | 2210 | 2330 |
W | STD | mm | 1200 | 1300 | 1200 | 1450 | 1450 | 1750 | 1900 | 1900 | 1900 |
H | STD | mm | 1180 | 1210 | 1425 | 1425 | 1430 | 1490 | 1970 | 1970 | 2325 |
Notas
- 1 Temperatura del aire a la entrada del evaporador 27 °C b.s./19 °C b.h.; temperatura del aire exterior 46 °C.
- 2 Temperatura del aire a la entrada del evaporador 27 °C b.s./19 °C b.h.; temperatura del aire exterior 35 °C.
- 3 Temperatura del aire a la entrada del condensador 20 °C, temperatura del aire exterior 7 °C b.s./ 6°C b.h.
- 4 Nivel de presión sonora medida en campo libre a 1 m de la unidad conforme a ISO 3744.
- N.B. (1) Weights of WP versions and ECO accessory are specified on technical brochure.
Documentos
- Gama de productos 00_clint_international_product_over_09.2019_w.pdf
- Guías de productos _clint_international_product_guide_09.2019_w.pdf
- Folletos comerciales 06_clint_international_leaflet_flexi-air_RTQXT-M-K_51362_12.2021_w.pdf
- Cuadernos técnicos 24_RTQXT-M_K_51-362_clbxtm_156.1.pdf
- Manuales de instalación, uso y mantenimiento EN_RTQXT_M_K_051_363_REV1_20220805111857.pdf