CHA-M/MK 252-P÷684-P

Modular aircooled liquid Chillers and Heat Pumps with axial fans, Scroll compressors and plate exchanger

SOLO_FREDDO.png caldo_e_freddo1.png COMPRESSORE_SCROLL111.png ASSIALE11.png SCAMBIATORE_PIASTRE11.png R410A1.png

The liquid Chillers and Heat Pumps of CHA-M/MK 252-P÷684-P MODULAR series, with R410A refrigerant, are designed for medium and large sized service or industrial buildings. They are used, combined with terminal units, for the air conditioning of the rooms.
The MODULAR units feature a dedicated layout of the unit itself and its internal components in order to build big capacity systems through modular combination of single units.
The range is made of 4 base modules from 19 to 51 TON, featuring V design condensing coils, axial fans, single or double cooling circuit with Scroll compressors and plate exchanger.
The electric panel positioned frontally and the optimization of internal layout allow to build multi-unit modular systems of extremely compact footprint.
The multi-unit systems can be centrally controlled with master-slave logic through RS485 ModBus connection that ensure balancing of operation time among the units and backup in case of failure.

Versions

  • CHA-M/MK - Cooling only
  • CHA-M/MK/WP - Reversible Heat Pump

Power range

  • 65,0-180 kW
  • 19,0-51,0 Ton

Caractéristiques

  • Structure with supporting frame, made of galvanised sheet metal with additional protection provided by polyester powder coating.
  • Scroll compressors with oil sight glass, internal overheat protection and crankcase heater.
  • Axial fans directly coupled to an electric motor with external rotor.
  • Condenser made of copper tubes and aluminium finned coils.
  • Evaporator AISI 316 stainless steel braze welded plates type with one circuit on the refrigerant side and one on the water side in 252-P÷342-P models, with two independent circuits on the refrigerant side and one on the water side in 504-P÷684-P models, complete with water differential pressure switch.
  • R410A refrigerant.
  • Electrical board includes: main switch with door safety interlock, fuses, thermal protection relays for compressors and thermocontacts for fans.
  • Microprocessor control and regulation system.

Accessoires fournis séparément

  • CR Panneau de commande à distance
252-P342-P504-P684-P
RefroidissementPuissance frigorifique (1)kW65,390,1131180
Puissance absorbée (1)kW22,230,344,460,6
EER (1)2,942,972,942,97
Refroidissement (EN14511)Puissance frigorifique (1)kW64,989,6130179
Puissance absorbée (1)kW22,630,845,261,6
EER (1)2,872,912,872,91
ChauffagePuissance thermique (2)kW73,4100147200
Puissance absorbée (2)kW24,231,848,463,6
COP (2)3,033,153,033,15
Chauffage (EN14511)Puissance thermique (2)kW73,9101148202
Puissance absorbée (2)kW24,832,749,665,4
COP (2)2,983,082,983,08
CompresseurQuantité2244
Circuits frigorifiques1122
Étages de puissance2244
ÉvaporateurDébit d'eaul/s3,124,306,248,60
Pertes de chargekPa43484348
Raccords hydrauliques"G2"2"2"2"
Caractéristiques électriquesAlimentationV/Ph/Hz400/3/50400/3/50400/3/50400/3/50
Courant max. de fonctionnementA53,566,6107133
Courant max. de crêteA170235340470
Pression sonore (3)dB(A)60606262
PoidsPoids de transportkg54759611141211
Poids en fonctionnementkg55060011201220

Dimensions

252-P342-P504-P684-P
LSTDmm2200220022002200
WSTDmm1100110022002200
HSTDmm2045204520452045

Remarques

  • 1 Eau glacée de 12 à 7 °C, température air extérieur 35 °C.
  • 2 Eau chauffée de 40 à 45 °C, température de l'air extérieur 7°C b.s./6°C b.h.
  • 3 Niveau moyen de pression sonore mesurée en champ libre à 1 m de l'unité comme défini de ISO 3744.
  • N.B. (1) Les poids des versions WP sont rapportés dans le cahier technique.