CWW-M/K 181-P÷522-P
Watercooled liquid Chillers and Heat Pumps with Scroll compressors and plate exchangers





The CWW-M/K 181-P÷522-P HYDROPLUS liquid Chillers and Heat Pumps, with R410A refrigerant, are designed for medium-sized domestic or industrial systems which require medium-high power, space-saving units and quiet operation. This range is ideal for indoor installation and, equipped with a self-contained structure, it reduces the overall dimensions to a minimum while at the same time making installation and maintenance operations easier.
Equipped with prepainted plate structure, Scroll compressors and plate type exchangers, these units have cooling and hydraulic circuits complete with everything necessary for quick installation and high energy efficiency, even in the version with tank and pump.
A wide series of accessories, factory-assembled or supplied separately, such as the desuperheater or the total heat recovery, rounds off the variety of equipment in this product range.
Versions
- CWW-M/K - Cooling only
- CWW-M/K/WP - Reversible Heat Pump
Power range
- 58,0-176 kW
- 16,0-50,0 Ton
Caractéristiques
- Structure with supporting frame, made of galvanised sheet metal with additional protection provided by polyester powder coating.
- Scroll compressors with oil sight glass, internal overheat protection and crankcase heater.
- Condenser AISI 316 stainless steel braze welded plates type with one circuit on the refrigerant side and one on the water side.
- Evaporator AISI 316 stainless steel braze welded plates type with one circuit on the refrigerant side and one on the water side, completed with water differential pressure switch.
- R410A refrigerant.
- Electrical board includes: main switch with door safety interlock, protection modules and overload protection for compressors.
- Microprocessor control and regulation system.
Accessoires
Accessoires montés en usine
- SL Silencieux unité
- BT Dispositif pour fonctionnement à basse température de l'eau
- DS Désurchauffeur
- RT Récupérateur de chaleur totale
- IS Protocole Modbus RTU, interface sérielle RS485
Accessoires fournis séparément
- MN Manomètres de haute et basse pression
- CR Panneau de commande à distance
- SPU Réservoir tampon et simple pompe de circulation
- SPD Réservoir tampon et double pompe de circulation
- PV2 Vanne pressostatique électronique à 2 voies
- PV3 Vanne pressostatique électronique à 3 voies
- AG Plots anti-vibrations en caoutchouc
- AG1 Rubber shock absorbers for SPU and SPD modules
Technical data
181-P | 241-P | 301-P | 392-P | 522-P | |||
Refroidissement | Puissance frigorifique (1) | kW | 57,5 | 73,9 | 94,5 | 137 | 176 |
Puissance absorbée (1) | kW | 13,2 | 16,9 | 21,9 | 31,9 | 41,3 | |
Refroidissement (EN14511) | Puissance frigorifique (1) | kW | 57,1 | 73,4 | 94,0 | 136 | 175 |
Puissance absorbée (1) | kW | 14,0 | 17,9 | 23,1 | 33,5 | 43,5 | |
EER (1) | 4,08 | 4,08 | 4,07 | 4,07 | 4,03 | ||
Chauffage | Puissance thermique (2) | kW | 71,3 | 92,4 | 116 | 168 | 218 |
Puissance absorbée (2) | kW | 16,8 | 21,3 | 27,6 | 40,6 | 51,9 | |
Chauffage (EN14511) | Puissance thermique (2) | kW | 71,9 | 93,2 | 117 | 169 | 219 |
Puissance absorbée (2) | kW | 17,7 | 22,5 | 28,8 | 42,3 | 54,2 | |
COP (2) | 4,06 | 4,14 | 4,06 | 4,00 | 4,05 | ||
Compresseur | Quantité | n° | 1 | 1 | 1 | 2 | 2 |
Circuits frigorifiques | n° | 1 | 1 | 1 | 1 | 1 | |
Étages de puissance | n° | 1 | 1 | 1 | 2 | 2 | |
Évaporateur | Débit d'eau | l/s | 2,75 | 3,53 | 4,52 | 6,55 | 8,41 |
Pertes de charge | kPa | 43 | 52 | 46 | 51 | 56 | |
Raccords hydrauliques | DN | 32 | 32 | 65 | 65 | 65 | |
Condenseur | Débit d'eau | l/s | 3,38 | 4,34 | 5,56 | 8,07 | 10,38 |
Pertes de charge | kPa | 52 | 59 | 48 | 54 | 60 | |
Raccords hydrauliques | DN | 32 | 32 | 65 | 65 | 65 | |
Caractéristiques électriques | Alimentation | V/Ph/Hz | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 |
Courant max. de fonctionnement | A | 39 | 48 | 59 | 95 | 119 | |
Courant max. de crête | A | 215 | 260 | 320 | 308 | 379 | |
Unité avec réservoir et pompe | Pression statique utile pompe | kPa | 125 | 100 | 120 | 125 | 120 |
Contenu d'eau réservoir | l | 300 | 300 | 300 | 300 | 300 | |
Raccords hydrauliques | "G | 2 ½" | 2 ½" | 2 ½" | 2 ½" | 2 ½" | |
Pression sonore | Version STD (3) | dB(A) | 59 | 59 | 60 | 60 | 62 |
Avec accessoire SL (3) | dB(A) | 56 | 56 | 57 | 57 | 59 | |
Poids | Poids de transport (4) | kg | 372 | 391 | 456 | 609 | 725 |
Poids en fonctionnement (4) | kg | 380 | 400 | 470 | 620 | 750 |
Dimensions
181-P | 241-P | 301-P | 392-P | 522-P | |||
L | UNITÉ | mm | 1200 | 1200 | 1200 | 1600 | 1600 |
UNITÉ + SPU/SPD | mm | 2310 | 2310 | 2310 | 2710 | 2710 | |
W | UNITÉ | mm | 680 | 680 | 680 | 680 | 680 |
UNITÉ + SPU/SPD | mm | 680 | 680 | 680 | 680 | 680 | |
H | UNITÉ | mm | 1520 | 1520 | 1520 | 1520 | 1520 |
UNITÉ + SPU/SPD | mm | 1520 | 1520 | 1520 | 1520 | 1520 |
Remarques
- 1 Eau glacée de 12 à 7 °C, température de l'eau dans le condenseur de 30 à 35 °C.
- 2 Eau chauffée de 40 à 45 °C, température de l'eau dans l'évaporateur de 15 à 10 °C.
- 3 Niveau moyen de pression sonore mesurée en champ libre à 1 m de l'unité comme défini de ISO 3744.
- 4 Unité sans réservoir et pompe.
- N.B. (1) Les poids des versions WP sont rapportés dans le cahier technique.
Documents
- Gamme de produits 00_clint_international_product_over_09.2019_w.pdf
- Guides de produits _clint_international_product_guide_09.2019_w.pdf
- Brochures commerciales 02_clint_international_leaflet_hydroplus_09.2019_w.pdf
- Cahiers techniques 13_CWW-M_K_181-P-522-P_clbm_137.7.pdf
- Manuels d'installation, d'utilisation et d’entretien CWW-MK-181P_522P_CLMM_137.7_x5N7nEM.pdf