_clint_hydroplus.png

CWW-M/SZ/K 181÷522

Watercooled liquid Chillers and Heat Pumps with Scroll compressors and shell and tube exchangers

SOLO_FREDDO.png caldo_e_freddo1.png COMPRESSORE_SCROLL111.png SCAMBIATORE_FASCIO1.png _clint_asia_icon_60_Hz_2015.png R410A1.png

The CWW-M/SZ/K 181÷522 HYDROPLUS liquid Chillers and Heat Pumps, with R410A refrigerant, are designed for medium-sized domestic or industrial systems which require medium-high power, space-saving units and quiet operation. This range is ideal for indoor installation and it reduces the overall dimensions to a minimum while at the same time making installation and maintenance operations easier.
Equipped with Scroll compressors and shell and tube exchangers, these units have cooling and hydraulic circuits complete with everything necessary for quick installation and high energy efficiency.
A wide series of accessories, factory-assembled or supplied separately, such as the desuperheater or the total heat recovery, rounds off the variety of equipment in this product range.
The units feature 460V power supply and 60Hz frequency.

Versions

  • CWW-M/SZ/K - Cooling only
  • CWW-M/SZ/K/WP - Reversible Heat Pump

Power range

  • 52,0-169 kW
  • 15,0-48,0 Ton

Caractéristiques

  • Structure with supporting frame, made of galvanised sheet metal with additional protection provided by polyester powder coating.
  • Scroll compressors with oil sight glass, internal overheat protection and crankcase heater.
  • Shell and tube type condenser, with easily removable cast iron heads to enable access for maintenance operations. Each cooling circuit is supplied with an independent condenser. Water connections for cooling tower and Dry-Cooler operation; on request for well water.
  • Shell and tube type evaporator, with two independent circuits on the refrigerant side and one on the water side.
  • R410A refrigerant.
  • Electrical board includes: main switch with door safety interlock, protection modules and overload protection for compressors.
  • Microprocessor control and regulation system.

Accessoires montés en usine

  • SL Silencieux unité
  • BT Dispositif pour fonctionnement à basse température de l'eau
  • HR Désurchauffeur
  • HRT Récupérateur de chaleur totale
  • IS Protocole Modbus RTU, interface sérielle RS485

Accessoires fournis séparément

  • MN Manomètres de haute et basse pression
  • CR Panneau de commande à distance
  • PV2 Vanne pressostatique électronique à 2 voies
  • PV3 Vanne pressostatique électronique à 3 voies
  • AG Plots anti-vibrations en caoutchouc
  • FL Fluxostat
181241301392522
RefroidissementPuissance frigorifique (1)kW52,274,796,2129169
Puissance absorbée (1)kW11,716,821,829,837,2
ChauffagePuissance thermique (2)kW64,893,4118159210
Puissance absorbée (2)kW14,921,127,437,946,8
CompresseurQuantité11122
Circuits frigorifiques11111
Étages de puissance11122
ÉvaporateurDébit d'eaul/s2,493,574,606,168,07
Pertes de chargekPa3166575645
Raccords hydrauliques"G1 ½"2"2 ½"3"3"
CondenseurDébit d'eaul/s3,054,375,647,599,85
Pertes de chargekPa815262643
Raccords hydrauliques"G2 ½"2 ½"2 ½"2 ½"2 ½"
Caractéristiques électriquesAlimentationV/Ph/Hz460/3/60460/3/60460/3/60460/3/60460/3/60
Courant max. de fonctionnementA34425183103
Courant max. de crêteA187226278268330
Pression sonoreVersion STD (3)dB(A)5959606062
Avec accessoire SL (3)dB(A)5656575759
PoidsPoids de transportkg460482554675822
Poids en fonctionnementkg490515590735895

Dimensions

181241301392522
LSTDmm20002200220022002500
WSTDmm820820820850850
HSTDmm14001400140014001400

Remarques

  • 1 Eau glacée de 12 à 7 °C, température de l'eau dans le condenseur de 30 à 35 °C.
  • 2 Eau chauffée de 40 à 45 °C, température de l'eau dans l'évaporateur de 15 à 10 °C.
  • 3 Niveau moyen de pression sonore mesurée en champ libre à 1 m de l'unité comme défini de ISO 3744.
  • N.B. (1) Les poids des versions WP sont rapportés dans le cahier technique.