RTQXT-M/K 51÷362
Single Skin packaged Roof Top units with Scroll compressors and radial fans
The single skin Packaged Roof Top units of the FLEXI AIR series, with R410A refrigerant, can be connected to a duct network for air conditioning of small and medium surface areas for public use such as halls, shopping centres, cafeterias, restaurants and health centres, or for industrial ambients such as food processing or preservation centres.
Equipped with radial fan or EC Inverter Plug-Fan, these units are available in a cooling only and in a reversible heat pump version. The EC Inverter Plug-Fan with high energy efficiency backward blades are managed by an electronic control adjusting fan rotational speed to adapt the air flow to the system capacity.
The cabinet features a perimeter base structure composed of elements with zinc coated galvanized treatment. The frame is realized with extruded aluminium alloy sections. The perimeter panels are realized in pre-painted metal sheet.
The unit can be equipped, as an option, with a Free-Cooling Economizer section in addition to the components installed on the basic version. The ECONOMIZER is automatically controlled both in FREE-COOLING or FREE-HEATING.
Versionen
- RTQXT-M/K - Cooling only
- RTQXT-M/K/WP - Reversible Heat Pump
- RTQXT-M/K/EC - Cooling only with EC Inverter Plug-Fan
- RTQXT-M/K/EC/WP - Reversible Heat Pump with EC Inverter Plug-Fan
Power range
- 13,0-85,0 kW
- 3,6-24,0 Ton
Merkmale
- The perimeter base structure is composed of elements in passivated and press-bent galvanised sheet. The frame is realised with extruded aluminium alloy sections coupled by 3-way joints. The assembly of the base and frame is with double support and guarantees the tradable surface of the base panels, whose installation takes place without the use of projecting screws. The perimeter panels can be easily removed. They are realised in pre-painted metal sheet and allow access inside the unit for maintenance and repair operations. The structure has a 10 mm thick insulation layer.
- Scroll compressors with oil sight glass, internal overheat protection and crankcase heater.
- Condenser and evaporator made of copper tube and aluminium finned coil.
- Delivery radial fan coupled to 3-phase motors by V belt and variable pulley.
- Both the cooling only and reversible heat pump versions are available with high efficiency delivery EC INVERTER PLUG-FAN, with electronic speed control to easily adapt to the system characteristics.
- R410A refrigerant.
- Electrical board includes: main switch with door safety interlock; thermal protection relays for compressors; thermocontacts for fans of the
- condensing unit section; contactors for fans motors of the air treatment section; interface relay and electrical terminals for external connections.
- Microprocessor for the automatic control of the unit, allowing continuous display of the operational status of the unit, control set and real air temperature and, in case of partial or total block of the unit, indication of security device that intervened.
- Operating outdoor ambient air temperature up to 52 °C.
Zubehör
Im Werk montiertes Zubehör
- ECO Geräteteil Economizer Free-Cooling mit Klappen aus Aluminium und Elektromotor. Die Steuerung mit Mikroprozessor koordiniert die Öffnung der Klappe für die Steuerung der Abluft, Umluft und Frischluft.
- SL Schalldämmung der Einheit
- CC Verflüssigungsregelung bis -20 °C
- ECA EC-Inverter-Ventilatoren in dem Verflüssiger Geräteteil
- TXKC Verflüssigerregister mit schwarzer Epoxidharzbeschichtung
- TXKE Verdampfungsregister mit schwarzer Epoxidharzbeschichtung
- FTM5 Plate filters efficiency M5
- AT Regelung nach konstantem Luftstrom
- AT/P Reglung mit konstanter Nutzförderhöhe
- PF Differentialdruckwächter für Filterüberwachung
- IST Protokoll Modbus TCP/IP, Ethernet-Port
- ISB BACnet MSTP-Protokoll, serielle Schnittstelle RS485
- ISBT BACnet TCP/IP-Protokoll, Ethernet-Port
- ISS Protokoll SNMP, Ethernet-Port
- MN Hoch- und Niederdruckmanometer
- CS Schutzabdeckungen für Klappen
- RP Schutzgitter Verflüssigerregister
Lose mitgeliefertes Zubehör
- CR Fernbedienung
- CDT Fernbedienung mit Touchscreen-Raumthermostat
- AG Gummi-Schwingungsdämpfer
Technical data
51 | 71 | 101 | 121 | 151 | 181 | 242 | 302 | 362 | |||
Kühlung | Kühlleistung (1) | kW | 12,8 | 17,4 | 23,2 | 29,9 | 34,0 | 41,1 | 57,4 | 65,7 | 84,9 |
Leistungsaufnahme (1) | kW | 4,9 | 6,3 | 8,8 | 11,4 | 12,9 | 16,6 | 23,0 | 26,4 | 34,3 | |
EER (1) | 2,61 | 2,76 | 2,64 | 2,62 | 2,64 | 2,48 | 2,50 | 2,49 | 2,48 | ||
Kühlleistung (2) | kW | 13,8 | 18,4 | 25,2 | 32,5 | 37,2 | 44,8 | 62,4 | 71,8 | 93,1 | |
Leistungsaufnahme (2) | kW | 4,2 | 5,6 | 7,8 | 10,1 | 11,5 | 14,8 | 20,7 | 23,4 | 30,7 | |
EER (2) | 3,29 | 3,29 | 3,23 | 3,22 | 3,23 | 3,03 | 3,01 | 3,07 | 3,03 | ||
Kühlung (Version EC) | Kühlleistung (1) | kW | 12,8 | 17,4 | 23,2 | 29,9 | 34,0 | 41,1 | 57,4 | 65,7 | 84,9 |
Leistungsaufnahme (1) | kW | 4,6 | 6,1 | 8,7 | 11,3 | 12,8 | 16,5 | 22,9 | 26,3 | 33,3 | |
EER (1) | 2,78 | 2,85 | 2,67 | 2,65 | 2,66 | 2,49 | 2,51 | 2,50 | 2,55 | ||
Kühlleistung (2) | kW | 13,8 | 18,4 | 25,2 | 32,5 | 37,2 | 44,8 | 62,4 | 71,8 | 93,1 | |
Leistungsaufnahme (2) | kW | 3,9 | 5,4 | 7,7 | 10,0 | 11,4 | 14,7 | 20,6 | 23,3 | 29,7 | |
EER (2) | 3,54 | 3,41 | 3,27 | 3,25 | 3,26 | 3,05 | 3,03 | 3,08 | 3,13 | ||
Heizung | Heizleistung (3) | kW | 14,1 | 19,0 | 25,9 | 33,4 | 38,3 | 49,1 | 64,8 | 75,1 | 96,6 |
Leistungsaufnahme (3) | kW | 4,3 | 5,6 | 7,8 | 10,0 | 11,1 | 13,9 | 20,4 | 22,4 | 28,5 | |
COP (3) | 3,28 | 3,39 | 3,32 | 3,34 | 3,45 | 3,53 | 3,18 | 3,35 | 3,39 | ||
Heizung (Version EC) | Heizleistung (3) | kW | 14,1 | 19,0 | 25,9 | 33,4 | 38,3 | 49,1 | 64,8 | 75,1 | 96,6 |
Leistungsaufnahme (3) | kW | 4,0 | 5,4 | 7,7 | 9,9 | 11,0 | 13,8 | 20,3 | 22,3 | 27,5 | |
COP (3) | 3,53 | 3,52 | 3,36 | 3,37 | 3,48 | 3,56 | 3,19 | 3,37 | 3,51 | ||
Geräteteil Luftaufbereitung | Luftmenge | m³/s | 0,86 | 0,94 | 1,25 | 1,58 | 1,89 | 2,36 | 3,15 | 3,93 | 4,72 |
Nutzförderhöhe | Pa | 60 | 60 | 150 | 150 | 150 | 150 | 210 | 210 | 210 | |
Ventilator | n° | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | |
Filter | Tipo | G4 | G4 | G4 | G4 | G4 | G4 | G4 | G4 | G4 | |
Geräteteil Verflüssiger | Verdichter | n° | 1 | 1 | 1 | 1 | 1 | 1 | 2 | 2 | 2 |
Kältekreisläufe | n° | 1 | 1 | 1 | 1 | 1 | 1 | 2 | 2 | 2 | |
Leistungsstufen | % | 0-100 | 0-100 | 0-100 | 0-100 | 0-100 | 0-100 | 0-50-100 | 0-50-100 | 0-50-100 | |
Luftmenge | m³/s | 1,87 | 1,81 | 2,85 | 2,78 | 4,44 | 4,44 | 8,89 | 8,89 | 8,89 | |
Elektrische Merkmale | Versorgungsspannung | V/Ph/Hz | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 |
Max. Betriebsstrom | A | 13 | 16 | 20 | 26 | 29 | 36 | 50 | 60 | 72 | |
Max. Anlaufstrom | A | 63 | 90 | 103 | 148 | 153 | 204 | 172 | 184 | 240 | |
Elektrische Merkmale (Version EC) | Versorgungsspannung | V/Ph/Hz | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 |
Max. Betriebsstrom | A | 14 | 17 | 20 | 26 | 29 | 36 | 54 | 60 | 71 | |
Max. Anlaufstrom | A | 64 | 91 | 103 | 148 | 153 | 203 | 176 | 184 | 239 | |
Schalldruck | Version STD (4) | dB(A) | 66 | 66 | 65 | 66 | 67 | 70 | 71 | 72 | 71 |
Gewichte | Transportgewicht | kg | 430 | 470 | 525 | 595 | 610 | 695 | 1010 | 1065 | 1165 |
Betriebsgewicht | kg | 415 | 455 | 510 | 580 | 595 | 680 | 995 | 1050 | 1150 | |
Gewichte (Version EC) | Transportgewicht | kg | 455 | 510 | 570 | 645 | 660 | 755 | 1100 | 1160 | 1295 |
Betriebsgewicht | kg | 440 | 495 | 555 | 630 | 645 | 740 | 1085 | 1145 | 1280 |
Dimensions
51 | 71 | 101 | 121 | 151 | 181 | 242 | 302 | 362 | |||
L | STD | mm | 1200 | 1450 | 1600 | 1800 | 2000 | 2140 | 2100 | 2210 | 2330 |
W | STD | mm | 1200 | 1300 | 1200 | 1450 | 1450 | 1750 | 1900 | 1900 | 1900 |
H | STD | mm | 1180 | 1210 | 1425 | 1425 | 1430 | 1490 | 1970 | 1970 | 2325 |
Aufzeichnungen
- 1 Lufteintrittstemperatur an Verdampfer 27 °C T.K. / 19 °C F.K.; Außenlufttemperatur 46 °C.
- 2 Lufteintrittstemperatur an Verdampfer 27 °C T.K. / 19 °C F.K.; Außenlufttemperatur 35 °C.
- 3 Lufteintrittstemperatur an Verflüssiger 20 °C; Außenlufttemperatur 7 °C T.K./6 °C F.K.
- 4 Durchschnittlicher Schalldruckpegel im Freifeld im Abstand von 1 m zur Einheit, gemäß ISO 3744.
- N.B. (1) Weights of WP versions and ECO accessory are specified on technical brochure.
Dokumente
- Produktübersicht 00_clint_international_product_over_09.2019_w.pdf
- Produkthandbücher _clint_international_product_guide_09.2019_w.pdf
- Kommerzielle Broschüre 06_clint_international_leaflet_flexi-air_RTQXT-M-K_51362_12.2021_w.pdf
- Technischen Unterlagen 24_RTQXT-M_K_51-362_clbxtm_156.1.pdf
- Installations-, Bedienungs- und Wartungshandbücher EN_RTQXT_M_K_051_363_REV1_20220805111857.pdf