The liquid chillers of the CWW-M/SZ/Y/A 1301÷2601 ENERGYMAX series, with R134a refrigerant, are designed for the service sector or industrial systems requiring high power. These units are characterized by an high efficiency, in A CLASS, with EER higher than 5,05 thanks to the dedicated technical solutions as flooded shell and tube evaporator and Screw compressors.
Units are equipped with latest generation Screw compressors, flooded shell and tube evaporator and connections for condensation with tower water or well water or with a Dry-Cooler. Furthermore, they have a series of accessories which are factory-assembled of supplied separately such as desuperheater, total heat recovery and, if neccessary, a device for operating a heat pump. Designed and produced to optimize the layout of each component so as to make any necessary maintenance operations more convenient, these units have an essential and compact structure intended for indoor installation.
 
The units feature 460V power supply and 60Hz frequency.

Versionen

  • CWW-M/SZ/Y/A - Cooling only

Power range

  • 239-518 kW
  • 68,0-147 Ton

Merkmale

  • Structure with supporting frame, made of galvanised sheet metal with additional protection provided by polyester powder coating.
  • Screw compressors, with external oil separator, suction filter, oil sight glass, thermal protection, hot gas shut off valves and stepless capacity steps.
  • Shell and tube type condenser, with easily removable cast iron heads to enable access for maintenance operations.
  • Flooded shell and tube type evaporator, with casing with high efficiency tube nest designed for R134a.
  • Electronic expansion valve.
  • R134a refrigerant.
  • Electrical board includes: main switch with door safety interlock, protection modules and overload protection for compressors.
  • Microprocessor control and regulation system.

Im Werk montiertes Zubehör

  • BT Ausführung für Betrieb mit niedriger Wassertemperatur
  • HR Enthitzer
  • HRT/S Vollständige Wärmerückgewinnung, seriell angeordnet
  • FE Frostschutzheizung für Verdampfer
  • DP Vorrichtung für den Wärmepumpenbetrieb.
  • II Inverter auf einem Verdichter und Soft Start auf anderen Verdichter
  • SS Soft Starter
  • WM Web Monitoring - Drahtlose Fernüberwachung (GPRS/EDGE/3G/TCP-IP)
  • IS Modbus RTU-Protokoll, serielle Schnittstelle RS485
  • CP Potentialfreie Kontakte

Lose mitgeliefertes Zubehör

  • MN Hoch- und Niederdruckmanometer
  • CR Fernbedienung
  • AM Federschwingungsdämpfer
  • PV3 Elektronisches 3-Wege-Druckregelventil
  • AG Gummi-Schwingungsdämpfer
  • FL Strömungswächter
130115011701190120012601
KühlungKühlleistung (1)kW239282337406462518
Leistungsaufnahme (1)kW465365788696
VerdichterAnzahl111111
Kältekreisläufe111111
LeistungsstufenSteplessSteplessSteplessSteplessSteplessStepless
VerdampferWassermengel/s11,4213,4716,1019,4022,0724,75
DruckverlustekPa393740463834
WasseranschlüsseDN100100100100100100
VerflüssigerWassermengel/s13,6216,0119,2123,1226,1829,34
DruckverlustekPa484157565446
WasseranschlüsseDN100100100100100125
Elektrische MerkmaleVersorgungsspannungV/Ph/Hz460/3/60460/3/60460/3/60460/3/60460/3/60460/3/60
Max. BetriebsstromA105121148177199214
Max. AnlaufstromA361416422488529742
SchalldruckVersion STD (2)dB(A)707173757677
GewichteTransportgewichtkg291030903217341037223910
Betriebsgewichtkg301032203360358039004120

Dimensions

130115011701190120012601
LSTDmm340034003400340034003400
WSTDmm115011501150115011501150
HSTDmm210021002100210021002100

Aufzeichnungen

  • 1 Kaltwasser von 12 bis 7 °C, Wassertemperatur am Verflüssiger von 30 bis 35 °C.
  • 2 Durchschnittlicher Schalldruckpegel im Freifeld im Abstand von 1 m zur Einheit, gemäß ISO 3744.