clint AQUAPLUS.png

clint tec_inverter_scroll.png

clint tec_microchannel.png

CHA/IK/A 91÷151

A CLASS energy efficiency aircooled liquid Chillers and Heat Pumps with axial fans, Inverter Scroll compressor and plate exchanger

SOLO_FREDDO.png caldo_e_freddo21.png _icon_inverter_Scroll_compressor_14.png ASSIALE11.png SCAMBIATORE_PIASTRE11.png MICROCHANNEL_ICON.png DOCCIA_CATALOGONE.png icon_costi_gestione_2020.png _icon_A_CLASS_2018_cooling.png _icon_A_CLASS_2018_heating.png R410A1.png icon_refrigerant_R452B.png icon_refrigerant_R454B.png

The liquid Chillers and Heat Pumps of the CHA/IK/A 91÷151 series, with R410A refrigerant, are designed to satisfy the needs of small and medium domestic and service sector environments.
With a peraluman structure corrosion-resistant over time, these units can be combined with Fan Coil units or with intermediate heat exchangers for process cooling applications.
All units feature A CLASS energy efficiency and are equipped with Inverter control on Scroll compressor for a better efficiency at partial loads (SEER/IPLV/SCOP). The Microchannel condensing coil, available on the dedicated version, ensures an even higher efficiency (high EER), having a better heat exchange than traditional coils.
A wide range of accessories, factory fitted or supplied separately, complete the outstanding versatility and functionality of the series.
The units are compliant to the ErP Regulation.
On request, units can be supplied with R452B or R454B refrigerant.

Versions

  • CHA/IK/A - Cooling only
  • CHA/IK/A/MC - Cooling only with MICROCHANNEL condensing coil
  • CHA/IK/A/WP - Reversible Heat Pump

Power range

  • 26.0-42.0 kW
  • 7.3-12.0 Ton

Features

  • Structure with supporting frame, in peraluman and galvanized sheet. Sound-proofed compressor compartment.
  • DC INVERTER Scroll compressor with oil sight glass, internal overheat protection, crankcase heater and soundproofing cover.
  • Axial fans with low ventilation and special wing profile, directly coupled to external rotor motors.
  • Condenser made of copper tube and aluminum finned coils or aluminium MICROCHANNEL coils.
  • Evaporator AISI 316 stainless steel braze welded plates type, complete with water differential pressure switch. On the Heat Pump units it is always installed an antifreeze heater.
  • Electronic expansion valve.
  • R410A refrigerant. On request R452B or R454B refrigerant.
  • Electrical board includes: main switch with door safety interlock, fuses and pump remote control switch.
  • Condensing Control is included: electronic proportional device that ensures efficient and continuous functioning of the unit with outside air temperature down to -20 °C in cooling mode. It also allows to reduce the sound level especially at night. It consists of a fans speed controller with continuous speed regulation and high and low pressure transducers on cooling circuit.
  • Functioning in heating mode with outside air temperature down to -15 °C.
  • Microprocessor control and regulation system.
  • Advanced functions: remote set-point with 0-10V signal, remote set-point with 4-20mA signal, remote signal for second set-point activation, demand limit from digital input, management of hybrid systems, management of domestic hot water production.

Factory fitted accessories

  • BT Low water temperature kit
  • TX Coil with pre-coated fins
  • TXB Coil with epoxy treatment
  • PS Single circulating pump
  • GS Single circulating pump gasket for glycol >30%

Loose accessories

  • CR Remote control panel
  • IS Modbus RTU protocol, RS485 serial interface
  • RP Coils protection metallic guards
  • AG Rubber shock absorbers
91101131151
Cooling STD versionsCooling capacity (1)kW25,830,535,942,3
Absorbed power (1)kW8,09,511,313,4
EER (1)3,223,213,183,16
Cooling STD versions (EN14511)Cooling capacity (1)kW25,730,435,842,2
Absorbed power (1)kW8,19,611,413,6
EER (1)3,193,163,133,11
SEER (2)4,424,164,214,22
Energy Efficiency (2)%174163165166
Cooling MC versionsCooling capacity (1)kW25,830,535,942,3
Absorbed power (1)kW7,99,411,213,3
EER (1)3,273,243,213,18
Cooling MC versions (EN14511)Cooling capacity (1)kW25,730,435,842,2
Absorbed power (1)kW8,09,511,313,5
EER (1)3,233,203,163,13
SEER (2)4,484,214,264,27
Energy Efficiency (2)%176165167168
Heating STD versionsHeating capacity (3)kW28,734,340,448,0
Absorbed power (3)kW8,19,911,814,0
COP (3)3,543,463,423,43
Heating STD versions (EN14511)Heating capacity (3)kW28,834,440,548,1
Absorbed power (3)kW8,210,112,014,2
COP (3)3,513,423,373,38
SCOP (4)3,743,753,543,74
Energy Efficiency (4)%147147139147
Energy Class (5)A+A+A+A+
SCOP (6)2,952,962,933,07
Energy Efficiency (6)%115115114120
Energy Class (7)A+A+A+A+
CompressorQuantity1111
EvaporatorWater flowl/s1,231,461,712,02
Pressure dropskPa20293131
Water connections"G1 ¼"1 ¼"1 ¼"1 ¼"
Electrical characteristicsPower supplyV/Ph/Hz400/3+N/50400/3+N/50400/3+N/50400/3+N/50
Max. running currentA21242734
Max. starting currentA11141518
Unit with pumpPump available static pressurekPa140115150105
Water connections"G1 ¼"1 ¼"1 ¼"1 ¼"
Sound pressureSTD versions (8)dB(A)60616262
MC versions (8)dB(A)59606161
WeightsTransport weightkg224239269283
Operating weightkg229244275289

Dimensions

91101131151
LSTD/MCmm1850185018501850
WSTD/MCmm1000100010001000
HSTD/MCmm1300130013001300

Notes

  • 1 Chilled water from 12 to 7 °C, ambient air temperature 35 °C.
  • 2 Seasonal energy efficiency of cooling at low temperature. According to EU Regulation n. 2016/2281.
  • 3 Heated water from 40 to 45 °C, ambient air temperature 7 °C d.b./6 °C w.b.
  • 4 Seasonal energy efficiency of heating at low temperature with average climatic conditions. According to EU Regulation n. 813/2013.
  • 5 Seasonal energy efficiency class of heating at low temperature with average climatic conditions. According to EU Regulation n. 811/2013.
  • 6 Seasonal energy efficiency of heating at medium temperature with average climatic conditions. According to EU Regulation n. 813/2013.
  • 7 Seasonal energy efficiency class of heating at medium temperature with average climatic conditions. According to EU Regulation n. 811/2013.
  • 8 Sound pressure level measured in free field conditions at 1 m from the unit. According to ISO 3744.
  • N.B. (1) Data of MC version are specified on technical brochure.
  • N.B. (2) Weights of WP version are specified on technical brochure.