TXW 132÷284

clint tec_ec_inverter_fans.png

TXW 132÷284

Water cassette 3-speed or EC Inverter radial fan

_icona_clint_solo_raffreddamento_2024.png _icona_clint_solo_raffreddamento-riscaldamento_2024.png _icona_clint_fan_centrifugo_2024.png _icona_clint_fan_centrifugo_EC_2024.png _icona_clint_refrigerant_H2O_2024.png

The Water Cassettes TXW 132÷284 have been projected to be installed on false ceiling. The intuitive design makes installation and maintenance process easier, while guaranteeing the highest levels of energy efficiency and silence, both in domestic environments or in the services sector including offices, hotels, restaurants, gyms and shops.
When part of a hydronic system equipped with a Liquid Chiller, the Water Cassette generates cool air, while, during the winter, if combined with a thermal system, it provides warm air, making possible to meet home or business heating needs. The series, in addition to having a rich set of accessories to complete the unit, also has an attractive and modern intake grill cover panel, with neutral and well-balanced shapes that integrates perfectly in the surrounding environment as well as adjustable deflectors to distribute the air in the room in an ideal manner.
Units are available both with 3-Speed and EC Inverter fans. The units equipped with EC Inverter motor modulate the air flow, adapting the performances instant to instant to the actual needs of the room to be conditioned, assuring a total comfort with greater energy savings.

Versions

  • TXW - Base unit for 2-Pipe system
  • TXW/WS - Base unit for 4-Pipe system
  • TXW/EC - Unit with EC Inverter fan for 2-pipe system
  • TXW/WS/EC - Unit with EC Inverter fan for 4-Pipe system

Power range

  • 2.5-11.0 kW
  • 0.7-3.2 Ton

Features

  • Load-bearing structure made of extremely thick galvanized steel-sheet with internal thermo-acoustic insulation. External brackets on the four corners for easy fixing to the roof.
  • Cover panel made of ABS, white RAL 9003 color, designed with the “Hook & Fix” coupling system. Central air intake grill with four manually adjustable air supply side flaps. Friction snap flaps, to ensure stable and uniform positioning.
  • Predisposition with fresh air connection and with supply air connection.
  • Air conveyor and condensate drain pan made by ABS to guarantee strength and long life. Condensate drain pan obtained in a single piece, equipped with a drain with cap for the total emptying in case of maintenance.
  • Centrifugal type condensate pump, including no-return valve to avoid frequent on/off and a two-level floater for the control of the condensate level and for alarm activation.
  • Heat exchanger coil made of copper pipes and hydrophilic aluminium fins for a better evacuation of the condensate, manual air vent and water drain valves.
  • Air filter easy to remove and to wash, made of a metal frame holding filtering section.
  • Radial fan with wing profile blades and built-in 3-Speed electric motor.
  • Radial fan with wing profile blades and built-in EC inverter electric motor. Modulating regulation with 0-10Vdc signal with control panels provided as accessory or with independent regulation system.
  • Universal connecting terminal (mounted)

Factory fitted accessories

  • EH Supplementary electrical heater
  • UCB Universal regulation card with Modbus RTU protocol
  • SNA Air temperature sensor for UCB
  • SNW2 Summer/winter water temperature probe for UCB
  • SNW3 Minimum water temperature probe for UCB
  • IRT Motherboard with IR receiver and remote control for AC versions

Loose accessories

  • GR Cover panel with grill
  • C Auxiliary condensate drain pan
  • SFA Air renewal flange
  • SFD Duct connection flange
  • V23 3-Way on/off valves for 2-Pipe system
  • V23M 3-Way modulating valves for 2-Pipe system
  • V22 2-Way On/Off valves for 2-Pipe system
  • V22M 2-Way modulating valves for 2-pipe system
  • V43 3-Way On/Off valves for 4-Pipe system
  • V43M 3-Way modulating valves for 4-Pipe system
  • V42 2-Way On/Off valves for 4-Pipe system
  • V42M 2-Way modulating valves for 4-Pipe system
  • TA1 Wall mounted electronic ambient thermostat for AC versions
  • VR1 Wall mounted electronic speed control panel for AC versions
  • DR1 Wall-mounted manual electronic control panel for AC versions
  • DR2 Wall mounted automatic electronic control panel for AC versions
  • DRH1 Wall mounted configurable electronic control panel for AC versions
  • DRH2 Wall mounted configurable electronic control panel for AC/EC versions
  • IRC Digital wall control panel for UCB
  • MC4 Multicontrol connection card for AC version
  • SNW4 Water temperature probe
  • TMB3 Minimun hot water temperature thermostat 32°C
  • TMB4 Minimum hot water temperature thermostat 42°C
132142153163174184253263274284
Cooling 2-Pipe unitTotal cooling capacity (1)kW2,513,034,234,715,295,898,048,9410,0411,19
Sensible cooling capacity (1)kW2,032,533,233,663,744,236,146,947,108,10
Water flow (1)l/h43152072680890810111380153417231920
Pressure drops (1)kPa7101215162016192023
Heating 2-Pipe unitHeating capacity (2)kW2,993,694,795,305,295,899,139,8810,0811,17
Water flow (2)l/h52164383492392110251590172117551947
Pressure drops (2)kPa8121317141717172020
Cooling 4-Pipe unitTotal cooling capacity (1)kW2,513,033,764,185,295,897,137,9410,0411,19
Sensible cooling capacity (1)kW2,032,533,003,393,744,235,706,457,108,10
Water flow (1)l/h43152064571790810111224136217231920
Pressure drops (1)kPa7101215162016192023
Heating 4-Pipe unitHeating capacity (3)kW3,494,294,595,194,595,198,789,988,789,98
Water flow (3)l/h306376402455402455770875770875
Pressure drops (3)kPa12192228222825302530
Cooling 2-Pipe unit (EC version)Total cooling capacity (1)kW---3,03---4,71---5,89---8,94---11,19
Sensible cooling capacity (1)kW---2,53---3,66---4,23---6,94---8,10
Water flow (1)l/h---520---808---1011---1534---1920
Pressure drops (1)kPa---10,0---15,0---20,0---19,0---23,0
Heating 2-Pipe unit (EC version)Heating capacity (2)kW---3,69---5,30---5,89---9,88---11,17
Water flow (2)l/h---643---923---1025---1721---1947
Pressure drops (2)kPa---12,0---17,0---17,0---17,0---20,0
Cooling 4-Pipe unit (EC version)Total cooling capacity (1)kW---------4,18---5,89---7,94---11,19
Sensible cooling capacity (1)kW---------3,39---4,23---6,45---8,10
Water flow (1)l/h---------717---1011---1362---1920
Pressure drops (1)kPa---------15,0---20,0---19,0---23,0
Heating 4-Pipe unit (EC version)Heating capacity (2)kW---------5,19---5,19---9,98---9,98
Water flow (2)l/h---------455---455---875---875
Pressure drops (2)kPa---------28,0---28,0---30,0---30,0
Water connections2-Pipe (In / Out)"G3/4"3/4"3/4"3/4"3/4"3/4"3/4"3/4"3/4"3/4"
4-Pipe (In / Out)"G3/4"3/4"3/4"3/4"3/4"3/4"3/4"3/4"3/4"3/4"
Air flowMaxm³/h5806527728687728681544173715441737
Medm³/h4044546447246447241288144912881449
Minm³/h280315424477424477848954848954
Air flow (EC version)Maxm³/h---652---868---868---1737---1737
Minm³/h---272---260---260---495---495
Electrical characteristicsPower supplyV/Ph/Hz230/1/50-60230/1/50-60230/1/50-60230/1/50-60230/1/50-60230/1/50-60230/1/50-60230/1/50-60230/1/50-60230/1/50-60
Max absorbed powerkW0,050,050,090,090,090,090,180,180,180,18
Electrical characteristics (EC version)Power supplyV/Ph/Hz---230/1/50-60---230/1/50-60---230/1/50-60---230/1/50-60---230/1/50-60
Max absorbed powerkW---0,07---0,07---0,07---0,15---0,15
Sound pressureMax (4)dB(A)42424848484851515151
Med (4)dB(A)32324444444447474747
Min (4)dB(A)26263333333336363636
Sound pressure (EC version)Max (4)dB(A)---42,0---48,0---48,0---51,0---51,0
Min (4)dB(A)---27,0---26,0---26,0---29,0---29,0
Weights 2-PipeBody transport weightkg20202121222240404242
Body operating weightkg17171818191935353737
Grille transport weightkg2222225555
Weights 4-PipeBody transport weightkg21212121222241414343
Body operating weightkg18181818191936363838
Grille transport weightkg2222225555

Dimensions

132142153163174184253263274284
LBODYmm5705705705705705701160116011601160
PANELmm6306306306306306301225122512251225
WBODYmm570570570570570570570570570570
PANELmm630630630630630630630630630630
HBODYmm250250250250250250250250250250
PANELmm30303030303030303030

Notes

  • 1 Ambient air temperature 27 °C d.b./19 °C w.b., water temperature 7/12 °C.
  • 2 Ambient air temperature 20 °C d.b., water temperature 45/40 °C,
  • 3 Ambient air temperature 20 °C d.b., water temperature 65/55 °C.
  • 4 Sound pressure level measured at 1 m from the unit with reverberation time 0,5 s.
  • N.B. (1) Maximum inlet water temperature 75 °C.
  • N.B. (2) Inhibited ethylene glycol can be added to the water.
  • N.B. (3) Maximum operating pressure 1500 kPa.