_logo_modular_2017.png

CHA-M/MK 252÷684

Modular aircooled liquid Chillers and Heat Pumps with axial fans, Scroll compressors and shell and tube exchanger

SOLO_FREDDO.png caldo_e_freddo1.png COMPRESSORE_SCROLL111.png ASSIALE11.png SCAMBIATORE_FASCIO1.png R410A1.png

The liquid Chillers and Heat Pumps of CHA-M/MK 252÷684 MODULAR series, with R410A refrigerant, are designed for medium and large sized service or industrial buildings. They are used, combined with terminal units, for the air conditioning of the rooms.
The MODULAR units feature a dedicated layout of the unit itself and its internal components in order to build big capacity systems through modular combination of single units.
The range is made of 4 base modules from 18 to 51 TON, featuring V design condensing coils, axial fans, single or double cooling circuit with Scroll compressors and shell and tube exchanger.
The electric panel positioned frontally and the optimization of internal layout allow to build multi-unit modular systems of extremely compact footprint.
The multi-unit systems can be centrally controlled with master-slave logic through RS485 ModBus connection that ensure balancing of operation time among the units and backup in case of failure.

Versions

  • CHA-M/MK - Cooling only
  • CHA-M/MK/WP - Reversible Heat Pump

Power range

  • 65.0-179 kW
  • 18.0-51.0 Ton

Features

  • Structure with supporting frame, made of galvanised sheet metal with additional protection provided by polyester powder coating.
  • Scroll compressors with oil sight glass, internal overheat protection and crankcase heater.
  • Axial fans directly coupled to an electric motor with external rotor.
  • Condenser made of copper tubes and aluminium finned coils.
  • Shell & tube type evaporator with one circuit on the refrigerant side and one on the water side in 252÷342 models; with two independent circuits on the refrigerant side and one on the water side in 504÷684 models, complete with water differential pressure switch.
  • R410A refrigerant.
  • Electrical board includes: main switch with door safety interlock, fuses, thermal protection relays for compressors and thermocontacts for fans.
  • Microprocessor control and regulation system.

Loose accessories

  • CR Remote control panel
252342504684
CoolingCooling capacity (1)kW64,889,4130179
Absorbed power (1)kW22,130,144,260,2
EER (1)2,932,972,932,97
Cooling (EN14511)Cooling capacity (1)kW64,589,0129178
Absorbed power (1)kW22,430,544,861,0
EER (1)2,872,912,872,91
HeatingHeating capacity (2)kW72,899,2146198
Absorbed power (2)kW24,131,648,263,2
COP (2)3,023,143,023,14
Heating (EN14511)Heating capacity (2)kW73,199,7146199
Absorbed power (2)kW24,532,349,064,6
COP (2)2,983,092,983,09
CompressorQuantity2244
Refrigerant circuits1122
Capacity steps2244
EvaporatorWater flowl/s3,104,276,218,60
Pressure dropskPa25352535
Water connections"G2"2"2"2"
Electrical characteristicsPower supplyV/Ph/Hz400/3/50400/3/50400/3/50400/3/50
Max. running currentA53,566,6107133
Max. starting currentA170235340470
Sound pressure  (3)dB(A)60606262
WeightsTransport weightkg62268712631393
Operating weightkg65072013201460

Dimensions

252342504684
LSTDmm2200220022002200
WSTDmm1100110022002200
HSTDmm2045204520452045

Notes

  • 1 Chilled water from 12 to 7 °C, ambient air temperature 35 °C.
  • 2 Heated water from 40 to 45 °C, ambient air temperature 7 °C d.b./6 °C w.b.
  • 3 Sound pressure level measured in free field conditions at 1 m from the unit. According to ISO 3744.
  • N.B. (1) Weights of WP version are specified on technical brochure.