clint AIR-X.png

clint tec_inverter_scroll_2025.png

clint tec_ec_inverter_plug_fans_2025.png

RTQ/IK/EC 101÷181

Single or double skin packaged Roof Top units with Inverter Scroll compressor and EC Inverter Plug-Fan

_icona_clint_solo_raffreddamento_2024.png _icona_clint_solo_raffreddamento-riscaldamento_2024.png _icona_clint_compressore_scroll_inverter_2024.png _icona_clint_fan_plug_EC_inverter_2024.png _icona_clint_solution_singolo_pannello_2024.png _icona_clint_solution_doppio_pannello_2024.png _icona_clint_solution_MS_2024.png _icona_clint_refrigerant_R410A_2024.png _icona_clint_refrigerant_R454B_2024.png

The packaged Roof Top units of this series are the ideal solution for air conditioning of medium surfaces such as shopping malls, restaurants and canteens. These units are equipped with Inverter Scroll compressor with R410A refrigerant, and are available in Cooling only and reversible Heat Pump version, also with Free-Cooling with 2 dampers. It is equipped with EC Inverter Plug-Fans, managed by an electronic control adjusting fans' rotational speed to adapt the air flow to the system capacity. For MS versions it is possible to connect an additional enthalpy wheel heat recovery module.


On request, units can be supplied with R454B refrigerant.
The units are compliant to the ErP Regulation.

Versions

  • RTQ/IK/EC - Cooling only
  • RTQ/IK/EC/WP - Reversible Heat Pump
  • RTQ/IK/EC/MS - Cooling only with Free-Cooling section (2 dampers)
  • RTQ/IK/EC/WP/MS - Reversible Heat Pump with free-cooling section (2 dampers)

Power range

  • 19.0-42.0 kW
  • 5.4-12.0 Ton

Features

  • INVERTER Scroll compressor with oil sight glass, internal overheat protection, crankcase heater and soundproofing cover.
  • Condenser and evaporator with copper tube and aluminium finned coil.
  • EC INVERTER PLUG-FAN delivery fan with high energy efficient reversed blades with external rotor motor and electronic speed adjustment for easy adaptation to plant features.
  • Electronic expansion valve.
  • Electrical board includes: disconnector switch with door lock; circuit breakers to protect each electrical utility (compressor, fans, etc.) contactors for the fan motors of the air treatment section and for the condensation fans; interface relays and push-in type terminals for easy and safe wiring including external customer connections.
  • Electronic proportional device: condensation control that allows the speed of the condensing-side fans to be adjusted according to the required load, allowing the sound level of the unit to be attenuated.
  • Microprocessor for the automatic control of the unit.
  • MS. Free-Cooling section with 2 dampers - Further to components of the basic version, includes two aluminium dampers with spring return servomotors (dampers with opposite movement).
  • Communication with Modbus RTU protocol through RS485 serial interface.
  • Structure of base perimeter made of steel sheet elements galvanised, passive treated and press-bent. The frame is made of extruded aluminium alloy profiles connected by 3 way joints. The perimeter panels are made of pre-painted sheet metal, easily removable, and allow access to the inside of the unit for maintenance. The panels on the air-handling side and condensate side are provided with insulation material. By selecting the DBK or DBK1 option, the unit will be supplied with 25 mm thick sandwich panels.
  • R410A refrigerant. On request R454B refrigerant.

Factory fitted accessories

  • DBK Double skin
  • DBK1 Double skin for main unit and rotary heat recovery unit
  • SL Unit silencement
  • ECA EC Inverter fans on condensing section
  • TXC Condensing coil with pre-coated fins
  • TXE Evaporating coil with pre-coated fins
  • FT7 Plate filters efficency ePM1 50% (F7)
  • FT8 Plate filters efficency ePM1 65% (F8)
  • AT Constant air flow regulation control
  • AT/P Constant available static pressure regulation control
  • AT/C Control adjustment of the air flow according to the load
  • EHG Electrical heater with step regulation
  • CH Enthalpic control
  • SQ Air quality probe
  • SQO Air quality probe (CO2)
  • SQV Air quality probe (CO2+VOC)
  • SC Smoke sensor
  • SB Fire sensor
  • PF Differential pressure switch filters control
  • IST Modbus TCP/IP protocol, Ethernet port
  • ISBT BACnet IP protocol, Ethernet port
  • ISS SNMP protocol, Ethernet port
  • IAV Remote set-point, 0-10V signal
  • IAA Remote set-point, 4-20mA signal
  • IAS Remote signal for second set-point activation
  • IDL Demand limit from digital input
  • MN High and low pressure gauges
  • CS Dampers rain hood

Loose accessories

  • CR Remote control panel
  • CDT Touch Screen room thermostat with unit visualization
  • RP Coils protection metallic guards
  • AG Rubber shock absorbers
  • AG3 Rubber shock absorbers for F-Module
  • AG4 Rubber shock absorbers for RWH module
101121151181
CoolingCooling capacity (1)kW19,124,431,141,6
Absorbed power (1)kW6,48,810,616,2
Cooling (EN 14511)SEER (2)4,714,364,573,87
Energy Efficiency (2)%185171180152
HeatingHeating capacity (3)kW19,424,631,043,9
Absorbed power (3)kW6,28,210,315,5
Heating (EN14511)SCOP (4)3,683,613,423,39
Energy Efficiency (4)%144141134133
Air treatment sectionAir flowm³/h3800510066008000
Available static pressurePA100120120150
Fan1111
Condensing sectionCompressor1111
Refrigerant circuits1111
Electrical heaterPower supplyV/Ph/Hz400/3/50400/3/50400/3/50400/3/50
Heating capacitykW18182727
Max absorbed currentA26263939
Steps2222
Electrical characteristicsPower supplyV/Ph/Hz400/3/50400/3/50400/3/50400/3/50
Max. running currentA16182234
Max. starting currentA11121318
Sound pressureSTD version (5)dB(A)71717274
With SL accessory (5)dB(A)68686971
WeightsTransport weightkg610615805815
Operating weightkg605610800810

Dimensions

101121151181
LSTD/MSmm1950195022002200
WSTD/MSmm1450145017501750
HSTD/MSmm1435143514701470

Notes

  • 1 Evaporator inlet air temperature 27 °C d.b./19 °C w.b.; ambient air temperature 35 °C.
  • 2 Seasonal energy efficiency of cooling. According to EU Regulation n. 2016/2281.
  • 3 Condenser inlet air temperature 20 °C, ambient air temperature 7 °C d.b./6 °C w.b.
  • 4 Seasonal energy efficiency of heating with average climatic conditions. According to EU Regulation n. 2016/2281.
  • 5 Sound pressure level measured in free field conditions at 1 m from the unit. According to ISO 3744.
  • N.B. (1) Weights of WP version are specified on technical brochure.