DXDXT-M/K 85÷660

Ducted Blower Split Systems. High ambient temperature (up to 52°C)

SOLO_FREDDO.png CALDO_FREDDO_MIDY.png COMPRESSORE_SCROLL111.png _CLINT_icon_XT_gold_2015.png R410A1.png

The ducted blower Split Systems of DXDXT-M/K series are the ideal solution for keeping the best comfort level in large-sized spaces as offices, shops, hotels or education facilities.
The range comprises 12 models from 85.000 BTU/h to 660.000 BTU/h and the systems are composed of one indoor unit connected to up to four outdoor units, depending on the cooling capacity required.
The systems operate with R410A refrigerant and feature Scroll compressor.
The units are designed for installation both in service rooms or built-in; the air ducts, totally hidden on the ceiling or on walls, provide the perfect comfort without compromising on the building architecture and design. Models over 140.000 BTU/h feature both horizontal and vertical air outlet, which can be chosen directly onsite, to allow the highest flexibility in installation.
The ducts ensure an even distribution of conditioned air to every corner of the room. Even multiple areas can be conditioned simultaneously just with one indoor unit.
The DXDXT-M/K models ensure the perfect functioning even on regions with high temperature, being able to work up to 52°C external air temperature.

Versiones

  • DXDXT-M/K - Cooling only (INU)
  • DXDXT-M/K - Cooling only (OTU)
  • DXDXT-M/K/WP - Reversible Heat Pump (INU)
  • DXDXT-M/K/WP - Reversible Heat Pump (OTU)

Características

  • Indoor and Outdoor units are made of galvanized steel sheet with electrostatic powder paint. Indoor units are complete with polyethylene for thermal and acoustical purpose.
  • Scroll compressors with oil sight glass, with internal overheat protection and crankcase heater.
  • Indoor units are provided with radial fans, directly coupled with single-phase 3-speed electric motor (to build models' sizes 85 – 110) or to 3-phase motors by V belt and variable pulley (to build models' sizes 140 – 660). Outdoor units are provided axial fans directly coupled to electric motor.
  • Indoor units to build models' sizes 85 - 165 come with standard horizontal air discharge; indoor units to build models' sizes 140 - 165 are convertible to vertical air discharge on site. Indoor units to build models' sizes 220 - 660 come with standard vertical air discharge and they are convertible to horizontal air discharge on site.
  • Indoor and Outdoor units are provided with copper tube and aluminum finned coils precharged with nitrogen.
  • All Indoor units are provided with return air plenum and standard cleanable filter.
  • Microprocessor for the automatic control of the unit allowing continuous display of the operational status, control the set and real air temperature and, in case of partial or total unit stop, indication of security device that intervened through a wired wall pad as standard.
  • Units matching with two or more outdoor units are provided with a sequential controller allowing part loading of the system capacity.
  • Wired wall pad included on indoor unit.
85110140165220280330390440495560660
RefrigeraciónPotencia frigorífica (1)BTU/h75000100000125000150000200000250000300000350000400000450000500000600000
Potencia frigorífica (1)kW22,029,336,643,958,673,287,9103117132147176
Potencia absorbida (1)kW11,214,117,824,428,836,451,553,956,776,277,998,7
Potencia frigorífica (2)BTU/h85000111000140000165000220000280000330000390000440000495000560000660000
Potencia frigorífica (2)kW24,932,540,648,364,482,096,7114129145164193
Potencia absorbida (2)kW9,411,814,920,524,130,543,145,247,563,865,382,7
CalefacciónPotencia térmica (3)BTU/h78200104000129700155800207600259500311400363300415200467100519000622800
Potencia térmica (3)kW22,930,538,045,660,876,091,2106122137152183
Potencia absorbida (3)kW8,711,514,520,523,529,642,043,946,262,163,580,4
Unidad internaCaudal de aire maxm³/s1,21,31,92,13,03,74,25,05,76,46,98,3
Presión estática útilPa150150150150150200200200200250250300
Conexion de líquidoinch5/8"5/8"5/8"5/8"5/8"5/8"5/8"5/8"5/8"5/8"5/8"5/8"
Conexión del gasinch1-1/8"1-1/8"1-3/8"1-3/8"1-1/8"1-3/8"1-3/8"1-3/8" . 1-1/8"1-1/8"1-3/8"1-3/8"1-3/8"
Desagüe condensainch1"1"1"1"1"1"1"1"1"1"1"1"
Presión sonora máx (4)dB(A)565758596062656566676868
Unidad externaCompresor111111111111
CompresorTipoScrollScrollScrollScrollScrollScrollScrollScrollScrollScrollScrollScroll
Conexion de líquidoinch5/8"5/8"5/8"5/8"5/8"5/8"5/8"5/8"5/8"5/8"5/8"5/8"
Conexión del gasinch1-1/8"1-1/8"1-3/8"1-3/8"1-1/8"1-3/8"1-3/8"1-3/8" . 1-1/8"1-1/8"1-3/8"1-3/8"1-3/8"
Presión sonora (5)dB(A)575758585757585757-56585758
Longitud máx conexionesDistancia máxima OTU-INU (6)m505050505050505050505050
Altura máxima OTU-INU (6)m303030303030303030303030
Características eléctricasAlimentación unidad externaV/Ph/Hz230/1/50230/1/50400/3+N/50400/3+N/50400/3+N/50400/3+N/50400/3+N/50400/3+N/50400/3+N/50400/3+N/50400/3+N/50400/3+N/50
Alimentación unidad internaV/Ph/Hz400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50
Corriente máx. funcionamientoA25313444536990101105136147176
Corriente máx. de arranqueA119129180243148212288244194255284366
PesosPeso de transporte unidad interna (7)kg127150215217235368378503556570850920
Peso en funcionamiento unidad interna (7)kg122145210212225358368493546560840910
Peso de transporte unidad externa (7)kg185190197230190197230197 / 190190230197230
Peso en funcionamiento unidad externa (7)kg175180187220180187220187/180180220187220

Dimensions

85110140165220280330390440495560660
LUNIDAD INTERNAmm158018801575157519051905190519052420242024202440
UNIDAD EXTERNAmm9659659651130965965113096596511309651130
WUNIDAD INTERNAmm7657659859859851240124012401520152015201820
UNIDAD EXTERNAmm9759759751110975975111097597511109751110
HUNIDAD INTERNAmm4304308708708701165116513851385138513851770
UNIDAD EXTERNAmm950950950950950950100095095010009501000

Notas

  • 1 Temperatura del aire interior 27 °C b.s./19 °C b.h.; temperatura del aire exterior 46 ° b.s.
  • 2 Temperatura del aire interior 27 °C b.s./19 °C b.h.; temperatura del aire exterior 35 ° b.s.
  • 3 Temperatura del aire interior 20 °C b.h; temperatura del aire exterior 7 °C b.s./6 °C b.h.
  • 4 Presión sonora medida a una distancia de 1 m y con tiempo de reverberación de 0,5 s.
  • 5 Nivel de presión sonora medida en campo libre a 1 m de la unidad conforme a ISO 3744.
  • 6 Longitud máxima alcanzable con diámetro de tubería adecuado y sifones.
  • 7 Unidad solo frío