RTA/K/EC 182÷804
Double skin packaged Roof Top units with Scroll compressors and EC Inverter Plug-Fans
The double skin packaged Roof Top units are the ideal solution for air conditioning of wide surfaces such as shopping malls and restaurants, canteens or for industrial areas. Those units feature Inverter Scroll compressor with R410A refrigerant and EC Inverter Plug-Fans.
Equipped with extruded aluminium alloy sections and 50mm-thick sandwich panelling, these units are available in Cooling only and Reversible Heat Pump version.
The flat or pocket filters help to keep the air quality at a suitable level.
On request, units can be supplied with R454B refrigerant.
The units are compliant to the ErP Regulation.
Versiones
- RTA/K/EC - Cooling only with EC Inverter Plug-Fans
- RTA/K/EC/WP - Reversible Heat Pump with EC Inverter Plug-Fans
Power range
- 58,0-252 kW
- 17,0-72,0 Ton
Características
- Structure of base perimeter made of steel sheet elements galvanised. Frame made of extruded aluminium alloy profiles connected by 3 way joints. Section connection is effected by means of assembling conic stirrups and water proofing is granted by gaskets.
- Scroll compressors with oil sight glass, internal overheat protection and crankcase heater.
- Condenser and evaporator with copper tube and aluminium finned coil.
- EC INVERTER PLUG-FAN delivery fan with high energy efficient reversed blades with external rotor motor and electronic speed adjustment for easy adaptation to plant features.
- Electrical board includes: door interlocking isolator, fuses, thermal protection relays on compressors, thermocontacts for the fans of the condensing unit and contactors for the fan motors of the air handling unit.
- Microprocessor for the automatic control of the unit.
- R410A refrigerant. On request R454B refrigerant.
Accesorios
Accesorios montados en fábrica
- HUR Toma de aire horizontal, impulsión de aire hacia arriba, puerta de inspección a la derecha
- HUL Toma de aire horizontal, impulsión de aire hacia arriba, puerta de inspección a la izquierda
- HDR Toma de aire horizontal, impulsión de aire hacia abajo, puerta de inspección a la derecha
- HDL Toma de aire horizontal, impulsión de aire hacia abajo, puerta de inspección a la izquierda
- HLR Toma de aire horizontal, impulsión de aire a la izquierda, puerta de inspección a la derecha
- HRL Toma de aire horizontal, impulsión de aire a la derecha, puerta de inspección a la izquierda
- IM Interruptores magnetotérmicos
- RE Relé de voltaje mínimo y máximo ajustable y control de fase
- SL Silenciamiento unidad
- SNM Sonda de impulsión de aire
- RFM Grifo circuito frigorífico en la línea de descarga
- RFL Grifo circuito frigorífico en la línea de líquido
- CC Control de condensación hasta -20 °C
- ECA Ventiladores EC Inverter en la sección de condensación
- TXC Batería condensante con aletas prebarnizadas
- TXE Batería evaporante con aletas prebarnizadas
- FT/M6 Filtros de bolsas flexibles eficiencia ePM10 70% (M6)
- FT/M7 Filtros de bolsas flexibles eficiencia ePM2.5 70% (F7)
- FT/M8 Filtros de bolsas flexibles eficiencia ePM1 70% (F8)
- FT/R6 Filtros de bolsas rígidas eficiencia ePM10 70% (M6)
- FT/R7 Filtros de bolsas rígidas eficiencia ePM1 50% (F7)
- FT/R8 Filtros de bolsas rígidas eficiencia ePM1 70% (F8)
- FT/E Filtro electrostático
- AT Control regulación caudal aire constante
- AT/P Control de regulación presión estática útil constante
- AT/C Control de ajuste del flujo de aire según la carga
- WS2 Batería de agua caliente con válvula de 3 vías
- EHG Batería calefacción con resistencia eléctrica por etapas
- SSA Sistemas de saneamiento activo para aire y ambientes
- PF Presostato diferencial para el control de los filtros
- SB Sensor de detección de incendios
- SC Sensor de detección de humo
- IS Protocolo Modbus RTU, interfaz serial RS485
- IST Protocolo Modbus TCP/IP, puerto Ethernet
- ISBT Protocolo BACnet IP, puerto Ethernet
- ISB1 Protocolo BACnet MSTP, interfaz serial RS485, con certificación BTL.
- ISBT1 protocolo BACnet IP, puerto Ethernet, con certificación BTL.
- ISS Protocolo SNMP, puerto Ethernet
- IAV Set-point remoto con señal 0-10V
- IAA Set-point remoto con señal 4-20mA
- IAS Señal remota para activación segundo set-point
- IDL Limitación potencia desde entrada digital
- CP Contactos libres
- RP Mallas de protección baterías
- MN Manómetros de alta y baja presión
Accesorios suministrados por separado
- CR Control remoto
- CDT Termostato ambiente con pantalla táctil con visualización de la unidad
- AG Antivibratorios de caucho
Technical data
| 182 | 202 | 242 | 262 | 302 | 363 | 393 | 453 | 524 | 604 | 804 | |||
| Refrigeración | Potencia frigorífica (1) | kW | 57,9 | 65,8 | 77,6 | 87,4 | 98,5 | 113 | 129 | 145 | 168 | 198 | 252 |
| Potencia absorbida (1, 2) | kW | 21,7 | 24,8 | 28,7 | 30,3 | 35,1 | 43,0 | 46,5 | 49,4 | 61,4 | 70,8 | 97,6 | |
| Refrigeración (EN14511) | SEER (3) | 3,65 | 3,68 | 3,80 | 3,82 | 3,90 | 3,84 | 3,71 | 3,81 | 3,88 | 3,76 | 3,78 | |
| Eficiencia Energética (3) | % | 143 | 144 | 149 | 150 | 153 | 151 | 145 | 149 | 152 | 147 | 148 | |
| Calefacción | Potencia térmica (4) | kW | 60,2 | 67,1 | 76,8 | 88,5 | 101 | 115 | 133 | 151 | 173 | 204 | 262 |
| Potencia absorbida (4, 2) | kW | 19,5 | 21,1 | 24,6 | 27,2 | 29,9 | 37,9 | 41,0 | 46,7 | 53,2 | 60,4 | 84,1 | |
| Calefacción (EN14511) | SCOP (5) | 3,22 | 3,23 | 3,31 | 3,31 | 3,26 | 3,23 | 3,20 | 3,29 | 3,33 | 3,32 | 3,24 | |
| Eficiencia Energética (5) | % | 126 | 126 | 129 | 129 | 127 | 126 | 125 | 129 | 130 | 130 | 127 | |
| Sección de tratamiento de aire | Caudal de aire | m³/h | 9800 | 12200 | 14900 | 14900 | 17800 | 20200 | 23300 | 23300 | 30200 | 36100 | 45400 |
| Presión estática útil | PA | 250 | 250 | 250 | 250 | 250 | 250 | 250 | 250 | 250 | 250 | 250 | |
| Ventilador | N° | 1 | 1 | 2 | 2 | 2 | 2 | 2 | 2 | 4 | 4 | 4 | |
| Filtro | Tipo | G4 | G4 | G4 | G4 | G4 | G4 | G4 | G4 | G4 | G4 | G4 | |
| Sección de condensación | Compresor | N° | 2 | 2 | 2 | 2 | 2 | 3 | 3 | 3 | 4 | 4 | 4 |
| Circuitos frigorifícos | N° | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 2 | 2 | 2 | |
| Etapas de parcialización | N° | 2 | 2 | 2 | 2 | 2 | 3 | 3 | 3 | 4 | 4 | 4 | |
| Batería de agua caliente | Potencia térmica (6) | kW | 89 | 106 | 130 | 132 | 144 | 180 | 200 | 201 | 257 | 304 | 336 |
| Pérdidas de carga lado aire | PA | 30 | 31 | 31 | 31 | 31 | 30 | 36 | 36 | 35 | 35 | 57 | |
| Caudal de agua (6) | l/s | 2,16 | 2,60 | 3,18 | 3,22 | 3,53 | 4,39 | 4,88 | 4,92 | 6,28 | 7,41 | 8,20 | |
| Pérdidas de carga lado agua | kPa | 27 | 28 | 27 | 28 | 33 | 28 | 29 | 29 | 30 | 31 | 37 | |
| Conexiones hidráulicas | "G | 1"½ | 1"½ | 1"½ | 1"½ | 1"½ | 2" | 2" | 2" | 2" | 2 ½" | 2 ½" | |
| Resistencia eléctrica | Alimentación | V/Ph/Hz | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 |
| Potencia térmica | kW | 15 | 21 | 27 | 27 | 27 | 41 | 41 | 41 | 41 | 48 | 55 | |
| Corriente absorbida máx | A | 22 | 30 | 39 | 39 | 39 | 59 | 59 | 59 | 59 | 69 | 79 | |
| Etapas | N° | 2 | 2 | 2 | 2 | 2 | 4 | 4 | 4 | 4 | 4 | 4 | |
| Características eléctricas | Alimentación | V/Ph/Hz | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 |
| Corriente máx. funcionamiento | A | 46 | 53 | 65 | 71 | 83 | 92 | 101 | 119 | 143 | 167 | 205 | |
| Corriente máx. de arranque | A | 157 | 172 | 161 | 186 | 226 | 187 | 215 | 261 | 257 | 309 | 381 | |
| Presión sonora | Versión STD (7) | dB(A) | 68 | 68 | 67 | 67 | 68 | 71 | 72 | 72 | 72 | 72 | 72 |
| Con accesorio SL (7) | dB(A) | 65 | 65 | 64 | 64 | 65 | 68 | 69 | 69 | 69 | 69 | 69 | |
| Pesos | Peso de transporte | kg | 1030 | 1185 | 1180 | 1280 | 1300 | 1540 | 1900 | 1950 | 2270 | 2480 | 3320 |
| Peso en funcionamiento | kg | 1010 | 1170 | 1160 | 1260 | 1280 | 1520 | 1870 | 1920 | 2240 | 2440 | 3270 | |
Dimensions
| 182 | 202 | 242 | 262 | 302 | 363 | 393 | 453 | 524 | 604 | 804 | |||
| L | STD | mm | 3435 | 3435 | 3595 | 3595 | 3595 | 4050 | 4775 | 4775 | 4775 | 4775 | 6800 |
| W | STD | mm | 2200 | 2200 | 2200 | 2200 | 2200 | 2200 | 2200 | 2200 | 2200 | 2200 | 2200 |
| H | STD | mm | 2125 | 2365 | 2365 | 2365 | 2365 | 2365 | 2365 | 2365 | 2365 | 2505 | 2505 |
Notas
- 1 Temperatura del aire a la entrada del evaporador 27 °C b.s./19 °C b.h.; temperatura del aire exterior 35 °C.
- 2 Potencia absorbida total.
- 3 Coeficiente de rendimiento estacional de refrigeración de acuerdo al Reglamento Europeo UE 2016/2281.
- 4 Temperatura del aire a la entrada del condensador 20 °C, temperatura del aire exterior 7 °C b.s./ 6°C b.h.
- 5 Coeficiente de rendimiento estacional de calefacción en las condiciones climáticas medias de acuerdo al Reglamento Europeo UE 2016/2281.
- 6 Temperatura del aire a la entrada 20°C; temperatura del agua a la entrada 70°C; temperatura del agua a la salida 60°C.
- 7 Nivel de presión sonora medida en campo libre a 1 m de la unidad conforme a ISO 3744.