FDW-M 23÷123

Ceiling concealed Fan Coil units. Draw Through

SOLO_FREDDO.png caldo_e_freddo1.png _clint_asia_icon_50-60_Hz_2015.png H2O.png

The Draw Through ceiling concealed Fan Coil units of the FDW-M series are designed for installation in domestic ambients or in service business including offices, hotels, restaurants, gyms and shops.
If connected to a system equipped with a water chiller, the fan coil generates cool air silently and with instantaneous reaction. Otherwise, during the winter, if combined with a heating system with boiler or heat pump, it delivers warm air to satisfy the heating needs of households and the service industry alike.
A filter, which absorbs and retains dust in suspension, allows to keep the air quality at a suitable level and its easy removal enables continuous cleaning cycles to be carried out which are particularly important in order to guarantee suitable hygiene standards in highly frequented rooms.

Versions

  • FDW-M - Built-in horizontal unit rear inlet and horizontal delivery
  • FDW-M/AP - Built-in horizontal unit rear inlet and horizontal delivery. With high ESP fans

Power range

  • 2,4-12,0 kW
  • 0,7-3,5 Ton

Caractéristiques

  • Structure made of galvanized sheet complete with heat/sound insulation, filter and natural discharge condensation tray.
  • Radial fan type directly coupled to a 4-speed single phase electric motor, with 3 speeds connected in the standard configuration.
  • Heat exchanger coils with copper pipes and aluminium fins with airvent on the distributors.
  • Standard water connections on left side based on air flow direction, they are easily converted to opposite side directly on-site without requiring additional parts.

Accessoires fournis séparément

  • C Bac auxiliaire des condensats
  • V2 Vanne à 3 voies on/off pour installation à 2 tuyaux
2333436383103123
RefroidissementPuissance frigorifique totale (1)kW2,373,364,626,668,329,8612,43
Puissance frigorifique sensible (1)kW1,702,433,314,776,067,229,04
Débit d'eau (1)l/h4085787951146143116962138
Pertes de charge (1)kPa17132556142136
ChauffagePuissance thermique (2)kW4,716,769,1313,1816,9620,1225,02
Débit d'eau (2)l/h4055817851133145917302152
Pertes de charge (2)kPa13181942121729
Raccords hydrauliques "G3/4"3/4"3/4"3/4"3/4"3/4"3/4"
Débit d'airMaxm³/h4206108301220163019702450
Medm³/h360480590990133016302090
Minm³/h240340420850102013301820
Pression statique utileVersion STDPa0 / 300 / 300 / 300 / 300 / 300 / 300 / 30
Version APPa60 / 8060 / 8060 / 8060 / 8060 / 8060 / 8060 / 80
Caractéristiques électriquesAlimentationV/Ph/Hz230/1/50 - 60230/1/50 - 60230/1/50 - 60230/1/50 - 60230/1/50 - 60230/1/50 - 60230/1/50 - 60
Puissance absorbée maxkW0,0640,0880,1160,1880,2580,2840,342
Pression sonoreMax (3)dB(A)34383844414445
Med (3)dB(A)31313639393740
Min (3)dB(A)27303433333533
PoidsPoids de transportkg19222630414446
Poids en fonctionnementkg17202428394244

Dimensions

2333436383103123
WSTDmm330330330330330330330
HSTDmm260260260260260260260
LSTDmm7957959951105139515251755

Remarques

  • 1 Température de l'air ambiant 27 °C b.s. / 19 °C b.h., température de l'eau 7/12 °C.
  • 2 Température de l'air ambiant 20 °C b.s., température de l'eau 70/60 °C.
  • 3 Pression sonore mesurée à une distance de 1 m et temps de réverbération de 0,5 s.