acqualogik_2024.png

CHA/K/AF 182-P÷604-P

A CLASS energy efficiency aircooled liquid Chillers and Heat Pumps with axial fans, Scroll compressors and plate exchanger

_icona_clint_solo_raffreddamento_2024.png _icona_clint_solo_raffreddamento-riscaldamento_2024.png _icona_clint_compressore_scroll_2024.png _icona_clint_fan_assiale_2024.png _icona_clint_exchanger_plate_2024.png _icona_clint_solution_AQUALOGIK_2024.png _icona_clint_solution_A_class_cooling_2024.png _icona_clint_solution_A_class_heating_2024.png _icona_clint_refrigerant_R410A_2024.png _icona_clint_refrigerant_R452B_2024.png _icona_clint_refrigerant_R454B_2024.png

The liquid Chillers and Heat Pumps of the CHA/K/AF 182-P÷604-P series, with R410A refrigerant, are designed for medium-sized service sector or industrial ambients and feature A CLASS energy efficiency.
They are used, combined with Fan Coil units, for the air conditioning or heating of the rooms or to remove the heat developed during industrial processes.
Equipped with axial fans, Scroll compressors and plate exchanger, even in the super silent version, these units can be completed by a hydraulic circuit with tank, with pump, with tank and pump or with AQUALOGIK technology.
The AQUALOGIK smart control system optimises the water set point and modulates the power supply voltage of the pump and the fans, thus making the use of the inertial tank superfluous. This obtains high energy efficiency, quiet operation and optimised dimensions and costs.
Are available as option the new EC Inverter fans with high available static pressure and efficiency for indoor ducted installation.
The Heat Pump versions are designed for hot water production up to 55°C.

On request, units can be supplied with R452B or R454B refrigerant.
The units are compliant to the ErP Regulation.

Versions

  • CHA/K/AF - Cooling only
  • CHA/K/AF/WP - Reversible Heat Pump
  • CHA/K/AF/SSL - Super silenced cooling only
  • CHA/K/AF/ST - Cooling only with AQUALOGIK technology
  • CHA/K/AF/WP/ST - Reversible Heat Pump with AQUALOGIK technology
  • CHA/K/AF/SSL/ST - Super silenced cooling only with AQUALOGIK technology
  • CHA/K/AF/WP/SSL/ST - Super silenced reversible Heat Pump with AQUALOGIK technology

Power range

  • 51,0-183 kW
  • 15,0-52,0 Ton

Features

  • Structure with supporting frame, made of galvanised sheet metal with additional protection provided by polyester powder coating.
  • Scroll compressors with oil sight glass, internal overheat protection and crankcase heater.
  • Axial fans directly coupled to an electric motor with external rotor.
  • Condenser made of copper tubes and aluminium finned coil.
  • Evaporator AISI 316 stainless steel braze welded plates type with one circuit on the refrigerant side and one on the water side in 182-P÷453-P models; with two independent circuits on the refrigerant side and one on the water side in 524-P÷604-P models, complete with water differential pressure switch. On the Heat Pump units it is always installed an antifreeze heater.
  • R410A refrigerant. On request R452B or R454B refrigerant.
  • Electrical board includes: main switch with door safety interlock, fuses, thermal protection relays for compressors and thermocontacts for fans.
  • On ST versions water circuit includes INVERTER circulating pump, safety valve and expansion vessel.
  • On ST versions Condensing Control is included: electronic proportional device that ensures efficient and continuous functioning of the unit with outside air temperature down to –20 °C in cooling mode. It also allows to reduce the sound level especially at night. It consists of a fans speed controller with continuous speed regulation, an high/low pressure transducer on cooling circuit and an electrical heater on electrical board.
  • Functioning in heating mode with outside air temperature down to -15 °C.
  • Microprocessor control and regulation system (with AQUALOGIK technology on ST versions).

Factory fitted accessories

  • IM Automatic circuit breakers
  • SL Unit silencement
  • RFM Cooling circuit shut-off valve on discharge line
  • RFL Cooling circuit shut-off valve on liquid line
  • CT Condensing control down to 0 °C
  • CC Condensing control down to -20 °C
  • BT Low water temperature kit
  • EC EC Inverter fans
  • ECH EC Inverter fans with high available static pressure
  • DS Desuperheater
  • RT Total heat recovery
  • TX Coil with pre-coated fins
  • SI Inertial tank
  • PS Single circulating pump
  • PSI Inverter single circulating pump
  • PD Double circulating pump
  • PDI Inverter double circulating pump
  • GS Single circulating pump gasket for glycol >30%
  • GD Double circulating pump gaskets for glycol >30%
  • FA Antifreeze heater for tank
  • SS Soft start
  • IS Modbus RTU protocol, RS485 serial interface
  • IAV Remote set-point, 0-10V signal
  • IAA Remote set-point, 4-20mA signal
  • IAS Remote signal for second set-point activation
  • IDL Demand limit from digital input
  • HYM Hybrid systems management
  • DHW Domestic hot water management
  • MN High and low pressure gauges

Loose accessories

  • CR Remote control panel
  • RP Coils protection metallic guards
  • AG Rubber shock absorbers
  • AM Spring shock absorbers