MEA/Y 1302-B÷9002-B
Condenserless liquid chillers with (Inverter) Screw compressors and shell and tube exchanger







Combined with the remote condenser, these units are ideal for indoor installation and, equipped with a self-supporting structure that sustains the main components, they reduce the overall dimensions to a minimum while at the same time making installation and maintenance operations easier.
Equipped with latest generation Screw compressors and shell and tube exchanger, these units can also be produced in a super silent version. They have cooling and hydraulic circuits complete with everything necessary for quick installation and high energy efficiency. A series of accessories, factory fitted or supplied separately, rounds off the variety of equipment in this product range.
Versions
- MEA/Y - Cooling only
- MEA/Y/SSL - Super silenced cooling only
Power range
- 235-2060 kW
- 67,0-586 Ton
Features
- Structure with supporting frame, made of galvanised sheet metal with additional protection provided by polyester powder coating.
- Screw compressors with built-in oil separator, suction filter, crankcase heater, oil sight glass, thermal protection and stepless capacity steps.
- Shell and tube evaporator with two independent circuits on the refrigerant side and one on the water side, complete with water differential pressure switch.
- Cooling circuit shut-off valves on discharge and liquid line.
- Electronic expansion valve.
- Electronic high and low pressure gauges.
- R134a refrigerant. On request R513A refrigerant.
- Electrical board includes: main switch with door safety interlock, fuses, thermal protection relays for compressors.
- Microprocessor control and regulation system.
Accessories
Factory fitted accessories
- IM Automatic circuit breakers
- RE Adjustable minimum/maximum voltage and phase control relay
- DSV Double relief safety valve with changeover switch on the high pressure side for each refrigerant circuit
- DSVHL Double relief safety valve with changeover switch on the high and on the low pressure side of each refrigerant circuit
- BT Low water temperature kit
- FE Antifreeze heater for evaporator
- II Inverter on one compressor and soft start for other compressors
- ID Inverter on all compressors
- SS Soft start
- WM Web Monitoring - Wireless remote monitoring (GPRS/EDGE/4G/TCP-IP)
- IS Modbus RTU protocol, RS485 serial interface
- IST Modbus TCP/IP protocol, Ethernet port
- ISB BACnet MSTP protocol, RS485 serial interface
- ISBT BACnet IP protocol, Ethernet port
- ISB1 BACnet MSTP protocol, RS485 serial interface, BTL certified.
- ISBT1 BACnet IP protocol, Ethernet port, BTL certified.
- ISS SNMP protocol, Ethernet port
- IAV Remote set-point, 0-10V signal
- IAA Remote set-point, 4-20mA signal
- IAS Remote signal for second set-point activation
- IDL Demand limit from digital input
- CP Potential free contacts
- MN High and low pressure gauges
Loose accessories
- CR Remote control panel
- AG Rubber shock absorbers
- AM Spring shock absorbers
- FL Flow switch
Dokumentumok
- Product overview (IT) clint_overview_ITA_2025_w.pdf
- Product overview (EN) clint_overview_ENG_2025_w.pdf
- Product guides (IT) Guida_Prodotti_CLINT_ITALIA_02_2025_v03_w.pdf
- Product guides (EN) Product_Guide_CLINT_EUROPA_02_2025_v03_w.pdf
- Commercial leaflets 09_clint_dpl_maxipower_2022_cld_165_w.pdf
- Technical brochures 50_mea_y_1302_B9002-B_clb_45.6_vLIZEav.pdf
- Specification items (IT) 44_Voci_di_capitolato_MEA_Y_1302B_9002B.docx
- Installation, use and maintenance manuals (IT) MEA_Y-J_1302B9003B_CLM_45.6_ab.pdf
- Installation, use and maintenance manuals (EN) MEA_Y-J_1302B9003B_CLM_45.6_ab_5k2b2Hz.pdf