RTA/K/EC 182÷804
Double skin packaged Roof Top units with Scroll compressors and EC Inverter Plug-Fans
The double skin packaged Roof Top units are the ideal solution for air conditioning of wide surfaces such as shopping malls and restaurants, canteens or for industrial areas. Those units feature Inverter Scroll compressor with R410A refrigerant and EC Inverter Plug-Fans.
Equipped with extruded aluminium alloy sections and 50mm-thick sandwich panelling, these units are available in Cooling only and Reversible Heat Pump version.
The flat or pocket filters help to keep the air quality at a suitable level.
On request, units can be supplied with R454B refrigerant.
The units are compliant to the ErP Regulation.
Версии
- RTA/K/EC - Cooling only with EC Inverter Plug-Fans
- RTA/K/EC/WP - Reversible Heat Pump with EC Inverter Plug-Fans
диапазон мощности
- 58,0-252 kW
- 17,0-72,0 Ton
Характеристики
- Structure of base perimeter made of steel sheet elements galvanised. Frame made of extruded aluminium alloy profiles connected by 3 way joints. Section connection is effected by means of assembling conic stirrups and water proofing is granted by gaskets.
- Scroll compressors with oil sight glass, internal overheat protection and crankcase heater.
- Condenser and evaporator with copper tube and aluminium finned coil.
- EC INVERTER PLUG-FAN delivery fan with high energy efficient reversed blades with external rotor motor and electronic speed adjustment for easy adaptation to plant features.
- Electrical board includes: door interlocking isolator, fuses, thermal protection relays on compressors, thermocontacts for the fans of the condensing unit and contactors for the fan motors of the air handling unit.
- Microprocessor for the automatic control of the unit.
- R410A refrigerant. On request R454B refrigerant.
Принадлежности
Принадлежности, установленные на заводе
- HUR Horizontal air intake, upwards air delivery, inspection door on the right
- HUL Horizontal air intake, upwards air delivery, inspection door on the left
- HDR Horizontal air intake, downwards air delivery, inspection door on the right
- HDL Horizontal air intake, downwards air delivery, inspection door on the left
- HLR Horizontal air intake, air delivery on the left, inspection door on the right
- HRL Horizontal air intake, air delivery on the right, inspection door on the left
- IM Автоматические выключатели с термомагнитными расцепителями
- RE Реле контроля фаз и мин/макс напряжений
- SL Шумоизолирующий кожух
- SNM Air delivery sensor
- RFM Запорные вентили на нагнетательной линии холодильного контура
- RFL Запорные вентили на жидкостной линии холодильного контура
- CC Устройство управления конденсацией для наружных температур до минус 20 °C
- ECA ЕС инверторные двигатели вентиляторов в конденсаторной секции
- TXC Конденсатор с специальным покрытием
- TXE Испаритель с специальным покрытием
- FT/M6 Мягкие карманные фильтры, эффективность ePM10 70% (M6)
- FT/M7 Мягкие карманные фильтры, эффективность ePM2.5 70% (F7)
- FT/M8 Мягкие карманные фильтры, эффективность ePM1 70% (F8)
- FT/R6 Жесткие рукавные фильтры, эффективность ePM10 70% (M6)
- FT/R7 Жесткие рукавные фильтры, эффективность ePM1 50% (F7)
- FT/R8 Жесткие рукавные фильтры, эффективность ePM1 70% (F8)
- FT/E Электростатические Фильтры
- AT Устройство автоматического поддержания расхода воздуха
- AT/P Электронное устройство для поддержания постоянным напор
- AT/C Управление Регулированием Расхода Воздуха в зависимости от Нагрузки
- WS2 Водяной воздухонагреватель с трехходовым клапаном
- EHG Электронагреватель со ступенчатым регулированием
- SSA Системы активный дезинфекции для воздуха и сред
- PF Дифференциальное реле на фильтре
- SB Датчик огня
- SC Датчик дыма
- IS Интерфейсная плата RS485
- IST Протокол Modbus TCP / IP, порт Ethernet
- ISBT BACnet IP протокол, Ethernet порт
- ISB1 BACnet MSTP протокол, RS485 интерфейсная плата
- ISBT1 BACnet TCP/IP протокол, Ethernet порт
- ISS Протокол SNMP, порт Ethernet
- IAV Дистанционная уставка, 0-10В управление
- IAA Дистанционная уставка, 4-20 мА управление
- IAS Дистанционный сигнал для активации второй уставки
- IDL Запрос ограничения по цифроовму входу
- CP Сухие контакты
- RP Металлические решетки для защиты конденсатора
- MN Манометры высокого и низкого давлений.
Принадлежности, поставка отдельно
- CR Пульт дистанционного управления
- CDT Пульт дистанционного управления с комнатным термостатом с сенсорным экраном
- AG Резиновые виброизолирующие опоры
Technical data
| 182 | 202 | 242 | 262 | 302 | 363 | 393 | 453 | 524 | 604 | 804 | |||
| Охлаждение | Холодопроиз-ть (1) | kW | 57,9 | 65,8 | 77,6 | 87,4 | 98,5 | 113 | 129 | 145 | 168 | 198 | 252 |
| Потребл. мощность (1, 2) | kW | 21,7 | 24,8 | 28,7 | 30,3 | 35,1 | 43,0 | 46,5 | 49,4 | 61,4 | 70,8 | 97,6 | |
| Охлаждение (EN 14511) | SEER (3) | 3,65 | 3,68 | 3,80 | 3,82 | 3,90 | 3,84 | 3,71 | 3,81 | 3,88 | 3,76 | 3,78 | |
| Энергоэффективность (3) | % | 143 | 144 | 149 | 150 | 153 | 151 | 145 | 149 | 152 | 147 | 148 | |
| Нагрев | Теплопроиз-ть (4) | kW | 60,2 | 67,1 | 76,8 | 88,5 | 101 | 115 | 133 | 151 | 173 | 204 | 262 |
| Потребл. мощность (4, 2) | kW | 19,5 | 21,1 | 24,6 | 27,2 | 29,9 | 37,9 | 41,0 | 46,7 | 53,2 | 60,4 | 84,1 | |
| Нагрев (EN 14511) | SCOP (5) | 3,22 | 3,23 | 3,31 | 3,31 | 3,26 | 3,23 | 3,20 | 3,29 | 3,33 | 3,32 | 3,24 | |
| Энергоэффективность (5) | % | 126 | 126 | 129 | 129 | 127 | 126 | 125 | 129 | 130 | 130 | 127 | |
| Секция обработки воздуха | Расход воздуха | m³/h | 9800 | 12200 | 14900 | 14900 | 17800 | 20200 | 23300 | 23300 | 30200 | 36100 | 45400 |
| Расп. статич. давл. | PA | 250 | 250 | 250 | 250 | 250 | 250 | 250 | 250 | 250 | 250 | 250 | |
| Вентилятор | N° | 1 | 1 | 2 | 2 | 2 | 2 | 2 | 2 | 4 | 4 | 4 | |
| Фильтр | Tipo | G4 | G4 | G4 | G4 | G4 | G4 | G4 | G4 | G4 | G4 | G4 | |
| Секция конденсатора | Компрессоры | N° | 2 | 2 | 2 | 2 | 2 | 3 | 3 | 3 | 4 | 4 | 4 |
| Фреоновые контуы | N° | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 2 | 2 | 2 | |
| Ступени производительности | N° | 2 | 2 | 2 | 2 | 2 | 3 | 3 | 3 | 4 | 4 | 4 | |
| Калорифер | Теплопроиз-ть (6) | kW | 89 | 106 | 130 | 132 | 144 | 180 | 200 | 201 | 257 | 304 | 336 |
| Аэродинамическое сопротивление | PA | 30 | 31 | 31 | 31 | 31 | 30 | 36 | 36 | 35 | 35 | 57 | |
| Расход воды (6) | l/s | 2,16 | 2,60 | 3,18 | 3,22 | 3,53 | 4,39 | 4,88 | 4,92 | 6,28 | 7,41 | 8,20 | |
| Падение давления | kPa | 27 | 28 | 27 | 28 | 33 | 28 | 29 | 29 | 30 | 31 | 37 | |
| Подсоед. по воде | "G | 1"½ | 1"½ | 1"½ | 1"½ | 1"½ | 2" | 2" | 2" | 2" | 2 ½" | 2 ½" | |
| Электрический нагреватель | Сеть питания | V/Ph/Hz | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 |
| Теплопроиз-ть | kW | 15 | 21 | 27 | 27 | 27 | 41 | 41 | 41 | 41 | 48 | 55 | |
| Максимальный ток потребления | A | 22 | 30 | 39 | 39 | 39 | 59 | 59 | 59 | 59 | 69 | 79 | |
| Ступени мощности | N° | 2 | 2 | 2 | 2 | 2 | 4 | 4 | 4 | 4 | 4 | 4 | |
| Электрические характеристики | Сеть питания | V/Ph/Hz | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 |
| Макс. рабочий ток | A | 46 | 53 | 65 | 71 | 83 | 92 | 101 | 119 | 143 | 167 | 205 | |
| Пусковой ток | A | 157 | 172 | 161 | 186 | 226 | 187 | 215 | 261 | 257 | 309 | 381 | |
| Schalldruck | Стандартная версия (7) | dB(A) | 68 | 68 | 67 | 67 | 68 | 71 | 72 | 72 | 72 | 72 | 72 |
| С опцией SL (7) | dB(A) | 65 | 65 | 64 | 64 | 65 | 68 | 69 | 69 | 69 | 69 | 69 | |
| Масса | Транспортный вес | kg | 1030 | 1185 | 1180 | 1280 | 1300 | 1540 | 1900 | 1950 | 2270 | 2480 | 3320 |
| Рабочий вес | kg | 1010 | 1170 | 1160 | 1260 | 1280 | 1520 | 1870 | 1920 | 2240 | 2440 | 3270 | |
Dimensions
| 182 | 202 | 242 | 262 | 302 | 363 | 393 | 453 | 524 | 604 | 804 | |||
| L | STD | mm | 3435 | 3435 | 3595 | 3595 | 3595 | 4050 | 4775 | 4775 | 4775 | 4775 | 6800 |
| W | STD | mm | 2200 | 2200 | 2200 | 2200 | 2200 | 2200 | 2200 | 2200 | 2200 | 2200 | 2200 |
| H | STD | mm | 2125 | 2365 | 2365 | 2365 | 2365 | 2365 | 2365 | 2365 | 2365 | 2505 | 2505 |
Примечания
- 1 Темп. воздуха на входе испарителя 27 °C по сухому/19 °C по влажному термометру, темп. наружного воздуха 35 °C.
- 2 Общая потребляемая мощность.
- 3 Сезонная энергетическая эффективность в режиме охлаждения в соответствии с документом Евросоюза п. 2016/2281.
- 4 Темп. воды на входе конденсатора 20 °C, темп. наружного воздуха 7 °C по сухому/6 °C по влажному термометру.
- 5 Сезонная энергетическая эффективность в средних климатических режимах в соответствии с документом Евросоюза п. 2016/2281.
- 6 Темп. воздуха на входе 20 °C, темп. воды на входе 70 °C, темп. воды на выходе 60 °C.
- 7 Уровень звукового давления в свободном поле на расстоянии 1 м. от агрегата. Согласно ISO 3744.
- N.B. (1) Масса тепловых насосов приведена в соответствующей технической документации.