DBW-M/SZ 133÷464

DBW-M/SZ 133÷464

Ducted Blower Fan Coil units

SOLO_FREDDO.png caldo_e_freddo1.png _clint_asia_icon_60_Hz_2015.png H2O.png

The Ducted Blower Fan Coil units of the DBW-M series are designed for installation in wide ambients as office buildings, hotels, restaurants, sport structures and shopping malls.
If connected to a system equipped with a water chiller, DBW-M generates cool or warm air silently and with instantaneous reaction. The range includes 8 models with cooling capacities from 4 to 15 TON which are characterized by high static pressure (up to 0,6 inWG) to satisfy the needs of wide installations where external unit is far from the internal ambients or there are multiple far ambients to be cooled simultaneously.
A filter, which absorbs and retains dust in suspension, allows to keep the air quality at a suitable level and its easy removal enables continuous cleaning cycles to be carried out which are particularly important in order to guarantee suitable hygiene standards in highly frequented rooms.
 
The units feature 230V or 380V power supply and 60Hz frequency.

Versions

  • DBW-M/SZ - Horizontal unit rear inlet and horizontal delivery

Power range

  • 12.0-52.0 kW
  • 3.5-15.0 Ton

Features

  • Structure made of galvanized steel sheet with electrostatic powder paint complete with polyethylene for thermal and acoustical purpose.
  • G3 standard cleanable filter.
  • Radial fan type, directly coupled with single-phase 3-speed electric motor or to 3-phase motors by V belt and variable pulley, depending on
  • the model.
  • Heat exchanger coils with copper pipes and aluminium fins with airvent and drain pan.
  • Standard water connections on left side based on air flow direction. On request units can be provided with water connections on right side.
133164203253324423424464
CoolingTotal cooling capacity (1)kW12,415,817,420,533,539,546,651,6
Sensible cooling capacity (1)kW8,411,212,715,223,627,332,035,1
Water flow (1)l/h21332718299335265762679480158875
Pressure drops (1)kPa133238332431
HeatingHeating capacity (2)kW15,420,925,229,643,650,857,864,2
Water flow (2)l/h21332718299335265762679480158875
Water connections inch3/4"3/4"3/4"1"1"1 ¼"1 ¼"1 ¼"
Air flowMaxm³/h22102890357044105770747074708150
Medm³/h20402550323039105090---------
Minm³/h15302210255028904580---------
Available static pressure Pa100100100100100150150150
Electrical characteristicsPower supplyV/Ph/Hz230/1/60230/1/60230/1/60230/1/60230/1/60380/3/60380/3/60380/3/60
Max absorbed powerkW0,40,82 x 0.42 x 0.42 x 0.81,91,91,9
Sound pressureMax (3)dB(A)5353565762686869
Med (3)dB(A)5050525359---------
Min (3)dB(A)4141444550---------
WeightsTransport weightkg4650758690130139139
Operating weightkg4448738488128137137

Dimensions

133164203253324423424464
LSTDmm855855149514951495163016301630
WSTDmm705705705705705975975975
HSTDmm565565565565565785785785

Notes

  • 1 Ambient air temperature 27 °C d.b./19 °C w.b., water temperature 7/12 °C.
  • 2 Ambient air temperature 20 °C d.b., water temperature 50 °C, same water flow as for cooling.
  • 3 Sound pressure level measured at 1 m from the unit with reverberation time 0,5 s.
  • N.B. (1) Data declared at 230/1/50