FBW-M 23÷123

Ceiling concealed Fan Coil units. Blow Through

SOLO_FREDDO.png caldo_e_freddo1.png _clint_asia_icon_50-60_Hz_2015.png H2O.png

The Blow Through ceiling concealed Fan Coil units of the FBW-M series are designed for installation in domestic ambients or in service business including offices, hotels, restaurants, gyms and shops.
If connected to a system equipped with a water chiller, FBW-M generates cool air silently and with instantaneous reaction. Otherwise, durinf the winter, if combined with a heating
system with boiler or heat pump, it delivers warm air to satisfy the heating needs of
households and the service industry alike.
A filter, which absorbs and retains dust in suspension, allows to keep the air quality at a suitable level and its easy removal enables continuous cleaning cycles to be carried out which are particularly important in order to guarantee suitable hygiene standards in highly frequented rooms.

Versions

  • FBW-M - Built-in horizontal unit rear inlet and horizontal delivery
  • FBW-M/AP - Built-in horizontal unit rear inlet and horizontal delivery. With high ESP fans

Power range

  • 2.3-12.0 kW
  • 0.7-3.5 Ton

Features

  • Structure made of galvanized sheet complete with heat/sound insulation, filter and natural discharge condensation tray.
  • Radial fan type directly coupled to a 4-speed single phase electric motor, with 3 speeds connected in the standard configuration.
  • Heat exchanger coils with copper pipes and aluminium fins with airvent on the distributors.
  • Standard water connections on left side based on air flow direction, they are easily converted to opposite side directly on-site without requiring additional parts.

Loose accessories

  • C Auxiliary condensate drain pan
  • V2 3-Way on/off valve for 2-Pipe system
2333436383103123
CoolingTotal cooling capacity (1)kW2,333,334,506,568,289,6712,24
Sensible cooling capacity (1)kW1,662,413,234,706,037,078,90
Water flow (1)l/h4015737741128142416632105
Pressure drops (1)kPa16132355141935
HeatingHeating capacity (2)kW4,626,698,9012,9816,8819,7224,65
Water flow (2)l/h3975757651116145216962120
Pressure drops (2)kPa13181840121627
Water connections "G3/4"3/4"3/4"3/4"3/4"3/4"3/4"
Air flowMaxm³/h4206108301220163019702450
Medm³/h360480590990133016302090
Minm³/h240340420850102013301820
Available static pressureSTD versionPa0 / 300 / 300 / 300 / 300 / 300 / 300 / 30
AP versionPa60 / 8060 / 8060 / 8060 / 8060 / 8060 / 8060 / 80
Electrical characteristicsPower supplyV/Ph/Hz230/1/50 - 60230/1/50 - 60230/1/50 - 60230/1/50 - 60230/1/50 - 60230/1/50 - 60230/1/50 - 60
Max absorbed powerkW0,0640,0880,1160,1880,2580,2840,342
Sound pressureMax (3)dB(A)33373844414344
Med (3)dB(A)31313538393739
Min (3)dB(A)26293332333433
WeightsTransport weightkg17202428394244
Operating weightkg15182226374042

Dimensions

2333436383103123
WSTDmm480480480480480480480
HSTDmm260260260260260260260
LSTDmm74091010401240149015901850

Notes

  • 1 Ambient air temperature 27 °C d.b./19 °C w.b., water temperature 7/12 °C.
  • 2 Ambient air temperature 20 °C d.b., water temperature 70/60 °C.
  • 3 Sound pressure level measured at 1 m from the unit with reverberation time 0,5 s.