UTW/HDT 63÷274
Ductable Fan Coil units with High Delta Water Temperature
These modular Fan Coil units are the ideal solution to meet the air treatment needs of systems including distribution through ducting or directly into the room and installation in false ceilings or in service rooms.
It has been especially designed for operation with High Delta Water Temperature.
If connected to a system equipped with a liquid Chiller, this terminal unit generates cool air silently and with instantaneous reaction. A filter, which absorbs and retains dust in suspension, allows to keep the air quality at a suitable level, and its easy removal enables continuous cleaning cycles to be carried out which are particularly important in order to guarantee suitable hygiene standards in highly frequented rooms.
This product range is complete with various accessories such as: outdoor air intake plenum, mixing section with dampers, room delivery plenum for flexible ducts and resistance heating section. Units are available both with AC and EC Inverter fans.The units equipped with EC Inverter motor are able to modulate the air flow ensuring a perfect adaptability to the load without any temperature fluctuations, achieving superior performance compared to the traditional solutions even from the point of view of the energy consumption.
Versions
- UTW/HDT - Base unit
- UTW/HDT/EC - Unit with EC Inverter fans
Power range
- 3.6-18.0 kW
- 1.0-5.0 Ton
Features
- Structure in galvanized sheet, entirely lined with heat/sound insulation material.
- Radial type fan, statically and dynamically balanced to reduce vibration and noise to a minimum, directly coupled with single-phase 3-speed electric motor.
- Radial type fan with double intake and EC INVERTER fan type.
- Heat exchanger in copper pipes and aluminium fins, complete with air vent and drain pan.
- Air filter made of recyclable synthetic material class EU3; inspection is foreseen from the bottom part.
- Air bleed valves, positioned on the water connections of the coil, make it possible to bleed air from the coil.
- Electrical board comprising a terminal board for wiring to room control panel and power supply.
Accessories
Loose accessories
- C Auxiliary condensate drain pan
- AF Filtering section
- GRI/R Intake grid with air filter
- BM Supply grid with adjustable fins
- PR Intake plenum
- PM Supply plenum
- P3 Supply plenum for flexible ducts
- EH1 Supplementary electrical heater section
- EH2 Supplementary electrical heater section
- SM Servo-motor for damper
- SF Supply flange
- DRA Wall mounted automatic electronic control panel
- VR Wall mounted fan speed control panel
- TA Wall mounted ambient thermostat
- DRE Wall mounted electromechanic control panel
- DRV Wall mounted automatic electronic control panel and base board (SRV+SPV)
- SRV Wall mounted automatic electronic control panel
- SPV Base board
- IS Modbus RTU protocol, RS485 serial interface
- BC Universal connecting terminal
- V2 3-Way on/off valve for 2-Pipe system
- MB Mixing box with damper
Technical data
63 | 93 | 104 | 133 | 153 | 233 | 274 | |||
Cooling | Total cooling capacity (1)(2) | kW | 3,6 | 5,9 | 8,3 | 8,5 | 9,0 | 12,2 | 17,7 |
Sensible cooling capacity (1)(2) | kW | 3,2 | 5,3 | 6,7 | 7,3 | 8,1 | 11,5 | 15,5 | |
Water flow (1)(2) | l/h | 344 | 564 | 793 | 812 | 860 | 1166 | 1691 | |
Pressure drops (1)(2) | kPa | 12 | 14 | 35 | 34 | 7 | 9 | 24 | |
Rows | Quantity | n° | 3 | 3 | 4 | 3 | 3 | 3 | 4 |
Water connections | In / Out | "G | 3/4" | 3/4" | 3/4" | 3/4" | 3/4" | 1" | 1" |
Air flow | Max | m³/h | 950 | 1600 | 1600 | 2200 | 2500 | 2900 | 3500 |
Med | m³/h | 800 | 1200 | 1300 | 1800 | 2000 | 2300 | 2600 | |
Min | m³/h | 600 | 850 | 900 | 1300 | 1400 | 1500 | 2000 | |
Air flow (EC version) | Max | m³/h | 950 | 1600 | 1600 | 2200 | 2500 | 2900 | 3500 |
Min | m³/h | 530 | 760 | 810 | 810 | 1140 | 1200 | 1200 | |
Available static pressure | Max | Pa | 75 | 90 | 80 | 80 | 85 | 90 | 90 |
Med | Pa | 50 | 50 | 50 | 50 | 50 | 70 | 75 | |
Min | Pa | 40 | 40 | 40 | 35 | 40 | 50 | 55 | |
Available static pressure (EC version) | Max | Pa | 75 | 90 | 80 | 80 | 85 | 115 | 115 |
Min | Pa | 40 | 40 | 40 | 40 | 40 | 45 | 55 | |
EH1 Electrical heater | Power supply | V/Ph/Hz | 400/3+N/50 | 400/3+N/50 | 400/3+N/50 | 400/3+N/50 | 400/3+N/50 | 400/3+N/50 | 400/3+N/50 |
Absorbed power | kW | 3 | 4 | 4 | 4 | 6 | 6 | 6 | |
Max. absorbed current | A | 4,3 | 8,7 | 8,7 | 8,7 | 13,0 | 13,0 | 13,0 | |
Steps | n° | 1 | 1 | 1 | 1 | 1 | 1 | 1 | |
EH2 Electrical heater | Power supply | V/Ph/Hz | 400/3+N/50 | 400/3+N/50 | 400/3+N/50 | 400/3+N/50 | 400/3+N/50 | 400/3+N/50 | 400/3+N/50 |
Absorbed power | kW | 6 | 8 | 8 | 8 | 12 | 12 | 12 | |
Max. absorbed current | A | 8,7 | 17,4 | 17,4 | 17,4 | 26,1 | 26,1 | 26,1 | |
Steps | n° | 1 | 1 | 1 | 1 | 1 | 1 | 1 | |
Electrical characteristics | Power supply | V/Ph/Hz | 230/1/50 | 230/1/50 | 230/1/50 | 230/1/50 | 230/1/50 | 230/1/50 | 230/1/50 |
Max absorbed power | kW | 0,17 | 0,26 | 0,26 | 0,40 | 0,40 | 0,46 | 0,72 | |
Max. absorbed current | A | 0,70 | 1,10 | 1,10 | 1,75 | 1,75 | 2,10 | 3,85 | |
Max. starting current | A | 1,4 | 2,3 | 2,3 | 2,3 | 2,3 | 5,5 | 8,5 | |
Electrical characteristics (EC version) | Power supply | V/Ph/Hz | 230/1/50 | 230/1/50 | 230/1/50 | 230/1/50 | 230/1/50 | 230/1/50 | 230/1/50 |
Max absorbed power | kW | 0,17 | 0,23 | 0,28 | 0,31 | 0,45 | 0,48 | 0,68 | |
Max. absorbed current | A | 1,27 | 1,65 | 1,98 | 1,98 | 3,00 | 3,00 | 3,00 | |
Max. starting current | A | ||||||||
Sound pressure | Max (3) | dB(A) | 52 | 54 | 54 | 59 | 59 | 60 | 62 |
Med (3) | dB(A) | 49 | 50 | 50 | 55 | 55 | 55 | 56 | |
Min (3) | dB(A) | 43 | 43 | 42 | 47 | 46 | 47 | 52 | |
Sound pressure (EC version) | Max (3) | dB(A) | 52 | 54 | 54 | 59 | 59 | 60 | 62 |
Min (3) | dB(A) | 43 | 43 | 42 | 42 | 45 | 45 | 44 | |
Weights | Transport weight | kg | 29 | 42 | 44 | 57 | 65 | 67 | 70 |
Operating weight | kg | 27 | 40 | 42 | 55 | 63 | 65 | 68 |
Dimensions
63 | 93 | 104 | 133 | 153 | 233 | 274 | |||
W | STD/EC | mm | 455 | 455 | 455 | 505 | 540 | 540 | 540 |
H | STD/EC | mm | 295 | 295 | 295 | 325 | 325 | 375 | 375 |
L | STD/EC | mm | 645 | 1005 | 1005 | 1105 | 1345 | 1345 | 1345 |
Notes
- 1 Ambient air temperature 27 °C d.b./19 °C w.b., water temperature 5,5/14,5 °C.
- 2 Performances also valid for EC version.
- 3 Sound pressure level measured at 1 m from the unit with reverberation time 0,5 s.
- N.B. (1) Maximum operating pressure 1000 kPa.
- N.B. (2) Inhibited ethylene glycol can be added to the water.
- N.B. (3) Data of EC version are specified on technical brochure.