RCA/K 5111÷8222

Remote aircooled Condensers with axial fans

ASSIALE11.png R410A1.png

These Remote aircooled Condensers with axial fans are designed to be combined with evaporating units with R410A refrigerant.
These units, available in three configurations depending on the level of noiselessness required, Standard, Silenced and Super silenced, are equipped with latest generation axial fans, with motor fan shrouds having a large radius of curvature to eliminate all the air flow turbulence and with larger plenum to uniform the air distribution on the cooling coil.
The units can be installed with either horizontal or vertical air delivery, as needed and can be equipped with high efficiency EC fans.

Versions

  • RCA/K - Cooling only units with horizontal air flow
  • RCA/K/EC - Cooling only units with horizontal air flow and EC Inverter fans
  • RCA/K/VX - Cooling only units with vertical air flow
  • RCA/K/EC/VX - Cooling only units with vertical air flow and EC Inverter fans

Power range

  • 1.4-23.0 m³/s
  • 2923-49498 Cfm

Features

  • Frame in oven painted with a polyurethane resin and galvanised steel casework.
  • The cowlings of the motorfans are made with a wide bending radius to eliminate any turbulence in the air flow.
  • Heat exchanger is made with corrugated tubes with a greater heat exchange surface, fins cut with a special louver configuration to give the best external coefficient of heat exchange.
  • Electrical board includes: main switch, fuses, fans wiring, terminals for external connections, fans speed controller via 0-10V signal.
  • Electrical board (EC versions) includes: main switch, automatic circuit breakers, fans wiring, terminals for external connections, therminals for 0-10V signal for fan speed control.
51115112511351146111611261136114612161226123612461256131613282218222
FanAir flowm³/s1,381,432,232,072,834,584,384,175,665,419,158,768,3413,7313,1419,5023,37
Quantity11111111222223344
ConnectionsInØ mm2222222828283535354235424242542 X 352 X 35
OutØ mm1818181822222828283528353535352 x 282 x 28
Electrical characteristicsPower supplyV/Ph/Hz230/1/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50
Absorbed powerkW0,220,260,830,830,631,901,901,901,261,263,803,803,805,705,705,767,20
Absorbed currentA0,970,631,451,451,253,203,203,202,502,506,406,406,409,609,6011,6015,60
Sound pressureSTD version (1)dB(A)4342535348606060505062626264645657
WeightsTransport weightkg102102102108183183196206206230206230253352373642642

Dimensions

51115112511351146111611261136114612161226123612461256131613282218222
LSTDmm11301130113011301490149014901490263026302630263026303770377032303230
VXmm11301130113011301490149014901490263026302630263026303770377032303230
WSTDmm600600600600600600600600600600600600600600600800800
VXmm9009009009001260126012601260126012601260126012601260126024002400
HSTDmm8708708708701230123012301230123012301230123012301230123023902390
VXmm98098098098099099099099099099099099099099099015651565

Notes

  • 1 Sound pressure level measured in free field conditions at 10 m from the unit. According to ISO 3744.
  • N.B. (1) Combinations are made at condensing temperature 50 °C, ambient air temperature 35 °C.
  • N.B. (2) Clearance areas are specified on installation, use and maintenance manual.