RCA/Y/SSL 8231÷9281

Super silenced Remote aircooled Condensers with axial fans

ASSIALE11.png _clint_icon_super-silenced.png R134a_NEW1.png icon_refrigerant_R513A.png

These Remote aircooled Condensers with axial fans are designed to be combined with evaporating units with R134a refrigerant.
These units, available in three configurations depending on the level of noiselessness required, Standard, Silenced and Super silenced, are equipped with latest generation axial fans, with motor fan shrouds having a large radius of curvature to eliminate all the air flow turbulence and with larger plenum to uniform the air distribution on the cooling coil.
The units, except the V shaped ones, can be installed with either horizontal or vertical air delivery, as needed and can be equipped with high efficiency EC fans.
On request, units can be supplied for R513A refrigerant.

Versions

  • RCA/Y/SSL - Super silenced cooling only unit with horizontal air flow
  • RCA/Y/EC/SSL - Super silenced cooling only unit with horizontal air flow and EC Inverte fans
  • RCA/Y/VX/SSL - Super silenced cooling only unit with vertical air flow
  • RCA/Y/EC/VX/SSL - Super silenced cooling only units with vertical air flow and EC Inverter fans

Power range

  • 23.0-76.0 m³/s
  • 47655-160545 Cfm

Features

  • Frame in oven painted with a polyurethane resin and galvanised steel casework.
  • The cowlings of the motorfans are made with a wide bending radius to eliminate any turbulence in the air flow.
  • Heat exchanger is made with corrugated tubes with a greater heat exchange surface, fins cut with a special louver configuration to give the best external coefficient of heat exchange.
  • Electrical board includes: main switch, fuses, fans wiring, terminals for external connections, fans speed controller via 0-10V signal.
  • Electrical board (EC versions) includes: main switch, automatic circuit breakers, fans wiring, terminals for external connections, therminals for 0-10V signal for fan speed control.
82318232824182428251826182718281926192719281
FanAir flowm³/s24,422,532,530,040,748,856,965,165,075,875,6
Quantity668810121416121416
ConnectionsInØ mm2 x 542 x 542 x 542 x 542 x 642 x 762 x 762 x 762 x 762 x 762 x 76
OutØ mm2 x 422 x 422 X 352 x 422 x 422 x 422 x 542 x 542 x 642 x 642 x 64
Electrical characteristicsPower supplyV/Ph/Hz400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50
Absorbed powerkW6,906,909,209,2011,5013,8016,1018,4018,7221,8415,49
Absorbed currentA13,2013,2017,6017,6022,0026,4030,8035,2034,8040,6037,44
Sound pressureSSL version (1)dB(A)5252535354545455585862
WeightsTransport weightkg10251110135614701687201723492681421848515484

Dimensions

82318232824182428251826182718281926192719281
LSSLmm458045805930593072808630998011330---
VX/SSLmm4580458059305930728086309980113307790924010490
WSSLmm800800800800800800800800---
VX/SSLmm24002400240024002400240024002400240024002400
HSSLmm23902390239023902390239023902390---
VX/SSLmm15651565156515651565156515651565226222622262

Notes

  • 1 Sound pressure level measured in free field conditions at 10 m from the unit. According to ISO 3744.
  • N.B. (1) Combinations are made at condensing temperature 50 °C, ambient air temperature 35 °C.
  • N.B. (2) Clearance areas are specified on installation, use and maintenance manual.