FDW-M 23÷123

Ceiling concealed Fan Coil units. Draw Through

SOLO_FREDDO.png caldo_e_freddo1.png _clint_asia_icon_50-60_Hz_2015.png H2O.png

The Draw Through ceiling concealed Fan Coil units of the FDW-M series are designed for installation in domestic ambients or in service business including offices, hotels, restaurants, gyms and shops.
If connected to a system equipped with a water chiller, the fan coil generates cool air silently and with instantaneous reaction. Otherwise, during the winter, if combined with a heating system with boiler or heat pump, it delivers warm air to satisfy the heating needs of households and the service industry alike.
A filter, which absorbs and retains dust in suspension, allows to keep the air quality at a suitable level and its easy removal enables continuous cleaning cycles to be carried out which are particularly important in order to guarantee suitable hygiene standards in highly frequented rooms.

Versiones

  • FDW-M - Built-in horizontal unit rear inlet and horizontal delivery
  • FDW-M/AP - Built-in horizontal unit rear inlet and horizontal delivery. With high ESP fans

Power range

  • 2,4-12,0 kW
  • 0,7-3,5 Ton

Características

  • Structure made of galvanized sheet complete with heat/sound insulation, filter and natural discharge condensation tray.
  • Radial fan type directly coupled to a 4-speed single phase electric motor, with 3 speeds connected in the standard configuration.
  • Heat exchanger coils with copper pipes and aluminium fins with airvent on the distributors.
  • Standard water connections on left side based on air flow direction, they are easily converted to opposite side directly on-site without requiring additional parts.

Accesorios suministrados por separado

  • C Bandeja auxiliar de condensados
  • V2 Válvula de 3 vías on/off para instalación a 2 tubos
2333436383103123
RefrigeraciónPotencia frigorífica total (1)kW2,373,364,626,668,329,8612,43
Potencia frigorífica sensible (1)kW1,702,433,314,776,067,229,04
Caudal de agua (1)l/h4085787951146143116962138
Pérdidas de carga (1)kPa17132556142136
CalefacciónPotencia térmica (2)kW4,716,769,1313,1816,9620,1225,02
Caudal de agua (2)l/h4055817851133145917302152
Pérdidas de carga (2)kPa13181942121729
Conexiones hidráulicas "G3/4"3/4"3/4"3/4"3/4"3/4"3/4"
Caudal de aireMaxm³/h4206108301220163019702450
Medm³/h360480590990133016302090
Mín.m³/h240340420850102013301820
Presión estática útilVersión STDPa0 / 300 / 300 / 300 / 300 / 300 / 300 / 30
Versión APPa60 / 8060 / 8060 / 8060 / 8060 / 8060 / 8060 / 80
Características eléctricasAlimentaciónV/Ph/Hz230/1/50 - 60230/1/50 - 60230/1/50 - 60230/1/50 - 60230/1/50 - 60230/1/50 - 60230/1/50 - 60
Potencia absorbida máxkW0,0640,0880,1160,1880,2580,2840,342
Presión sonoraMax (3)dB(A)34383844414445
Med (3)dB(A)31313639393740
Mín. (3)dB(A)27303433333533
PesosPeso de transportekg19222630414446
Peso en funcionamientokg17202428394244

Dimensions

2333436383103123
WSTDmm330330330330330330330
HSTDmm260260260260260260260
LSTDmm7957959951105139515251755

Notas

  • 1 Temperatura del aire ambiente 27 °C b.s/19 °C b.h., temperatura agua 7/12 °C.
  • 2 Temperatura del aire ambiente 20 °C b.s., temperatura agua 70/60 °C.
  • 3 Presión sonora medida a una distancia de 1 m y con tiempo de reverberación de 0,5 s.