High efficiency air cooled liquid Chillers and Heat Pumps with axial fans, Scroll compressors and plate exchanger

_icona_clint_solo_raffreddamento_2024.psd _icona_clint_solo_raffreddamento-riscaldamento_2024.psd _icona_clint_compressore_scroll_2024.psd _icona_clint_fan_assiale_2024.psd _icona_clint_exchanger_plate_2024.psd _icona_clint_solution_A_class_cooling_2024.psd _icona_clint_solution_A_class_heating_2024.psd icona_clint_XT.psd _icona_clint_refrigerant_R410A_2024.psd

The CHAXT/K/AF 726-P÷24012-P liquid Chillers and Heat Pumps, with R410A refrigerant, are characterized by high efficiency in cooling and heating.
The units are characterized by multi-compressor design on double cooling circuit, to reach high energy performances, reduction of current at start-up, elimination of inertial tanks and excellent silent functioning. The use of components built in large series makes them highly reliable and the management of a high number of compressors allows increased life span with reduction of machine stopping risks and easier maintenance operations.

Versions

  • CHAXT/K/AF - Cooling only
  • CHAXT/K/AF/WP - Reversible Heat Pump

Power range

  • 170-586 kW
  • 48.0-167 Ton

Features

  • Structure with supporting frame, made of galvanised sheet metal with additional protection provided by polyester powder coating.
  • Scroll compressors with oil sight glass, internal overheat protection and crankcase heater.
  • Axial fans directly coupled to an electric motor with external rotor.
  • Condenser made of copper tubes and aluminium finned coils.
  • Evaporator AISI 316 stainless steel braze welded plates type with two independent circuits on the refrigerant side and one on the water side, complete with water differential pressure switch. On the Heat Pump units it is always installed an antifreeze heater.
  • Cooling circuit shut-off valve on liquid line in 1048-P÷24012-P models.
  • Electronic expansion valve.
  • Electronic high and low pressure gauges.
  • R410A refrigerant.
  • Electrical board includes: main switch with door safety interlock, fuses or magnetothermic switches, thermal protection relays for compressors and thermocontacts for fans.
  • Electrical board with dedicated components sizing and ventilation system for unit operation at high outdoor ambient temperature.
  • Functioning in heating mode with outside air temperature down to -15 °C.
  • Microprocessor control and regulation system.
  • Operating outdoor ambient air temperature up to 52 °C.

Factory fitted accessories

  • IM Automatic circuit breakers
  • RE Adjustable minimum/maximum voltage and phase control relay
  • SL Unit silencement
  • RFM Cooling circuit shut-off valve on discharge line
  • RFL Cooling circuit shut-off valve on liquid line
  • CT Condensing control down to 0 °C
  • CC Condensing control down to -20 °C
  • BT Low water temperature kit
  • EC EC Inverter fans
  • DS Desuperheater
  • RT Total heat recovery
  • TX Coil with pre-coated fins
  • EW External water connections
  • PS Single circulating pump
  • PSI Inverter single circulating pump
  • PD Double circulating pump
  • PDI Inverter double circulating pump
  • GS Single circulating pump gasket for glycol >30%
  • GD Double circulating pump gaskets for glycol >30%
  • FE Antifreeze heater for evaporator
  • SS Soft start
  • WM Web Monitoring - Wireless remote monitoring (4G)
  • IS Modbus RTU protocol, RS485 serial interface
  • ISBT BACnet IP protocol, Ethernet port
  • ISB1 BACnet MSTP protocol, RS485 serial interface, BTL certified
  • ISBT1 BACnet IP protocol, Ethernet port, BTL certified
  • MTS Master/Slave Network Management
  • IAV Remote set-point, 0-10V signal
  • IAA Remote set-point, 4-20mA signal
  • IAS Remote signal for second set-point activation
  • IDL Demand limit from digital input
  • MN High and low pressure gauges
  • ISS SNMP protocol, Ethernet port

Loose accessories

  • CR Remote control panel
  • RP Coils protection metallic guards
  • AG Rubber shock absorbers
  • AM Spring shock absorbers
726-P786-P826-P906-P1048-P1128-P1208-P13010-P15010-P16812-P18012-P20010-P24012-P
CoolingCooling capacity (1)kW170190211232257281309339370414458513586
Absorbed power (1)kW74,283,492,1101115127135151167187206234269
Cooling capacity (2)kW197220245271300329361396435485538603692
Absorbed power (2)kW62,069,076,083,095,0105111124137154169192220
EER (2)3,183,193,223,273,163,133,253,193,173,153,183,143,14
Cooling (EN14511)Cooling capacity (2)kW197220245271300329361396435485538603692
Absorbed power (2)kW62,970,077,084,096,3106112126139155171194222
EER (2)3,133,143,183,223,113,103,213,153,133,123,153,113,12
HeatingHeating capacity (3)kW214239266295325359391431473526586658754
Absorbed power (3)kW65,073,081,088,099,0109119129143162176202231
COP (3)3,293,273,283,353,283,293,283,343,313,253,333,263,26
Heating (EN14511)Heating capacity (3)kW214239266295326360392432474527587659755
Absorbed power (3)kW66,274,482,389,4101111121131146164179209234
COP (3)3,243,223,243,303,233,253,243,293,263,213,293,163,23
CompressorQuantity3+33+33+33+34+44+44+45+55+56+66+65+56+6
Refrigerant circuits2222222222222
Capacity steps6666888881010810
EvaporatorWater flowl/s9,3910,4911,6812,9214,3015,6817,2118,8820,7323,1225,6428,7432,98
Pressure dropskPa45,049,044,042,050,039,046,049,049,033,041,039,032,0
Water connectionsDN808080808080808080150150150150
Electrical characteristicsPower supplyV/Ph/Hz400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50
Max. running currentA166179187202239254270291329374397441520
Max. starting currentA289311354370371422437423497541564628707
Unit with pumpPump available static pressurekPa155135200180180180160145125180165155140
Water connectionsDN100100100100100100100100100100100150150
Sound pressureSTD version (4)dB(A)72737474747474767675767777
With SL accessory (4)dB(A)69707171717172737372737474
Weight STD versionsTransport weightkg1854217122892317243726802690286930043512364242404458
Operating weightkg1870219023102340246027102720290030403560369043004520

Dimensions

726-P786-P826-P906-P1048-P1128-P1208-P13010-P15010-P16812-P18012-P20010-P24012-P
LSTDmm4000400040004000500050005000500050006200620072007200
SSLmm50005000500050006200620062006200620072007200------
WSTDmm2200220022002200220022002200220022002200220022002200
SSLmm22002200220022002200220022002200220022002200------
HSTDmm2100210021002100210021002100210021002100210021002100
SSLmm22002200220022002200220022002200220022002200------

Notes

  • 1 Chilled water from 12 to 7 °C, ambient air temperature 46 °C.
  • 2 Chilled water from 12 to 7 °C, ambient air temperature 35 °C.
  • 3 Heated water from 40 to 45 °C, ambient air temperature 7 °C d.b./6 °C w.b.
  • 4 Sound pressure level measured in free field conditions at 1 m from the unit. According to ISO 3744.
  • N.B. (1) Weights of WP versions are specified on technical brochure.