clint MAXI_POWER.eps

clint tec_inverter_screw_2025.eps

CHAXT/Y/A 1302÷6002

High efficiency air cooled liquid Chillers and Heat Pumps with axial fans, (Inverter) Screw compressors and shell and tube exchanger

_icona_clint_solo_raffreddamento_2024.psd _icona_clint_solo_raffreddamento-riscaldamento_2024.psd _icona_clint_compressore_screw_inverter_2024.psd _icona_clint_compressore_screw_2024.psd _icona_clint_fan_assiale_2024.psd _icona_clint_exchanger_shell_and_tube_2024.psd _icona_clint_solution_web_monitoring_2024.psd _icona_clint_solution_A_class_cooling_2024.psd _icona_clint_solution_A_class_heating_2024.psd icona_clint_XT.psd _icona_clint_refrigerant_R134a_2024.psd _icona_clint_refrigerant_R513A_2024.psd

The CHAXT/Y/A 1302÷6002 units, with R134a refrigerant, have extremely high efficiency levels due to reduced electrical absorption and a high efficiency of the compressor-exchanger combination.
The latest generation Screw compressors and the new design optimized in every detail ensure the reach of the highest efficiency. Furthermore, accessories as the Inverter control on Screw compressors, on circulating pumps and EC Inverter on fans are also available for getting the highest efficiency at part load.
Are available as option the new EC Inverter fans with high available static pressure and efficiency.


On request, units can be supplied with R513A refrigerant.

Versions

  • CHAXT/Y/A - Cooling only
  • CHAXT/Y/A/WP - Reversible Heat Pump

Power range

  • 227-1348 kW
  • 65.0-383 Ton

Features

  • Structure with supporting frame, made of galvanised sheet metal with additional protection provided by polyester powder coating.
  • Screw compressors with built-in oil separator, suction filter, crankcase heater, oil sight glass, thermal protection and stepless capacity steps.
  • Axial fans directly coupled to an electric motor with external rotor.
  • Condenser made of copper tube and aluminum finned coils.
  • Shell and tube evaporator with two independent circuits on the refrigerant side and one on the water side, complete with water differential pressure switch.
  • Cooling circuit shut-off valves on discharge and liquid line.
  • Electronic expansion valve.
  • Electronic high and low pressure gauges.
  • R134a refrigerant. On request R513A refrigerant.
  • Electrical board includes: main switch with door safety interlock, fuses, thermal protection relays for compressors and thermocontacts for fans.
  • Condensing Control is included: electronic proportional device that ensures efficient and continuous functioning of the unit with outside air temperature down to 0 °C in cooling mode. It also allows to reduce the sound level especially at night. It consists of a fans speed controller with continuous speed regulation and high and low pressure transducers on cooling circuit.
  • Functioning in heating mode with outside air temperature down to -10 °C.
  • Microprocessor control and regulation system.

Factory fitted accessories

  • IM Automatic circuit breakers
  • RE Adjustable minimum/maximum voltage and phase control relay
  • SL Unit silencement
  • DSV Double relief safety valve with changeover switch on the high pressure side for each refrigerant circuit
  • DSVHL Double relief safety valve with changeover switch on the high and on the low pressure side of each refrigerant circuit
  • CC Condensing control down to -20 °C
  • BT Low water temperature kit
  • EC EC Inverter fans
  • HR Desuperheater
  • HRT/S Total heat recovery in series
  • HRT/P Total heat recovery in parallel
  • TX Coil with pre-coated fins
  • EW External water connections
  • SP Inertial tank
  • PU Single circulating pump
  • PUI Inverter single circulating pump
  • PD Double circulating pump
  • PDI Inverter double circulating pump
  • SPU Inertial tank and single circulating pump
  • SPUI Inertial tank and Inverter single circulating pump
  • SPD Inertial tank and double circulating pump
  • SPDI Inertial tank and Inverter double circulating pump
  • GS Single circulating pump gasket for glycol >30%
  • GD Double circulating pump gaskets for glycol >30%
  • FE Antifreeze heater for evaporator
  • FX Antifreeze heater for evaporator and pipes
  • FB Antifreeze heater for evaporator/tank
  • FQ Antifreeze heater on evaporator, tank and pipes
  • FZ Antifreeze heater for evaporator, single pump and pipes
  • FH Antifreeze heater for evaporator, double pump and pipes
  • FU Antifreeze heater for evaporator, tank, single pump and pipes
  • FD Antifreeze heater for evaporator, tank, double pump and pipes
  • II Inverter on one compressor and soft start for other compressors
  • ID Inverter on all compressors
  • SS Soft start
  • WM Web Monitoring - Wireless remote monitoring (4G)
  • IS Modbus RTU protocol, RS485 serial interface
  • IST Modbus TCP/IP protocol, Ethernet port
  • ISBT BACnet IP protocol, Ethernet port
  • ISB1 BACnet MSTP protocol, RS485 serial interface, BTL certified
  • ISBT1 BACnet IP protocol, Ethernet port, BTL certified
  • ISS SNMP protocol, Ethernet port
  • MTS Master/Slave Network Management
  • IAV Remote set-point, 0-10V signal
  • IAA Remote set-point, 4-20mA signal
  • IAS Remote signal for second set-point activation
  • IDL Demand limit from digital input
  • CP Potential free contacts
  • MN High and low pressure gauges

Loose accessories

  • CR Remote control panel
  • RP Coils protection metallic guards
  • AG Rubber shock absorbers
  • AM Spring shock absorbers
  • FL Flow switch
1302150217021902200226023002360242024802500254026002
CoolingCooling capacity (1)kW2272703213674115096187508561005111612281348
Absorbed power (1)kW99117134154171209256302361414443518566
Cooling capacity (2)kW2633133594134645746968399591136126413981533
Absorbed power (2)kW8296114131146179219256305352380440480
EER (2)3,213,263,153,153,183,213,183,283,143,233,333,183,19
Cooling (EN14511)Cooling capacity (2)kW2623123584124635736948379561132126313971532
Absorbed power (2)kW8397115132147180221258308356383444485
EER (2)3,163,223,113,123,153,183,143,243,103,183,303,153,16
HeatingHeating capacity (3)kW2723243724284805947218699931176---------
Absorbed power (3)kW81,095,0113130144177217253302348---------
COP (3)3,363,413,293,293,333,363,323,433,293,38---------
Heating (EN14511)Heating capacity (3)kW2733253734304825967238729961180---------
Absorbed power (3)kW83,097,0116133147181222259309356---------
COP (3)3,293,343,233,233,273,293,263,363,223,31---------
CompressorQuantity2222222222222
Refrigerant circuits2222222222222
Capacity stepsSteplessSteplessSteplessSteplessSteplessSteplessSteplessSteplessSteplessSteplessSteplessSteplessStepless
EvaporatorWater flowl/s12,5714,9517,1519,7322,1727,4233,2540,0945,8254,2860,3966,7973,24
Pressure dropskPa30264944342842343948384659
Water connectionsDN125125150150150150150200200200250250250
Electrical characteristicsPower supplyV/Ph/Hz400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50400/3/50
Max. running currentA2012372613013373934855806647209228761002
Max. starting currentA263281337361405504596785827855126712611379
Unit with tank and pumpPump available static pressurekPa13015015514017516016514512016014095180
Tank water volumeL20002000200020002000200030003000---------------
Water connectionsDN100100100125125150150150200200200200200
Sound pressureSTD versions (4)dB(A)76767676777677777778797980
STD versions with SL accessory (4)dB(A)73737373747374747475767677
Weight STD versionsOperating weight (5)kg3690374038504390507055406790807081709230101601089011270
Transport weight (5)kg356236093708420747825202649674307484877396401038010800

Dimensions

1302150217021902200226023002360242024802500254026002
LSTDmm4400440050005550620067008900111001110011100134001340013400
WPmm55505550555077507750890010050134001340013400---------
WSTDmm2200220022002200220022002200220022002200220022002200
WPmm2200220022002200220022002200220022002200---------
HSTDmm2100210021002100210021002100210021002500250025002500
WPmm2100210021002100210021002100210021002500---------

Notes

  • 1 Chilled water from 12 to 7 °C, ambient air temperature 46 °C.
  • 2 Chilled water from 12 to 7 °C, ambient air temperature 35 °C.
  • 3 Heated water from 40 to 45 °C, ambient air temperature 7 °C d.b./6 °C w.b.
  • 4 Sound pressure level measured in free field conditions at 1 m from the unit. According to ISO 3744.
  • 5 Unit without tank and pump.
  • N.B. (1) Weights of WP versions are specified on technical brochure.